DESCRIPTION

UT-MT-0930_1.3_220421 (EN) 

Operation and Maintenance Manual

IRM

12

2.1.1  Generality 

The device IRM performs measure of the insulation resistance of the circuit airport series through the periodic 

application of a voltage of about 800 V

DC

 to an end of the series circuit by measuring the leakage current to the 

ground. The measuring interval can be customised (default: 60 sec). The device IRM can be inserted on the 

series circuit independently on the type of regulator unit and without the need to make changes to the circuit. A 

disconnector switch easily accessible allow the supply control.

A LED display positioned on the front of the device IRM allows to locally view the measured insulation resistance 

value AND alternatively the current values (and voltage, optional) on the series circuit, and the main alarms. All 

the threshold values (pre‑alarm and alarm) can be customised.

The internal connection between the measurement card and the interface card is realized through a pair of optical 

fibres.

The device IRM allows the remote monitoring (optional) of the measured values.

The device is suitable at monitoring series circuits powered by power regulator units not higher than 30 kVA/6.6 A, 

in the measuring field 10 kΩ ÷ 500 MΩ.

2.1.2  Construction detail

The device consists of a case in zinc‑coated steel, painted with thermosetting epoxy powders (colour RAL 7032). 

The internal sides of the device are segregated by panels in polycarbonat, removable only in safety conditions for 

the operator (as indicated on the monitoring plates).

The intake and outlet of the cables of the series circuit and of the supply circuit is foreseen from below through 

suitable cable gland. The protective conductor (min. 10 mm2) must be attested through a terminal stud to the 

screw M8 present on the container. On the bottom in addition there are connectors or cable entry systems for the 

connection of signals (optionals).

The device is predisposed for the wall fastening through suitable fastening system through screws and plugs (not 

provided). A template 330x420 mm allows an easier realization of support holes properly aligned.

2.1.3  Optional devices

 

Series circuit rated voltage reading: the device allows the measuring of the voltage on the series circuit, 

making them available on the local display and on the remote reading.

 

Electromechanical remote signalling: a terminal board on the card or a connector make available the reverse 

contacts (NC, C, NA) to repeat the WARNING, ALARM and MANUAL status.

 

IRMS remote control option: is possible remote monitoring of the values measured from the device, through 

a LONTALK network (standard ISO/IEC 14908-2). A connector type HARTING 5 pin (2 conductors twisted 

pair + shield) ‑supplied‑ allows to easily connect the device to the network.

Содержание IRM

Страница 1: ...EN 06ea44df 4930 4943 9da8 a9181f2c00fe Insulation Resistance Measurement INSULATION RESISTANCE MEASUREMENT SERIES CIRCUITS 6 6A UP TO 30 KVA FIELDBUS CONNECTION LONWORKS MANAGEMENT SOFTWARE SERVER AN...

Страница 2: ...the property of their respective owners The copyrights of this manual are the property of EnergyTechnology S r L The instructions drawings tables and other contained in this manual are of a reserved t...

Страница 3: ...ial property rights 9 1 9 Disposal 9 1 10 Article identification 9 2 DESCRIPTION OF THE DEVICE 2 1 General characteristics 11 2 2 Article number 13 3 INSTALLATION 3 1 Insulation measurement device 15...

Страница 4: ...Page left intentionally blank UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 4...

Страница 5: ...ing in aerodromes Constant current regulator FAA AC 150 5345 10 L 828 Constant current regulator unit without monitoring L 829 Constant current regulator unit with monitoring ICAO Annex 14 Manual of a...

Страница 6: ...3 Safety instructions CAREFULLY READ THIS DOCUMENT The improper use of the equipment or the failure to comply all the precautions indicated implies life danger and serious injury to persons and damag...

Страница 7: ...ing out maintenance or repair 1 5 Definition of operator All operations on devices and on its internal parts must be performed by professional staff properly formed and aware of the risks connected wi...

Страница 8: ...e components in the shortest possible time without prejudice to the fact that for the so called commercial components and more generally for the components supplied by third party manufacturers will o...

Страница 9: ...respondence received by the Supplier or in any case assimilated or gained during the conclusion of the Contract of sale Any right regarding intellectual and industrial property connected to equipments...

Страница 10: ...Page left intentionally blank UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 10...

Страница 11: ...for lighting and signalling in aerodromes Constant current regulator FAA AC150 5345 10 L 828 series circuit with CCR current regulator unit without monitoring L 829 series circuit with CCR current re...

Страница 12: ...ists of a case in zinc coated steel painted with thermosetting epoxy powders colour RAL 7032 The internal sides of the device are segregated by panels in polycarbonat removable only in safety conditio...

Страница 13: ...face A B LonTalk 4P GND Ethernet RJ45 2 2 1 Infeed Cut Out The device IRM is equipped with a cut out for an easier disconnection of the device The disconnection of the supply circuit does not prevent...

Страница 14: ...Page left intentionally blank UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 14...

Страница 15: ...nd with the regulations in force The device periodically performs the measure of the insulation resistance of the series circuit in order to monitor the deterioration of the features of the materials...

Страница 16: ...eatures before installing the device Use the device only in combination with series circuit powered by CCR regulator units by power not higher than 30 kVA compliant with the standard IEC 61822 FAA AC...

Страница 17: ...INSTALLATION UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 17 PROTECTIVE CONDUCTOR min 10mm2 SERIES CIRCUIT max 6 6A 30kVA...

Страница 18: ...INSTALLATION UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 18 REMOTE SIGNALLING...

Страница 19: ...INSTALLATION UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 19 CNS REMOTE SIGNALLING...

Страница 20: ...ent data to local database with the configured interval The supervision software focuses on realizing the calculation of statistics average standard deviation maximum and minimum and of providing a gr...

Страница 21: ...y be interfaced directly with the network structure The IRM _ _ __ _ B measurement devices are equipped with ETHERNET network interface and may be configured with an own IP address to be easily reache...

Страница 22: ...Page left intentionally blank UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 22...

Страница 23: ...possible to close the upstream cut out to supply the device 4 1 Preliminary operations If the device is equipped with a local cut out rotate it in ON position When the device is ONLINE series circuit...

Страница 24: ...4 4 2 Visualization current value and voltage optional The device can monitor the actual current value on the connected series circuit If the device is equipped with the voltage measurement device opt...

Страница 25: ...ual IRM 25 4 3 Parameter management The device is provided already configured with the default values All the parameters can be freely customised on the basis of the customer needs The configurable pa...

Страница 26: ...e if the insulation value falls below the set threshold the WARNING signal activates The overcoming of the threshold is locally signalled by turning on the LED WARNING yellow The same information is t...

Страница 27: ...e if the insulation value falls below the set threshold the ALARM signal activates The overcoming of the threshold is locally signalled by turning on the LED ALARM red The same information is transfer...

Страница 28: ...CE UT MT 0930_1 3_220421 EN Operation and Maintenance Manual IRM 28 4 3 3 Measuring interval The operator can customise the interval of time between one measure of the insulation resistance and the su...

Страница 29: ...treme precision In accordance with the suggestions contained in the document ICAO Airport Service Manual Part 9 Airport Maintenance Practices or on the basis of what reported in the document FAA AC 15...

Страница 30: ...fuses 5x20 1A Delayed 487 0015 2 Interface display card F077 version with relay SESMC0004 Interface display card F077 base version without relay 150 3794 3 Measurement card F058 150 2876 4 Main cut o...

Страница 31: ...Contact us OCEM AT 4 3 39 051 66 56 611 4 4 info ocem com...

Страница 32: ...ocem OCEM AT a division of ENERGY TECHNOLOGY S r l Via della Solidariet 2 1 40056 Valsamoggia Bologna Italy Insulation Resistance Measurement UT MT 0930_1 3_22 04 2021 EN...

Отзывы: