Control
29
Menus
ADDDIF TEMP
Additional electrical heater restart determined by water temperature degeneration: it is adjustable from 1 to
10 degree (factory setting is 4 degree); the electrical heater will stop when the water get to setting
temperature, then restarts as soon as the water temperature decrease 4 degree (factory setting)
ADD START : ( 10 to 65 degree adjustable , factory setting is 40 degree )
Electrical heater start water temperature, it is adjustable from 10 - 65°C, factory setting is 40°C, this
means when compressor heat the water temperature over 40°C, then allow the electrical heater to start,
this setting is for energy-saving and water tank heating (WARMWATER) only.
HDO ON ( )
Choose "
" to activate the function 'External signal controls heat pump to start or stop'; there are two
signal connections (NC), when external signal switch on them, the compressor, electrical hearer and motor
will stop running (The water pump will keep running if the operation mode is 'Room heating'); After switch
off them, the compressor, electrical heater, motor will restart and work as previous setting.
This function is for the countries which electricity has two different prices in high peak and low peak that
peak electricity;
they can use signal to stop heat pump when in high peak electricity and start the heat pump when in low
Notice: never input electricity directly to HDO terminals!
OPERATION
TIME
HEATPUMP
ADD 1
0
H
0
H
ADD 2
0
H
ADD 3
0
H
Menu Text
Description
Adjustable by
HEATPUMP
Total operating hours of heat pump since installation.
Operating time will not be reset to zero.
ADD
Total operating hours of auxiliary heater 1
(3kW) since installation. Operating time will
not be reset to zero.
can not
can not
Sub-Menu OPERATING TIME
ADD DELAY : ( 3 to 10 Min adjustable , factory setting is 10M )
Time delay of electrical heater starting: from 3 to 30 minutes adjustable, factory setting is 10 minutes. For
example, since compressor has been running 15 minutes, when 10 minutes
(
factory setting
)
later the
return water temperature remain or decrease, the electrical heater will start automatically.
ADD2
ADD3
(6kW) since installation. Operating time will
Total operating hours of auxiliary heater
will not be reset to zero.
(9kW) since installation. Operating time will
Total operating hours of auxiliary heater
will not be reset to zero.
can not
can not