Press the pin button for 3 secs. and the thermostat returns to factory settings. Time
and day is also reset and must be set according to “Setting the thermostat into
operation”.
5. Reset to factory setting
4-event time and temperature
Day 1-5
06:00
Time
Temperature
08:00
16:00
22:30
08:00
23:00
Hi-Low temp.
5:2
24 H / ˚C
ON
4-event sequence
Scale
Adaptive control
Day 6-7
25˚C
OCC2-1991
w/floor sensor
OCC2-1999
w/room sensor
20˚C
15˚C
22˚C
15˚C
22˚C
15˚C
28˚C / 15˚C
20˚C
27˚C
20˚C
27˚C
20˚C
55˚C / 5˚C
6. Failure codes
E0 =
Internal failure, replace thermostat
E1 =
Built-in sensor short-circuit or disconnected, replace thermostat
E2 =
External sensor short-circuit or disconnected