34
−
Item
Upper
display
Description/setting range
Factory
setting
Sensor
correction
-100.0
℃
to 100.0
℃
0
Reference
junction
compensation
Reference junction compensation
: Disabled,
: Enabled
Square root
: Disabled,
: Enabled
Input cutoff
level
Input cutoff level at square root.
0.0 to 25.0%
10.0
First order lag
0 to 20 sec.
0
Moving
average
Moving average times
1 to 8
8
PV error upper
limit
1402
PV error lower
limit
-1999 to +9999 (decimal point position
follows the setting.)
-231
SU2 Control/output
n: Output No. (n=1,2)
Multi output
: Current,
: SSR drive,
:
Relay
Control mode
: PID control (both outputs for dual
output)
: PD control (both outputs for dual
output)
: ON-OFF (both outputs for dual
output)
: PID for 1st ON-OFF
control for 2nd output
: ON-OFF for 1st PID
control for 2nd output
Control
direct/reverse
action
・
Control action
: Reverse action,
: Direct action
Gapped control
: Disabled,
: Enabled
Cycle time
n
.
Output cycle time 1 to 120 sec.
Cycle type = Output ON time + output
OFF time
60
Output
hysteresis
width
n
.
0.00 to 20.00%
0.10
Preset value
Preset output value lower limit to upper
limit
0
Use of preset
Use of preset output
: Not used,
: Used
PID mode
Selection of PID to be used during remote
SP execution
: Normal PID,
: Programmed PID
Profiling
Profiling control
: Disabled ,
:
Enabled (master controller)