ACCESSORIES
DISCHARGE AIR NOZZLE KIT ASSEMBLY
The optional discharge nozzle kits are used to direct the conditioned
air to a specific target area. By concentrating the airflow, the noz-
zles increase the air velocity towards production lines to cool per-
sonnel and/or equipment. In server rooms, the nozzles can be used
to direct the airflow through the rack to remove the hot air from the
area of the equipment.
2NK-1
for model 2OACH12
, (2) 4-inch diameter nozzles with an
approximate compressed length of 15 inches. The Approximate
extended length is 21 inches.
2NK-2
for models 2OACH18, 2OACH24
(2) 6-inch diameter nozzles
with an approximate compressed length of 22 inches. The approxi-
mate extended length is 32 inches.
2NK-3
for models 2OACH36 and 2OACH60
, (2) 8-inch diameter
nozzles with an approximate compressed length of 20 inches. The
extended length is approximately 29 inches.
Nozzle Kit
Kit Voltage
UPK-115 115V
UPK-230 208/230V
Replacement Pump Only
057-008R
115V
057-012R
230V
CONDENSATE PUMP KIT
A plug-in condensate pump kit is available for applications where emptying the
5-gallon condensate tank is not practical. The pump kit consists of a condensate
pump with mounting hardware and electrical connections, along with the tubing
required for the drain and discharge of the condensate water.
PARTS LIST
•
Condensate Pump with Mounting
Hardware/Screws
•
Drain hose
•
Tubing
•
Wiring Harness
•
Low Voltage Jumper
•
Hose Clamps
The condensate pump provides for the automatic removal of
condensate water during the cooling process. The pump is
capable of pumping to a 20 foot height, allowing for the
routing of the drain line above the drop-ceiling to a nearby
drain. The pump is controlled by an internal float-switch/
check valve, which turns the pump on and off automatically.
The pump is also equipped with a condensate over-flow
safety switch that will shut down the unit compressor when
the pump is not working properly.
12
The nozzle kits come pre-assembled with the nozzles secured to a mounting plate
and with edge guards. By removing the discharge grille, you can insert the nozzle
kit into the opening without the use of tools.
Содержание 2OACH Series
Страница 26: ...24 PIPING SCHEMATIC...
Страница 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24...
Страница 28: ...26 WIRING SCHEMATIC FOR 2OACH3612...
Страница 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR...
Страница 30: ...THREE PHASE MONITOR 28...
Страница 31: ...29 WIRING SCHEMATIC FOR 2OACH3632...
Страница 32: ...30 WIRING SCHEMATIC FOR 2OACH3634...
Страница 33: ...31 WIRING SCHEMATIC FOR 2OACH6032...
Страница 34: ...32 WIRING SCHEMATIC FOR 2OACH6034...