3-3        Electric connections:

 

 

 

CAUTION: before connecting the appliance, make sure that the supply power line is disconnected from the network.

 

 

Characteristics of the general power supply: 

 

 

mode of neutral TT and TN.S; the circuit of heat pump must be connected to an earthing circuit 

 

Connections: 

 

 

The electric installation must be carried out by a professional qualified (like an electrician) according to the rules and standards in 

force in the country of installation. 

 

The power supply of the heat pump must come preferably from an exclusive circuit and having the bodies of lawful protection. 

 

Controller must be installed or indoor wall and the place is easy for use. 

 

Electric protection of which must lay out the heat pump: 

 

 

circuit breaker curves D or standard fuse of protection Am, gauged with 16A 

 

differential protection of 30 mA 

 

In the event of connection to an electrical plug by the user:

 

 

- - The heat pump is being provided with an electric cable, it is possible to connect it with a plug. 

- The plug must be checked in conformity with the power of the appliance by a qualified technician. 

- The plug must be safe from the rain, of easy access to be cleaned and one will have to regularly check the good condition of this plug. 

 

 
 

BEFORE THE STARTUP OF HEAT PUMP, IT IS SIGNIFICANT TO

 

 

INCLUDE/UNDERSTAND THE OPERATING AND THE SETTINGS OF WHICH YOU WILL 

TAKE NOTE IN THE FOLLOWING PARAGRAPHS

 

 

 

3-4 Running of reversible heat pump :

 

 

By using the free energy contained in the ambient air, the heat pump enables to heat the water of the water in a 

very economic way. 

Your  heat  pump  is  a  heat  machine  that  can  transfer  the  heat  from  a  low  temperature  place  (ambient  air)  to  a 

higher temperature place. 

 

Running in heating mode : 

The heat of  the  air is absorbed  by the  cold, liquid  refrigerant, through the evaporator  (radiator  with  wings), in 

which    it’s    vaporized;    then    the    compressor    increases    the    pressure    and    the    temperature,    and    sends    it    into   

the    condenser 

(exchanger) where it loses its heat by transmitting it to the water and it comes back in the liquid state; it loses its pressure and 

cools again into the pressure reducer before returning to the evaporator for a new cycle. 

 

Running in cooling mode or defrosting mode        : 

4 way valve enables to reverse the cycle of the refrigerant ; the liquid fluid is vaporized into the exchanger (that 

becomes the evaporator) by taking the heat of the water of the water, passes into the compressor which heats it then into the 

radiator (which becomes the condenser) where it comes back at the liquid state. 

Note:        Single water heater without cooling water mode; Single water chiller without heating water mode and defrosting mode.

 

 

12 

Содержание KS25-C120

Страница 1: ...AIR SOURCE HEAT PUMP All in one type TOP DISCHARGE WITH DOUBLE DUCTS Installation And Operating Instructions MODEL KS25 C120 KS25 C150 KS25 C200 KS35 C300 FEB 2010...

Страница 2: ...he animals or the objects On no account the importer of this apparatus could not be made responsible for this damage Use of the heat pump this heat pump is intended exclusively with use for which it w...

Страница 3: ...lectric connections p12 3 4 Running of reversible heat pump p12 3 5 Description of the screen of display and control p13 4 Use in standard mode p14 5 Instruction for the fitter 5 1 Devices of control...

Страница 4: ...le to result in death Any wrong handling can cause serious damage to the user and the machine TO NOT DO To follow attentively To be sure of the electric connections To be sure of the disconnection of...

Страница 5: ...ore all the button OFF Do not draw on the power supply cable Well have in hand the plug to disconnect it Fire hazard could occur due to the wrenching of the electric cable Do not touch the plug with w...

Страница 6: ...2 1 Outside 4 3 9 2 8 5 1 11 12 10 7 6 Power Plug Control pannel Air Inlet Air Outlet Temperature Sensor Drainage hole Cold Water Inlet Hot Water Oulet 9 Service valve 10 solar coil inlet 11 solar coi...

Страница 7: ...5 Plastic Base 19 Capillary 33 6 Water tank 20 Defrost sensor 34 7 Motor Capacitor 21 Assistant unit of air outlet 35 8 Compressor capacitor 22 Fan motor 36 9 Compressor 23 Electrical Box 37 10 Circu...

Страница 8: ...695 1825 Air ducts Dimension mm 150 150 Net weight Gross weight kg 55 64 66 75 73 82 81 90 Water Connection Inch 1 1 Capacity of the water tank L 120 150 200 300 Power Supply V Ph Hz 220 240 1 50 220...

Страница 9: ...agram below 0 5m UNIT 0 5m 0 5m 0 5m The ventilator should not blow towards the windows or crossing place There must be more than 1 5M space on the top of the unit The fixing board of the unit must be...

Страница 10: ...lve to fill water Meanwhile open the hot water out valve till water spill over from the hot water out valve It means the tank is full of water Close the tap water in valve check leakage by storing ful...

Страница 11: ...choice Option B Installation in the laundry washing room Hot water heating from room air Optional use laundry drying decalcified water for steam iron Dehumidification Option C Installation in the same...

Страница 12: ...BEFORE THE STARTUP OF HEAT PUMP IT IS SIGNIFICANT TO INCLUDE UNDERSTAND THE OPERATING AND THE SETTINGS OF WHICH YOU WILL TAKE NOTE IN THE FOLLOWING PARAGRAPHS 3 4 Running of reversible heat pump By u...

Страница 13: ...and down It sets the temperature of water and time of dose the heater OFF CLOCK On off To adjust the current hour and functioning timetable To adjust the hour 2 WITHOUT WATER TANK ASSISTANT ELECTRICA...

Страница 14: ...minutes lights Press the button or for increasing or decreasing the minutes Validate in pressing on or wait 10 seconds the display will leave this setting mode by it self Setting of running selected...

Страница 15: ...ifference of compressor star 3 C to 15 C adjustable 3 After setting the value the defrosting setting will exit automatically after several seconds And the system will memorize the last value of each s...

Страница 16: ...the following three terms are met in the same time a T4 7 lasts for a while b compressor runs continuously for more than 5 minutes c Compressor runs accumulative total for 45 minutes the interval betw...

Страница 17: ...ient temperature is more than 4 2 Compressor electric heater Working conditions A When the compressor is not working and ambient temperature is less than 0 electric heater will start B When ambient te...

Страница 18: ...8 Gas Flow Diagram 18...

Страница 19: ...OTOR T2 YV1 CURRENT INDUCTOR FOUR WAY VALVE 1 XT1 YV2 PUBLIC TERMINAL FOUR WAY VALVE 2 C2 FAN MOTOR CAPACITOR 2 XT POWER TERMINAL With Water Tank Electrical Heater RED S CM C BLACK C1 Y G WIRING DIAGR...

Страница 20: ...k plastic conduit to evacuate the condensates is not connected or is stopped The condensates are entailed by the condensation of the humid air on the wings of the evaporator It s quite natural Install...

Отзывы: