Sauna Heater Manual
Temperature windows display
- - L
o
or - -H
o
1. Thermometer isn’t
connected or cable is broken
2. The temperature is lower
than 0
o
C .
3. The temperature is higher
than 115
o
C
1. -- L
o
C means temperature
sensor hasn’t connected or the
temperature is lower than 0
o
C
check the connection, cable or
change sensor
2. --H
o
C means there is a short
circuit in the temperature
sensor or the temperature is
higher than 115
o
C check the
connection,cable or change
sensor.
3.Change controller.