4 Setup System
4.1. Set after-run
To ensure that all ice and snow is completely melted, the heating system will stay
on for a specified time after there is no longer any need to melt snow If some ice
and snow remains after the heating system has been deactivated, the after-run time
should be increased slightly The longer the afterheat duration, the more effective
and less economical the system will be
On DIP switch 1-4, you can set the after-run time It can be set between 2 and 17
hours