AirBoss

Deluxe Air-Cooled Portable Air Conditioners

Specifications subject to change without notice

MODEL: PAC

1211 1811 2412

3612

3632

3634 6012

6032

6034

Cooling Capacity 

1

11,800 16,800 24,020

36,050

36,050

36,050

60,050

60,050

60,050

Voltage (V/Phase) at 60Hz

115/1 

208-230/1 208-230/1 208-230/3 460/3

208-230/1 208-230/3 460/3

Cooling Amps 

6

10.4

14.1

14.9

18.1

17.2

8.7

32.0

20.4

14.8

Cooling Watts 

6

1180

1670

2700

3620

3620

3620

6000

6000

6000

In Rush Current (Amps)

77.5

100.5

90

140

122

122

169

140

140

Plug Type

5-15P

5-20P

6-20P

6-30P

L15-30P

L16-20P 6-50P

L15-30P

L16-20P

EER 

3

10.0

10.0

8.9

10.0

10.0

10.0

10.0

10.0

10.0

Compressor HP

1

1 1/2

2

3

3

3

5

5

5

Compressor RLA

9.5

12.3

10.5

13.6

8.8

5.0

27.6

18.1

9.0

Compressor LRA

50

63

48

83

77

35

158

137

62

Evap CFM 

4

400

600

810

1310

1310

1310

1950

1950

1950

Evap Motor HP

1/8

1/8

1/3

1/3

1/3

1/3

1

1

1

Evap Motor Watts

200

210

350

375

375

375

550

550

550

Condenser CFM

580

930

1010

1390

1390

1390

2200

2200

2200

Condenser Motor HP

1/8

1/8

1/3

1

1

1

1

1

1

Condenser Motor Watts

280

450

330

460

460

460

750

750

750

Condensate 5 

Gallon 

Condensate Tank - STANDARD (Pump Optional)   

Pump -STANDARD (20 ft. Lift)

Sound Level 

5

54

60

65

69

78

R-410A Charge Oz.

18

40

37

66

80

(A)  Height with Casters (in.)

37

44 1/2

51

52 

(B)  Width (in.)

20

24 

27 

(C)  Depth (in.)

25

30

35

39

(D)  Height w/o Casters (in.)

32 1/2

39 1/2

45

46 

Net Weight (lb.)

180

260

260

365

485

485

515

Shipping Weight (lb.)

200

285

285

405

525

525

555

Shipping Volume (cu. ft.)

19

28

40

48

380

420

SPECIFICATIONS

1.  Cooling Capacity is total BTUH at 80ºDB/67ºWB return air, 
     95ºF Outdoor at high fan speed
2.  Time Delay fuses/circuit breakers are recommended
3.  EER is determined at high fan speed, with condenser   
     discharge air ducted into another area
4.  CFM with free discharge
5.  Sound Pressure, dB at 5 feet, commercial operation
6.  Amps & Watts at 208 Volts

May operate down to 55º if equipped with hot gas bypass 
(Factory installed)

Ambient operating range 65º to 105º

50 Hz MODELS AVAILABLE - CONSULT FACTORY

Note: Condenser inlet air plenum adds 

13 inches to dimension “C”

D

B

A

C

Содержание AIR BOSSR410A

Страница 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL PAC60 PAC12 AIR BOSS Portable Air Cooled Spot Cooler R410A Models...

Страница 2: ...f the Oceanaire Air Boss spot cooler It is recom mended to read and fully understand the instructions outlined within this manual before operating the Air Boss unit As with all commercial air conditio...

Страница 3: ...ront of the unit while rejecting heat from the top of the unit The Air Boss models range in cooling capacities from 12 000 BTU HR to 60 050 BTU HR to satisfy most space cooling requirements The Air Bo...

Страница 4: ...ser CFM 580 930 1010 1390 1390 1390 2200 2200 2200 Condenser Motor HP 1 8 1 8 1 3 1 1 1 1 1 1 Condenser Motor Watts 280 450 330 460 460 460 750 750 750 Condensate 5 Gallon Condensate Tank STANDARD Pum...

Страница 5: ...of the condensate The pump comes with a 25 foot long vinyl hose that allows for the disposal of the condensate water to a drain The automatic pump is capable of a 20ft lift to handle just about any in...

Страница 6: ...xhaust duct directs condenser air out of the area allowing the evaporator air to cool the specific space ROOM AIR CONDITIONER When ducted the OceanAire AirBoss can be used as a room air conditioner to...

Страница 7: ...t below for plug and receptacle details for all Air Boss models A DAMAGED LCDI POWER SUPPLY CORD MUST BE REPLACED WITH A NEW POWER SUPPLY CORD OBTAINED FROM OCEANAIRE AND NOT REPAIRED UNIT MODEL PLUG...

Страница 8: ...r less weight level of water is desired turn the adjusting screw clockwise Do not exceed 6 full turns counter clockwise CAUTION TURN UNIT OFF BEFORE ADJUSTING SET SCREW BEFORE REMOVING TANK TO EMPTY C...

Страница 9: ...7 CK 12PL 2 Req d for 2DCP 4 CK 12 CK 16 2DDA 6 2DDA 10 2DDA 16 2NK 1 2NK 2 2NK 3 DEP 10 2DEP 12 DEP 16 2DCP 1 2DCP 2 2DCP 4 AIR BOSS UNIT ACCESSORIES...

Страница 10: ...nd PAC12 2DDA 10 10 Inch Round PAC18 24 DDA 16 16 Inch Round PAC36 60 CONDENSATE PUMP KIT PC 1P 115V Models PC 2P 230V Models Not Required for PAC60 s CEILING PANEL KIT CK 12 PAC12 18 24 CK 16 PAC36 6...

Страница 11: ...uct panel and a 16 inch flexible duct Note Drop ceiling spaces should be vented or large enough to handle the warm condenser air Check local codes to assure compliance If longer runs of duct are requi...

Страница 12: ...Boss discharge grill one can insert the nozzle kit into the opening without the use of tools Nozzle Kits Kit Voltage PC 1P 115V PC 2P 208 230V CONDENSATE PUMP KIT PC 1P and PC 2P A plug in condensate...

Страница 13: ...ir plenum with the ceiling panel kits allow for a minimum separation distance of 2 feet between the unit discharge duct and the return air duct s It is also recommended to direct the condenser dischar...

Страница 14: ...configuration and application information DEP 10 for PAC12 transitions the return air opening to 10 inch round duct 2DEP 12 for PAC18 and PAC24 transitions the return opening to a 12 inch round duct D...

Страница 15: ...vaporator discharge to a 6 inch diameter round duct 2DDA 10 for PAC1811 and PAC2412 converts the evaporator to a 10 inch diameter round duct 2DDA 16 for PAC36 and PAC60 models converts the evaporator...

Страница 16: ...n the back of the unit to make certain that the proper power is available for the unit Refer to Specifications section for voltage and amperage requirements For proper NEMA receptacles refer to Electr...

Страница 17: ...ycle Remember the set point must be lower than the room temperature for the unit to start The OUTDOOR and DAY NIGHT buttons are not used and do not effect unit opera tion This is a cooling only thermo...

Страница 18: ...temperature sensing is not bent or damaged 2 To remove the thermostat sub base remove the 2 mounting screws and the 3 wires red yellow green or red white black Make sure the 3 wires do not fall into t...

Страница 19: ...mostat setting may be too high REMEDY Make sure set point is lower than room temperature You should see a snowflake designating that the thermostat is calling for cooling Note there is a 4 minute time...

Страница 20: ...lacing them in a dishwasher or soaking them in a solution of warm water and detergent for 10 minutes Then rinsing them clean with hot water and shaking excess moisture from filter CONDENSATE PUMP Cond...

Страница 21: ...Switch Condenser Blower Condenser Coil Capillary tube Strainer Control Box Casters Evaporator Blower Motor Capacitors Evaporator Coil Evaporator Drain Pan Condensate Tank Condensate Tank Tray Water L...

Страница 22: ...HEMATIC Air Cooled Spot Cooler SUCTION LINE DISCHARGE LINE FILTER DRIER ACCESS VALVES COMPRESSOR EVAPORATOR BLOWER CONDENSER COIL EVAPOTATOR COIL CAPILLARY TUBES HP RESET AIR AIR CONDENSER BLOWER REFR...

Страница 23: ...CONDENSATE TANK FULL SWITCH NC NO COM O A CEAN IRE OPTIONAL CONDENSATE PUMP KIT PC 1P 115V OR PC 2P 208 230V INSTALL SAFETY SWITCH IN LOW VOLTAGE LOOP REPLACING CONDENSATE TANK FULL SWITCH 21...

Страница 24: ...CEAN IRE www oceanaire inc com CONDENSATE TANK FULL SWITCH NC NO COM Plug L15 30P OPTIONAL CONDENSATE PUMP KIT PC 2P 208 230V INSTALL SAFETY SWITCH IN LOW VOLTAGE LOOP REPLACING CONDENSATE TANK FULL...

Страница 25: ...CEAN IRE www oceanaire inc com CONDENSATE TANK FULL SWITCH NC NO COM Plug L16 20P OPTIONAL CONDENSATE PUMP KIT PC 2P 208 230V INSTALL SAFETY SWITCH IN LOW VOLTAGE LOOP REPLACING CONDENSATE TANK FULL...

Страница 26: ...24...

Страница 27: ...O A CEAN IRE www oceanaire inc com Plug L15 30P 25...

Страница 28: ...26 O A CEAN IRE www oceanaire inc com Plug L16 20P...

Страница 29: ...EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 50 AMPS 250 VOLTS WITH GROUNDING TYPE ATTACH MENT PLUG AND GROUNDING TYPE CONNECTOR LOAD FITTING FOR MODELS PAC3632 AND PAC6032 AN EXTENSION CO...

Страница 30: ...control box cover and check the observe the LED on the phase monitor The LED signals the following GREEN Proper Operation RED GREEN BLINKING signals reverse phase rotation Switch any two of the power...

Страница 31: ...ned or operated in accordance with the furnished written instructions or has been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation...

Страница 32: ...DATE PURCHASED INSTALLED BY For Technical Support or to locate a distributor for service parts contact Oceanaire at 847 583 0311 Please indicate the Model Number and Serial Number of the unit to assur...

Отзывы: