TROuBLeSHOOTING:

Problem

Possible cause & solution

Channel Led does not light up

(when in learning mode)

Check that the power Led is flashing quickly. If it is not, switch dIP-3 to ON position.

2-wire bus may be incorrectly connected. Voltage at each room sensor should be no lower than 4.0V (check 

for + & - continuity and short circuits). 

With wireless room sensors, check that the batteries have been inserted correctly.

With wireless room sensors, check whether the initialize button has been pressed. 

With wireless room sensors, check that the WLRC3-19 (receiver) has been connected correctly.

If the Leds for channel 9-14 do not light up, check that the AO module has been connected to the master 

correctly.

Check that the room sensor in the room has been set to the correct channel number.

The channel selector on the room sensor may be slightly out of position, try rotating it and then set it again.

Channel Led does not light up

(when in install mode after the room sensor 

has been activated (set to maximum))

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

The master itself has cancelled install mode. After 2 hours the master automatically de-activates install 

mode. Reset dIP-1.

Check that the room sensor in the room has been set to the correct channel number (two room sensors 

might be interchanged). 

The actuator on the manifold does not 

open after 3 minutes

Check that the red channel Led is lit (if not, see above).

The actuator for the room is not connected to the correct output on the master.

Bad electrical connection between actuator and terminals.

The actuator may be faulty or manually locked.

uFH pump does not start in install mode

Bad electrical connection between pump and terminals.

Install mode has not been activated. Move dIP-1 to the OFF position and then back to the ON position.

The pump may be faulty.

Содержание WLM3

Страница 1: ...WLDT3 WLM3 WLCT3 WLTD3 WLTA3 Installation Quick Guide www ojelectronics com 67347 02 15 HKT...

Страница 2: ...2 2015 OJ Electronics A S Installation Quick Guide Page 3 Setting up the system Page 5 Wireless system only Page 5 Testing the system Page 6 Troubleshooting Page 7 CONTENTS QUICK GUIDE...

Страница 3: ...LRC3 using the special cable included in the box NB For room sensors controllers with floor temperature limitation sensors please refer to the separate instructions included with the unit Installation...

Страница 4: ...or bus or direct to master maintaining continuity of positive and negative connections Connect 230V AC power supply UFH circulating pump and boiler in accordance with electrical regulations With FS ma...

Страница 5: ...press the OK button to go to the next channel CH 2 and repeat this step until all the required channels have been set 3 5 After all channels have been set select the ESC menu entry and press OK NB If...

Страница 6: ...nel 1 LED should light up and the actuator on output 1 should activate Important If the room sensor controller is of wireless type a delay of up to 5 minutes may occur before the channel LED lights up...

Страница 7: ...nel number The channel selector on the room sensor may be slightly out of position try rotating it and then set it again Channel LED does not light up when in install mode after the room sensor has be...

Страница 8: ...ical connection between boiler and terminals During install mode the boiler relay will not operate The attached boiler may be faulty LED not lit Timing sequence delay is activated FS master only mixin...

Страница 9: ...ay be causing large heat loss Room is too hot after running for at least 48 hours This might be caused by draughts caused by internal wall cavities or open doors or windows which affect the temperatur...

Страница 10: ...10 2015 OJ Electronics A S...

Страница 11: ...11 2015 OJ Electronics A S...

Страница 12: ...ark warminster wiltshire ba12 8sp united kingdom T 44 01985 213 003 F 44 01985 213 310 sales ojuk co uk www ojUK co uk OJ ELECTRONICS A S c o Robert Bielecki UL walbrzyska 33 58 160 SWIEBODZICE POLska...

Отзывы: