www.odencontrol.se 8
3.
Press the turning module 30R1 in place until it is resting at the surface of the valve flange adapter. Tighten the
clamp collar screws. Check that you can move the valve by hand. Put the valve spindle to closed position. NB
Some valve spindles are changing their axial position in closed position.
4.
Attach P30BU to 30R1 using two M5 and four M8 with washers (and eventually nuts with washers). The
radial seal should not be used with this unit.
5.
Check that the valve/actuator is running smoothly by adding a threaded pin to the M10 thread in the clamp
collar and then rotate the valve.
6.
A pin with a M10 thread could be fitted to the clamp collar and be used as a mechanical stop for ball valves
without mechanical stop. At power failure (break) the threaded pin can be used a handle for controlling the
valve manually.
7.
The ground wire (green/yellow), fitted to the actuators flange, must be connected to a suitable ground point at
the valve.
8.
All threads should be locked by Loctite 243.
9.
Perform a Power Calibration (see section 6) . If the valve does not have a mechanical stop, perform a Position
Calibration or turn the valve spindle to closed valve position with a poly grip spanner. Secure the position
firmly, and perform a Power Calibration by using OVP. Select ”No” for aut. Power Cal after > 8 h power
break in OVP.
P30R2 Turning actuator
1.
Fit the valve flange adapter to the valve.
2.
Press 30R2 to the valve spindle. It is important having a close but not
hard fitting to the valve spindle and also to its key; otherwise the
high positioning accuracy of the Oden Actuator is not used to its full
extent. Do not use a hammer; this may damage the valve spindle.
3.
Check that you can move the valve by hand. Put the valve spindle to
closed position. NB Some valve spindles are changing their axial
position in closed position.
4.
Attach P30BU to 30R2 using two M5 and four M8 with washers (and eventually nuts with washers). The
radial seal should not be used with this unit.
5.
The ground wire (green/yellow), fitted to the actuators flange, must be connected to a suitable ground point at
the valve.
6.
All threads should be locked by Loctite 243.
7.
Perform a Power Calibration (see section 6). If the valve does not have a mechanical stop, perform a Position
Calibration.
P30R3 Turning actuator
1.
Fit the valve flange adapter to the valve.
2.
Release the tapered clamping sleeves and put the turning unit 30R3 in
place until it is resting at the surface of the valve flange adapter.
3.
Turn the valve to closed position.
4.
Fit the 30R3 to the valve flange adapter by the screws.
5.
Turn the coupling gear shaft with its pin to the internal mechanical stop (closed valve position) if the valve
(ball valve) has no own stop and tighten the clamping sleeve. If the valve has its own mechanical stop leave a
free distance between the internal stop pin and the mechanical stop of about 2 mm.
6.
Check that the valve/actuator is running smoothly within the working range by turning the coupling gear by
hand.
NB The internal stop pin at the coupling gear shaft must not hit the other internal mechanical stop when the
valve is in max opened position (normally 20 mA position). If so, you have to decrease the working range in
OVP.
7.
Place the radial seal on the visible gear of P30BU.