2 Technical data
2.1 Heat pump technical data
Dimensions and weight
Measurements without
cover and extra legs
S 180
S 280
S 380
S 490
S 600
Height (mm)
2091
2091
2091
2091
1900
Width (mm)
2723
2723
2723
2723
4700
Depth (mm)
911
911
911
911
1000
Weight (kg)
2300
2900
3600
4000
3200
Measurements without
cover and extra legs
S 800
S 1000
S 1200
S 1500
S 2000
Height (mm)
1900
2100
2100
2190
2190
Width (mm)
4700
4700
4700
5500
5500
Depth (mm)
1000
1100
1100
1600
1600
Weight (kg)
4000
4500
5300
6500
7500
Connections
For information on pipe connections, see connection diagrams delivered with the
ChillHeat pump.
S 180
S 280
S 380
S 490
S 600
Electrical
connections
3 L / PE / 400 VAC 50 Hz, ask for other alternatives
Fuse size (A)
250
355
400
500
2x3x400
S 800
S 1000
S 1200
S 1500
S 2000
Electrical
connections
3 L / PE / 400 VAC 50 Hz, ask for other alternatives
Fuse size (A)
2x3x400
2x3x630
2x3x630
2x3x800
2x3x1000
Refrigerant circuit
The fill quantities according to the table below are normative.
The amount of the refrigerant varies depending eg. on the heat pump
exchanger option, other accessories and conditions.
Always check the exact amount of the refrigerant from the heat pump’s
type plate.
S 180
S 280
S 380
S 490
S 600
Refrigerant
R134A
R134A
R134A
R134A
R134A
Refrigerant (kg)
30
55
60
95
2 x 75
CHS01 1951EN
9 (63)