English 19
P2 parameter group - room unit address
No. Description
Range
P2.1
ROOM UNIT ADDRESS
This setting determines the room unit address. It
can be 1 or 2.
During initial operation, the room unit address is set
automatically.
0 - auto setting
1 - address 1
2 - address 2
S1 parameter group - service parameters
No. Description
Range
S1.2
ROOM TEMPERATURE
This setting determines the sensor used for room
temperature.
Info:
For setting 3, the average value of the installed
and auxiliary sensor is calculated for the room
temperature.
0 - none
1 - built-in sensor
2 - auxiliary sensor (AUX)
3 - built-in and additional
sensor
S1.3
CALIBRATION OF BUILT-IN TEMPERATURE
SENSOR
This setting determines the correction of the tempe-
rature measured by the built-in sensor.
-5,0 ÷ 5,0 °C (
0,0
)
S1.4
AUXILIARY TEMPERATURE SENSOR (AUX)
CALIBRATION
This setting determines the correction the measured
temperature measured by the auxiliary sensor.
-5,0 ÷ 5,0 °C (
0,0
)
S1.5
RELATIVE HUMIDITY SENSOR CALIBRATION
This setting determines the correction of the relative
humidity measured in the room.
-10 ÷ 10 % (
0
)
S1.6
AIR PRESSURE SENSOR CALIBRATION
This setting determines the correction of measured
air pressure.
-100 ÷ 100 mb (
0
)
S1.7
AIR QUALITY SENSOR CALIBRATION
This setting determines the correction of measured
air quality.
-1000 ÷ 1000 (
0
)
S1.8
LIGHT SENSOR CALIBRATION
This setting determines the correction of lighting
measured in the room.
0,5÷ 2 (
1
)