Input list
5.5 All Reset
All Reset is the operation to return to the factory setting all parameters
except for basic settings. To perform All Reset, press key and
key
simultaneously for more than 3 seconds.
Input
Code
Input range
Input
Code
Input range
TC (thermocouple) input
DC voltage, DC current input
mV
mV
mV
V
V
V
mA
-10.0 to 10.0mV
0.0 to 20.0mV
0.0 to 50.0mV
1.0 to 5.0V
0.0 to 5.0V
0.0 to 10.0V
4.0 to 20.0mA
RTD (resistance temperature
detector) input
Pt
100
-199.9 to 850.0
℃
-199.9 to 300.0
℃
-150.0 to 150.0
℃
B
R
R
S
K
K
K
E
J
J
T
WRe5-
26
N
PR40-20
PL
Ⅱ
U
L
Au-Fe
0 to 1820
℃
0 to 1760
℃
0 to 1200
℃
0 to 1760
℃
-200 to 1370
℃
0 to 600
℃
-199.9 to 300.0
℃
-199.9 to 700.0
℃
-199.9 to 900.0
℃
-199.9 to 400.0
℃
-199.9 to 400.0
℃
0 to 2320
℃
0 to 1300
℃
0 to 1880
℃
0 to 1390
℃
-199.9 to 400.0
℃
-199.9 to 900.0
℃
0.0 to 300.0K
JPt
100
-199.9 to 650.0
℃
-199.9 to 300.0
℃
-150.0 to 150.0
℃
[Caution] Data initialization by All Reset
All Reset maintains the following items and initializes all other items.
Group
Maintained item
SU1
Input type, reference junction compensation, square
root, input cutoff level (when square root is used),
scaling
SU2
Output type (at multi output), control mode, control
reverse/direct action, cycle time, output hysteresis width
SU3
DO function selection
SU4
DI
function selection, SP No./PID No. selection
SU6
Communication address, Baud rate, communication
type