26
OLCT10N
Manual
Sensor specifications
Gas
Measurement
range
(ppm)
Temp.
range°C
Accurcay
Life Expectancy T
50
/ T
90
(months)
(sec)
CO
Carbon
monoxide
300
1000
-20 to
+50
+/- 5
36 15/40
H
2
S
Hydrogen
sulfide
30
100
-40 to
+50
+/- 5
36 15/30
NH
3
Ammonia
100
1000
-20 to
+40
+/- 5
24
25/70
24 20/60
NO
Nitric
Oxide
100
300
-20 to 50
+/- 5
36 10/30
36
NO
2
Nitrogen
dioxide
10
30
-20 to 50
+/- 5
24 30/60
O
2
Oxygen
0-30% vol
-20 to
+50
0.4 % vol
(from 15 to
22 % O
2
)
28 6/15
Line length (use with MX43)
Below is a table which gives the maximum distances in meter (in feet) of wiring
OLCT10N transmitters to the MX43 based on cable size when connected on a
single line of without the need of an external power supply.
Number of toxic OLCT10N
transmitters
Cable core size
0.9 mm²
(AWG 18)
0.5 mm²
(AWG 20)
0.22 mm²
(AWG 24)
10
1000 (3200)
20
1000
(3200)
900 (2950)
25
1000
(3200)
500 (1600)
32
1000 (3200)
800 (2625)
300 (980)
Содержание OLCT10N
Страница 1: ...x P N NPO10NGB Rev A Digital Transmitter OLCT10N...
Страница 23: ...23 Chapter 6 Declaration of EC conformity...
Страница 24: ...24 OLCT10N Manual...