Merlin CT1200S

 

 

 

 

 

                                         

User Guide 

 

 

Rev: 03    05-23

 

6  

Panel LED Status 

 

 

Power  

When the system is connected to the mains 
supply, the Power LED will illuminate.  

If no power is present, this LED will not light up.  

 

Gas on  

When the fans are running at the correct 
speed and the key switch is turned on, the 
CT1200S will open the gas valve and the 

green ‘Gas On’ LED will illuminate.

  

ON = Gas On     

OFF = Gas Off  

 

EM Stop  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will 
illuminate AMBER and the gas will be turned off.  

OFF = OK  

ON = Emergency Stop button pressed 

 De-press the button and reset the system. 

 

Supply Fan  

Under normal working the LED will illuminate GREEN. If a supply fan fault is present, the LED will 
be flashing. If the LED flashes for more than 20 seconds, the gas will be shut off. 

ON = OK  

FLASHING = the supply fan is not running. 

 

Extract Fan 

Under normal working the LED will illuminate GREEN. If a supply fan fault is present, the LED will 
be flashing. If the LED flashes for more than 20 seconds, the gas will be shut off. 

ON = OK  

FLASHING = the extract fan is not running. 

 

Fan Fault 

Under normal working conditions this LED is off. If a fan fault is present for more than 20 seconds, 
the LED will illuminate AMBER. 

OFF = OK  

ON = the gas supply has been shut off due to a ventilation fault.  

 

IF A FAULT IS FOUND YOU WILL NEED TO CONTACT YOUR SERVICE/MAINTENANCE COMPANY. 

YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR UNLESS YOU ARE QUALIFIED TO DO SO. 

 

 

 

 

 

 

 

Содержание Merlin CT1200S

Страница 1: ...ation Interlock system Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this guide cont...

Страница 2: ...als 4 2 1 POWER IN 4 2 2 TO VALVE 4 2 3 TO BMS 4 2 4 EM REMOTE 4 2 5 FAN PD SWITCHES 4 3 Installation Operation 5 3 1 System ON and OFF 5 3 2 Emergency Shut Off 5 3 3 BMS Integration 5 3 4 Fire Alarm...

Страница 3: ...y holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power it will not work without power This device should...

Страница 4: ...on COM and normally open N O These are volt free connections 2 4 EM REMOTE The terminal for remote emergency shut off buttons is detailed on the circuit board as EM REMOTE These connections are linked...

Страница 5: ...4 Fire Alarm Integration The Merlin CT1200S can be integrated with a fire alarm to close the gas supply automatically in the event of a signal from the fire alarm panel The volt free fire alarm signa...

Страница 6: ...normal working the LED will illuminate GREEN If a supply fan fault is present the LED will be flashing If the LED flashes for more than 20 seconds the gas will be shut off ON OK FLASHING the supply f...

Страница 7: ...ice NEVER paint the device Paint will seal vents and interfere with the device 6 CT1200S Wiring Spec 1 POWER IN Mains Input 100 240VAC Single Phase 2 TO VALVE Gas Solenoid Valve Power Output 100 240VA...

Страница 8: ...warranty period In no event shall the manufacturer be liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consum...

Отзывы: