BE- IT2698
1/4
ITOE0236-en
Technical Information
OEtroCom-2, OEtroCom-3, OEtroCom-Easy
Control panels
Remplace, remove or add an electronic PCB
Troubleshooting
JS
N°
ITOE0236
-
en
29/09/2020
1.
Make a PCB autodetection
Autodetection allows the identification of the electronic PCBs which are on the appliance and
the correct operation of the system.
Perform an autodetection in the following cases:
- Replacing an electronic PCB on a device
- Removing or adding a PCB to a device
- Cascade: replacing, removing or adding an electronic PCB on one of the devices.
- One of the following error codes appears:
H02.02
,
H02.03
,
H02.36
,
H02.37
,
H02.45
,
H02.46
,…
2.
On OEtroCom-2 control panel
1. If an error code is displayed: clear the error by pressing the
RESET
key,
2. Press the
2 right-hand keys
to access the
Installer Menu
,
3. Enter the code
0012
4. If more than one electronic PCB is displayed: select the main PCB:
- EHC-…
- CU-GH-…
- CU-OH-…
- EEC…
5. Validate
6. Select autodetection parameter
AD
(at the end of the parameter list) and confirm
.
- The autodetection is carried out,
- The main screen is displayed again when the automatic detection is complete.
- The mounted electronic PCBs are visible in the different menus.
EN