background image

 

 

QM- IT2705 

                          2/4 

    ITOE0242-en

 

 

4.

 

Connect the BUS cables 

 

 

1. 

Connect the BUS cables 

B

  between the connector 

X5

  of the master boiler 

A

  and the 

connectors 

X9 / X10

 of the 

CB-01

 boards of the follower boilers, 

2. 

Fit the 

terminating connector C

 to the connector 

X4

 of the master boiler 

A

3. 

Fit the 

terminating connector D 

to the connector 

X10

 of the last of the follower boilers. 

5.

 

Check the parameters 

Set the cascade master boiler parameters (boiler with OEtroCom-3 control panel) as required. 

Access

 : Press menu key    

 

Installation Setup

 

 

SCB-10

 

 

Cascade management B

 

 

Parameters, counters, signals

 

 

Parameters

 :  

 

Code / Text displayed

 

Description / setting

 

AP083 

Enable master func 

Set to enable (1) for the master device.  

On follower boilers, this parameter must be set to deactivate (0). 

NP005 

Cascade Permuta

tion

 

By default the master boiler is numbered 1, but this can be changed with this 

parameter. 

NP006 

Cascade Type 

Select the cascade type: traditional or parallel. 

Management of the cascade of boilers by successive addition or in parallel 

(simultaneous operation) 

0 = Traditional (factory set) (

Successive addition

 of additional boilers) 

1 = Parallel: All boilers start up 

at the same time.

 

NP007 

CascTOutsideHeatParl 

Outdoor temperature that starts all cascaded appliances at the same time. Factory 

setting: 10 °C. 

NP008 

CascTPostRunGenePump 

Minimum overrun time of the appliance pump.  

Factory setting: 4 minutes. 

NP009 

CascInterStageTime 

Waiting time before starting or stopping cascaded devices. 

Factory setting: 4 minutes. Setting: 1 min - 60 min 

NP011 

CascadeTypeAlgo 

Type of cascade algorithm: 0: temperature dependent (factory)  

1: power-dependent 

NP012 

CascPowerRiseTime 

Time available to reach the desired temperature.  

Factory setting: 1 (value multiplied by 10). 

NP013 

CascForceStop Pprim 

Activation (1) or deactivation (2) of the cascade's primary pump. 

AP111 

Can line length 

Cable length for the S-BUS. Select the value that is equal to or larger than the actual 

cable length. 

 

 

 

Содержание GMR 6160

Страница 1: ...roCom 3 or OEtroCom 2 control panel 2 Check the software versions of the circuit boards Check the following points Circuit boards SCB 10 OEtroCom 3 must be in version 1 04 or higher All SCB 10 circuit boards must be at the same version Burner management circuit boards CU GH06 must be in version 2 1 or higher All CU GH06 circuit boards must be at the same version 3 Remove the 2 jumpers from the CB ...

Страница 2: ...arameter NP006 Cascade Type Select the cascade type traditional or parallel Management of the cascade of boilers by successive addition or in parallel simultaneous operation 0 Traditional factory set Successive addition of additional boilers 1 Parallel All boilers start up at the same time NP007 CascTOutsideHeatParl Outdoor temperature that starts all cascaded appliances at the same time Factory s...

Страница 3: ...0 board menu with the rotary button Select and validate parameter Software Version to view the SCB 10 board version On OEtroCom 2 control panel Access the menus by pressing simultaneously the two keys on the right Select the Information Menu and access the menu with key Select the desired PCB using the keys Confirm the selection with Scroll through the parameters using the key the software version...

Страница 4: ...igher and All CU GH06 boards must be at the same version at least 2 1 or higher Appliance concerned Description Reference in spare parts GMR 6160 OEtroCom 3 or GMR 6160 OEtroCom 2 7718238 CU GH06 version 2 1 GMR 6160 OEtroCom 3 7774497 SCB 10_E version 1 04 GMR 6160 OEtroCom 3 7718239 Set of boards SCB 10 SW1 04 CU GH06 SW2 1 ...

Отзывы: