background image

Ohio Medical Corporation., 1111 Lakeside Drive, Gurnee, IL 60031-4099 (800/448-0770) www.ohiomedical.com 

Medical Gas Alarm Manual  

  255098 (Rev.8) 07/08 

Page 17 

4.4  Master Alarm Connections from Source Equipment 
 

Each Master Alarm Panel may accommodate up to 10 alarm inputs.  Dry Contacts from 
source equipment are connected directly to the Master Alarm Panel circuit board at positions 
“MA1” through “MA10”. Each of these contact points is clearly marked on the circuit board 
and includes both positive (+) and negative (-) terminals.  The dry contacts from the source 
equipment must be rated for at least 12 V

DC

WARNING —  T

HE

 

EQUIPMENT

 

THAT

 

IS

 

CONNECTED

 

TO

 

THIS

 

INTERFACE

 

IS

 

NOT

 

CONSIDERED

 

TO

 

BE

 

PART

 

OF

 

THE

 

SYSTEM

 

CONFIGURATION

 

UNLESS

 

THE

 

EQUIPMENT

 

IN

 

QUESTION

 

COMPLIES

 

WITH

 

THE

 

STANDARD

 

FOR

 

HOSPITAL

 

AND

 

SIGNALING

 

AND

 

NURSE

 

CALL

 

EQUIPMENT

, UL 1069

 

The “Maintenance Mode” switch needs to be on to disable the audible alarm while wiring 
contacts to the master alarm module. To make the Maintenance switch active, move the 
switch at position “S11” on the Master Alarm Module toward the row of switches labeled “S1” 
to “S10” as shown in Figure 8A. The maintenance lamp will be illuminated on the front of the 
panel.  Moving the switch away from the row of switches will restore the Master Alarm to 
normal operation. 
 
Switch settings on the Master Alarm Panel must be set to configure each alarm point for 

normally open or normally closed operation.  As shown on Figure 8A, the switches are on 
the headers labeled “S1” through “S10”.  The switches at position “S1” corresponds to the 
alarm connected to the first pair of contacts “MA1”, “S2” to “MA2”, “S3” to “MA3”, and so on. 

 
If one of the S1 through S10 switches is positioned toward the “S11” switch, the circuit loop is 

normally open. It will cause an alarm when a closed contact is applied to the input terminal 
strip (MA1-MA10).  The switches at positions S1 & S3-S10 are shown in this position in 
Figure 8A.  This is the factory default setting.  Any pair of contacts that are not connected to 
source equipment should have their corresponding switch positioned toward the 
maintenance switch. 

 
If one of the S1 through S10 switches is positioned away from the S11 switch, the circuit loop 

is normally closed. The contact will create an open circuit loop when an alarm condition 
exists.  The S2 switch is shown in this position in figure 8A.  This is the setting for input 
contact that is closed during normal operation but open during an alarm condition. 

 
Per NFPA 99, information relayed from the source equipment is to be sent to two separate 

master alarm panels at separate locations inside the medical facility. Wiring from the 
source equipment is to be ran in parallel to each master alarm module and can not to be 
slaved from one master alarm panel to the another.  

 

Содержание Area

Страница 1: ...Medical Gas Alarms OHIO MEDICAL CORPORATION P N 255098 Rev 8 07 08 Installation and Maintenance Manual Area Alarm Master Alarm Combo Alarm...

Страница 2: ...Ohio Medical Corporation 1111 Lakeside Drive Gurnee IL 60031 4099 800 448 0770 www ohiomedical com Medical Gas Alarm Manual 255098 Rev 8 07 08 Page 2 NOTES...

Страница 3: ...RING A VARIETY OF VERY WELL KNOWN TRADE NAMES TODAY IN THE THIRD GENERATION OF FAMILY OWNERSHIP AND MANAGEMENT SQUIRE COGSWELL COMPANY CONTINUES TO SERVE THE WORLDWIDE NEEDS FOR HOSPITAL VACUUM PUMPIN...

Страница 4: ...to Drywall Plaster Installation 12 4 2 Installation Wiring Instructions After Drywall Plaster Installation 13 4 3 Area Alarm Remote Output Signal Connections 16 4 4 Master Alarm Connections From Sourc...

Страница 5: ...Should such repair or replacement become necessary contact Ohio Medical Customer Service 800 448 0770 for original equipment replacement parts 2 0 System Description Function The Ohio Medical Corpora...

Страница 6: ......

Страница 7: ......

Страница 8: ...the pressure input increases above a specified high set point When the pressure or vacuum decreases below a specified low set point When an alarm condition is detected on the Master Alarm Module When...

Страница 9: ...as dry contacts on the backside to connect to a pair of contacts on a Master Alarm Module for remote monitoring purposes 2 4 Master Alarm Panel The Master Alarm Panel monitors dry contacts from source...

Страница 10: ...ead screws attaching the circuit board to the weldment plate 4 Extract the area alarm PCB Weldment assembly from the front panel assembly 5 Either slide required label through pocket provided in mylar...

Страница 11: ......

Страница 12: ...udes adjustable brackets to allow for varying wall thickness and for ease of installation 1 Remove the power supply cover 2 Install the brackets to the left and right sides of the box assembly using t...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Alarm Panel are contacts to be used to transmit an alarm condition to a Master Alarm Panel or to other slave alarm device if required These contacts may be used to transmit either a High Alarm or Low...

Страница 17: ...ration Switch settings on the Master Alarm Panel must be set to configure each alarm point for normally open or normally closed operation As shown on Figure 8A the switches are on the headers labeled...

Страница 18: ...B Each of these pairs of contacts are clearly marked on the circuit board and includes both positive and negative terminals The dry contacts going to the other alarm devices or a building management s...

Страница 19: ...er power source to supply the necessary power To connect a remote buzzer which is similar to the one installed on the Annunciator panel 1 Connect the 24V terminal to the positive power terminal of the...

Страница 20: ...s the user desires to change the default settings If the standard default values do not match the desired configuration the user can change program configuration data and save them All programming is...

Страница 21: ...8A FAC Setting type FAC for utilizing Factory default Setting changes parameter type saves selection goes to step 8B or 8C Exits Module returns to step 5 or USr for user to utilize own perferred Sett...

Страница 22: ...condition will not be acknowledged if the vacuum reaches the HSP setting Range Working Default Default Default Gas Types Setting Pressure HSP LSP Normal 2 Corresponding Step 7 Range Step 8 Step 9 Pres...

Страница 23: ...matches the number of sensors and area alarm modules the alarm is using press the S key 4 Press the S key to advance to step 4 5 Press the S key to advance to step 5 if resound interval is not being...

Страница 24: ...hown is rAn9 and then variables shown 7 table A or B in chapter 5 2 8 High set point first shown is HSP second is either FAC 8 or Usr and then the high set point value being implemented 9 Low Set Poin...

Страница 25: ...egrator is available from the factory upon request 7 0 Specifications Summary Cable Requirement for a Area alarm module to remote sensor b Master alarm module to source equipment c Dry contact master...

Страница 26: ...o the Annunciator in the wrong sequential order Check programming Sensor s Pressure Range is not correct for sensor board being used SENr is displayed when alarm is turned on Check if the number of se...

Страница 27: ...ircuit Board with Weldment Overlay 263061 Dry Contact Master Alarm Circuit Board with Weldment Overlay 261561 Dual Area Alarm Circuit Boards w Weldment Overlay MOUNTING PLATES PIPING STRUCTURAL COMPON...

Страница 28: ...nsor w Demand Check EVAC 261849 7 Local Sensor w Demand Check CO2 261581 1 Remote Sensor w Demand Check OXYGEN 261581 2 Remote Sensor w Demand Check VACUUM 261581 3 Remote Sensor w Demand Check N2O 26...

Страница 29: ...hio Medical Corporation a Before returning any part or component to the factory proper return authorization must first be obtained from Ohio Medical Service Department b The user will be required to i...

Страница 30: ...Ohio Medical Corporation 1111 Lakeside Drive Gurnee IL 60031 4099 800 448 0770 www ohiomedical com Medical Gas Alarm Manual 255098 Rev 8 07 08 Page 30 NOTES...

Страница 31: ...Ohio Medical Corporation 1111 Lakeside Drive Gurnee IL 60031 4099 800 448 0770 www ohiomedical com Medical Gas Alarm Manual 255098 Rev 8 07 08 Page 31 NOTES...

Страница 32: ...N Phone 800 448 0770 or 847 855 0500 Fax 847 855 6300 Email info ohiomedical com http www ohiomedical com For 24 7Technical Support call 847 855 6234 for assistance LonWorks is a registered trademark...

Отзывы: