background image

SPECIFICATIONS 

2OACH 

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE 

Cooling Capacity

 is total BTUH at 80ºDB/67ºWB return air, 95ºF Outdoor  

at high fan speed 

Heating Capacity

 is total BTUH at 70ºDB/60ºWB indoor, 47ºDB/43ºWB 

Outdoor 

Dedicated Circuit and Time Delay fuses/circuit breakers are recommended 

EER is determined at high fan speed, with condenser discharge air ducted 
into another area 
CFM with free discharge 
Amps & Watts at 115/208/460 volts 

         

COOLING

 

AMBIENT

         OPERATING RANGE 65º TO 105º 

        HEATING AMBIENT

         OPERATING RANGE 40º TO 85º 

              NOT APPROVED FOR OUTDOOR 

 

2

 

width

h
e
i
g
h
t

depth

MODEL:  2OACH

1211

1811

2412

3612

3632 3634 6012

6032 6034

COOLING CAPACITY

11,800

16,800

24,020

HEATING CAPACITY

11,000

15,000

22,000

VOLTAGE (V/Phase) at 60Hz

208-230/3 460/3 208-230/1 208-230/3 460/3

AMPS

10.4

14.1

14.9

19.6

17.2

8.7

32

20.4

14.8

TOTAL WATTS

1180

1670

2700

IN-RUSH AMPS

60

75

68

113

93

60

178

162

87

PLUG TYPE

5-15P LCDI 5-20P LCDI 6-20P LCDI 6-30P LCDI L15-30P L16-20P

6-50P

L15-30P L16-20P

EER

8.9

COMPRESSOR

ROTARY

ROTARY

ROTARY

COMPRESSOR HP

1

1.5

2

3

3

3

5

5

5

COMPRESSOR LRA

50

63

48

83

77

35

158

137

52

EVAPORATOR CFM - HIGH

400

600

810

EVAPORATOR MOTOR HP
CONDENSER CFM

580

930

1010

CONDENSER MOTOR HP

1/3

CONDENSATE  TANK
R-410A CHARGE (oz.)

18

40

37

HEIGHT (in.)

38.8

WIDTH (in.)

20.0

DEPTH (in.)

26.8

NET WEIGHT (lb.)

180

380

520

2OACHSPECS10012021

115/1

1200

1950

208-230/1

10.0

10.0

SCROLL

SCROLL

5 Gallon  - STANDARD (Pump Optional)

Pump - STANDARD (20 ft. Lift)

66

80

46.8

52.7

54.3

60,100

53,500

36,050

32,500

3620

6000

24.0

365

31.4

37

41.0

260

485

28.2

28.1

2200

1

1

1/8

1/3

1390

1/8

Содержание 2OACH Series

Страница 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL 2OACH SERIES Portable Air Cooled Heat Pump Form EISM 2OACH 10012021...

Страница 2: ...ontinuous improvement the items and procedures described in this manual are subject to change without notice Please note model and serial number of the 2OACH unit before contacting the factory TABLE O...

Страница 3: ...et When connected to the proper source of electrical power the 2OACH is controlled by a solid state electronic controller with numerous options of temperature and airflow controls that will provide th...

Страница 4: ...APACITY 11 000 15 000 22 000 VOLTAGE V Phase at 60Hz 208 230 3 460 3 208 230 1 208 230 3 460 3 AMPS 10 4 14 1 14 9 19 6 17 2 8 7 32 20 4 14 8 TOTAL WATTS 1180 1670 2700 IN RUSH AMPS 60 75 68 113 93 60...

Страница 5: ...mode and the indoor blower will run continuously at one of six levels of fan speed CONDENSATE TANK PUMP 2OACH units come equipped with a means for handling the condensate generated during the cooling...

Страница 6: ...exhaust duct directs the warm air away from the space allowing the evaporator air to cool the specific area ROOM AIR CONDITIONER When ducted properly the 2OACH can be used as a room air conditioner to...

Страница 7: ...2OACH is a heat pump and the supply air will feel warm but not extremely hot to the touch Nozzle kits can be used for directional heating OUTDOOR FAN DISCHARGE COLD RETURN AIR GRILLE AND FILTER ELECTR...

Страница 8: ...low for plug and receptacle details for all 2OACH models A DAMAGED POWER SUPPLY CORD MUST BE REPLACED WITH A NEW POWER SUPPLY CORD AND NOT REPAIRED UNIT MODEL PLUG CONFIGURATION RECEPTACLE 115 VOLT 2O...

Страница 9: ...SION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 50 AMPS 250 VOLTS WITH GROUNDING TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR LOAD FITTING FOR MODELS 2OACH3632 AND 2OACH6032 AN EXTENSION CORD...

Страница 10: ...h water level is reached a cut out switch will AUTOMATICALLY cycle off the compressor condenser fan TANK LEVEL ADJUSTMENT INSTRUCTIONS An adjustment screw is provided to vary the cut off level of the...

Страница 11: ...9 NOTE IT IS IMPORTANT TO SPECIFY MODEL NUMBER AND SERIAL NUMBER WHEN ORDERING ACCESSORIES 2OACH Optional ACCESSORIES...

Страница 12: ...16 Inch Round 2OACH36 60 DISCHARGE DUCT ADAPTER 2DDA 6 6 Inch Round 2OACH12 2DDA 10 10 Inch Round 2OACH18 24 2DDA 16 16 Inch Round 2OACH36 60 CONDENSATE PUMP KIT UPK 115 115V Models UPK 230 230V Mode...

Страница 13: ...s included to replace a 2ft X 2ft drop ceiling panel where the connection is desired The CK 12 is available for 2OACH12 18 and 24 The ceiling panel kit consists of 8 feet of flexible duct and a 2 X 2...

Страница 14: ...5V 057 012R 230V CONDENSATE PUMP KIT A plug in condensate pump kit is available for applications where emptying the 5 gallon condensate tank is not practical The pump kit consists of a condensate pump...

Страница 15: ...M NOTE When installing the condenser return air plenum with a ceiling panel kit allow for a minimum separation distance of 2 feet between the unit discharge duct and the return air duct It is also rec...

Страница 16: ...rigid to the return air intake to reduce air noise and increase the number of options for solving difficult application problems The plenum attaches to the front of the unit replacing the return air...

Страница 17: ...ge to a 6 inch diameter round duct 2DDA 10 for models 2OACH18 and 2OACH24 converts the evaporator discharge to a 10 inch diameter round duct 2DDA 16 for models 2OACH36 AND 2OACH60 converts the evapora...

Страница 18: ...proper NEMA receptacles refer to Electrical service plug configuration When using extension cords use the proper gauge cord and check cord voltage to the unit TIME DELAY FUSES CIRCUIT BREAKERS ARE REC...

Страница 19: ...is needed to change between cooling and heating modes COOL The system will operate in cooling mode only HEAT The system will operate in heating mode only MOISTURE CONTROL The system operates in the co...

Страница 20: ...l help to avoid freeze ups P4 Adjust the P4 setting to match the actual INSIDE room temperature if needed P10 Use this parameter to display temperatures in the desired units P13 To cycle the evaporato...

Страница 21: ...ours 03 and 486 3486 hours 01 and 59 1059 hours TOTAL HOURS REPRESENTS COMPRESSOR RUN TIME MODEL CODE SETTINGS 2OACH12 P1 65 P2 45 2OACH18 P1 80 P2 50 2OACH24 P1 70 P2 50 2OACH36 P1 85 P2 40 2OACH60 P...

Страница 22: ...to the front panel Unplug the display cable and remove display Install new display and secure Plug in display cable C POWER MODULE To remove the power module remove the rear control box cover Disconn...

Страница 23: ...TOR FAN RUNS BUT COMPRESSOR AND CONDENSER FAN DO NOT START CAUSE SET POINT setting may be too high for cooling or too low for heating REMEDY Make sure set point is adjusted accordingly You should see...

Страница 24: ...them in a solution of warm water and detergent for 10 minutes Then rinsing them clean with hot water and shaking excess moisture from filter CONDENSATE PUMP Condensate pumps come standard on all Size...

Страница 25: ...INTERIOR VIEW Filter Drier Evaporator Blower Motor Condenser Blower Motor Condenser Coil Evaporator Coil Electronic Controller Thermostat Display Cable Condensate Tank Reversing Valve Control Box Hot...

Страница 26: ...24 PIPING SCHEMATIC...

Страница 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24...

Страница 28: ...26 WIRING SCHEMATIC FOR 2OACH3612...

Страница 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR...

Страница 30: ...THREE PHASE MONITOR 28...

Страница 31: ...29 WIRING SCHEMATIC FOR 2OACH3632...

Страница 32: ...30 WIRING SCHEMATIC FOR 2OACH3634...

Страница 33: ...31 WIRING SCHEMATIC FOR 2OACH6032...

Страница 34: ...32 WIRING SCHEMATIC FOR 2OACH6034...

Страница 35: ...ritten instructions or has been altered or modified in any way b Product that has been subjected to any abnormal power conditions such as loss of power power surges voltage irregularities such as brow...

Страница 36: ...___________________________ Purchased from _______________________________ Date Installed _________________________________ For Technical Support or service parts contact our Keep Cool Team at 847 583...

Отзывы: