SeTTING uP THe SySTeM

1.    

Turn on the power and perform a full reset of the master by pressing the OK button for 16 seconds until all the area Leds flash alternately 

 

  (the unit must be in dAy temperature mode - sun symbol). 

2.

  Set the clock on any WLCT3 room controller. 

 

  2.1.  If the hour digit is not flashing, press the small pinhole button beside the clock symbol.

 

  2.2.  Adjust the hours and press OK.

 

  2.3.  Adjust the minutes and press OK.

 

  2.4.  Adjust the day number (1 = Monday) and press OK. 

3.

   In addition to the settings for its own room, the WLCT3 room controller can be used to set the operating times and temperatures of other room sensors 

(channels).

 

   To achieve this, do the following on the WLCT3 room controller: 

 

  3.1.  If “CH 1” is already shown on the display of the WLCT3 room controller, proceed directly to step “3.4”.

 

  3.2.  Press the uP and dOWN buttons simultaneously for 4 seconds to enter the “InFo” menu.

 

  3.3.  Press the uP and down Buttons to locate the “AreA” menu and then press OK.

 

  3.4. The display now shows “CH 1” (channel 1).

 

   

-  Press the OK (√) button.

 

   

-  Select “On” if this channel (room sensor) is to be controlled by the WLCT3 room controller by pressing the ‘dOWN’ button, otherwise select “OFF”.

 

   

-  Now press the OK button to go to the next channel (CH 2) and repeat this step until all the required channels have been set.

 

  3.5.  After all channels have been set, select the “eSC” menu entry and press OK.

  

NB: If different times and temperatures are required for other channels (room sensors) within the system, more than one 

WLCT3 room controller

 can be 

used. Care must be taken to ensure that a channel is not set to “On” on more than one 

WLCT3 room controller

.

AddITIONAL STePS FOR WIReLeSS SySTeM:

Learning mode button

BR1026A09

a

© 2015 OJ Electronic  

A/

S

Channal

selector

-G

B

Jumper

Button learning

mode

BR1026A09a

BR1025A10a

© 2015 OJ Electronic  

A/

S

9

10

-G

B

ON

OFF

Common UHF-PUMP

Commission mode

X-RELAY

Learn mode
Boiler test
Install mode

WLM2 Compatible

ON / OFF Control

BR1025A10a

4. 

Switch on dIP-3 to activate learning mode. 

5. 

All wireless room sensors/controllers must now be initialized:

 

 

-   Initialize analogue room sensors (WLTA3, WLTd3, WLTM3) by 

removing the plastic battery pull tab or pressing the internal 

initialization button (learning mode button) until a beep is heard.

 

-   Initialize digital room sensors/controllers (WLCT3 and WLdT3) by 

pressing the pinhole button (learning mode button) beside the clock or 

I until a beep is heard.

  

When communication with a room controller/sensor has been 

established, the corresponding channel Led on the master will light up. 

6.  

Switch off dIP-3 to deactivate learning mode:

Содержание WLM3

Страница 1: ...WLDT3 WLM3 WLCT3 WLTD3 WLTA3 Installation Quick Guide www ojelectronics com 67347 02 15 HKT...

Страница 2: ...2 2015 OJ Electronics A S Installation Quick Guide Page 3 Setting up the system Page 5 Wireless system only Page 5 Testing the system Page 6 Troubleshooting Page 7 CONTENTS QUICK GUIDE...

Страница 3: ...LRC3 using the special cable included in the box NB For room sensors controllers with floor temperature limitation sensors please refer to the separate instructions included with the unit Installation...

Страница 4: ...or bus or direct to master maintaining continuity of positive and negative connections Connect 230V AC power supply UFH circulating pump and boiler in accordance with electrical regulations With FS ma...

Страница 5: ...press the OK button to go to the next channel CH 2 and repeat this step until all the required channels have been set 3 5 After all channels have been set select the ESC menu entry and press OK NB If...

Страница 6: ...nel 1 LED should light up and the actuator on output 1 should activate Important If the room sensor controller is of wireless type a delay of up to 5 minutes may occur before the channel LED lights up...

Страница 7: ...nel number The channel selector on the room sensor may be slightly out of position try rotating it and then set it again Channel LED does not light up when in install mode after the room sensor has be...

Страница 8: ...ical connection between boiler and terminals During install mode the boiler relay will not operate The attached boiler may be faulty LED not lit Timing sequence delay is activated FS master only mixin...

Страница 9: ...ay be causing large heat loss Room is too hot after running for at least 48 hours This might be caused by draughts caused by internal wall cavities or open doors or windows which affect the temperatur...

Страница 10: ...10 2015 OJ Electronics A S...

Страница 11: ...11 2015 OJ Electronics A S...

Страница 12: ...ark warminster wiltshire ba12 8sp united kingdom T 44 01985 213 003 F 44 01985 213 310 sales ojuk co uk www ojUK co uk OJ ELECTRONICS A S c o Robert Bielecki UL walbrzyska 33 58 160 SWIEBODZICE POLska...

Отзывы: