Troubleshooting Pulse inputs

If the device you have attached does not appear in the Modbus device list, check the following:

Verify the pulse input connections are correct .  

Verify the status LED blinks for the specific pulse input in question.  Try bridging the two terminals at the input of the 
AcquiLite to verify the input LED turns on.

Bridge the terminals of the pulse output meter and verify the input LED turns on.  This will verify the wiring to the meter 
is correct. 

Modbus Setup

The Modbus setup page provides several options related to the Modbus RS485 serial port.

AcquiLite Name: 

This is the name of the AcquiLite.  This name will be present on all log file descriptors when uploaded to 

a central database website such as BMO.  It is helpful to name the AcquiLite based on the physical location of the system, or 
building.  Note: this feature was labeled “Loop Name” in older firmware versions.

Data logging period:

 This option sets the log interval for the AcquiLite.  Options range from once per minute to once per 

hour. All  of the selections are even divisions of one hour.  The AcquiLite calculates the next log time by finding the next 
multiple of the log period past the start of the hour.  For example, if the log period is 15 minutes,  log readings will be taken 
at 0, 15, 30 and 45 minutes past the hour.  The  log period is not calculated based on “15 minutes after the last reading”

When the AcquiLite is first started, it will take an initial reading of all the Modbus devices immediately. Following that, the 
next log reading will be calculated as a multiple of the log period after the hour.  The initial reading is taken to allow the 
AcquiLite to gather information for meters that require demand calculations, as well as provide accurate information starting 
when the AcquiLite is booted. 

Modbus/TCP access:

 The AcquiLite has a Modbus TCP gateway feature that allows other systems to send queries to all 

attached Modbus RS485 devices.  This feature allows control of what systems have access to the Modbus TCP gateway 
feature.  The settings include “no access”, “local subnet only” and “allow any”.   This basic security feature only allows 
control based on the IP address of the system making the request.  The Modbus TCP protocol does not have provisions for 
any authentication password or other methods of security.  By default, the gateway feature is disabled, and set to “No 
Access.”

The Modbus TCP gateway is a feature that allows the AcquiLite to share the attached Modbus RS485 devices with other 
systems such as PCs with software and building control systems. The gateway receives incoming TCP requests, verifies the 
length of the packet does not exceed 255 bytes, and forwards the packet to the Modbus RS485 loop.  The gateway does not 
verify the contents of the packet, nor the target address specified in the request.   If the Modbus RS485 device sends a valid 
response back, the gateway will return this information to the the system requesting it via TCP.  If no response is received, a 
timeout failure will be sent to the requester.  Because the gateway does not process the contents of the request or reply, it is 
possible to query devices on the Modbus RS485 loop that are not specifically supported by the AcquiLite.   A Modbus/TCP 
technical guide may be available soon at 

www.obvius.com

Alarm Setup

The Modbus Alarms section provides the ability to send messages when alarm levels are exceeded.  Messages can be sent by 
email, SNMP or displayed on the LCD console.   Alarms are processed at the end of the data logging period.  For more 
frequent alarms, shorten the data log interval.  Log readings and alarm processing can be set to as often as once per minute.

Display all alarms on LCD console

:   When checked, all alarm messages are shown on the LCD display of the AcquiLite.

SNMP Trap Send Enabled

:  When checked, SNMP Trap messages are sent after every log period for each data point that 

is in an alarm state.  The trap includes information about the AcquiLite system data point, and alarm state.  A full MIB is 
located on the AcquiLite, click the MIB link to the right of this option.  

SNMP Trap Host 1 (2,3):

 When SNMP traps are enabled, a trap message is sent to each of the trap host addresses.  Specify 

the trap host by IP address, not DNS name.

Direct email on alarm

. When checked, the AcquiLite will send an email message when any data point changes its alarm 

state.  

Page 16

A7810 AcquiLite – Data Acquisition Server

www.calcert.com

[email protected]

1.800.544.2843

0

5

10

15

20

25

30

Содержание AcquiLite A7810

Страница 1: ...B Data Acquisition Server Obvius LLC Installation and Operation Manual Model A7810 Date Aug 10 2011 Page 1 A7810 AcquiLite Data Acquisition Server www calcert com sales calcert com 1 800 544 2843 0 5 10 15 20 25 30 ...

Страница 2: ...outside of Obvius s authorized facilities 4 has not been sold subject to other warranty terms specified at the time of sale and 5 is still owned by the original purchaser This warranty provides specific legal rights that may be varied by state law Obvius s products are not designed for life or safety applications Product Application Limitation Obvius products are not intended for use in critical a...

Страница 3: ...ooting Ethernet Problems 18 System Options 18 Status 18 Processes 18 Date and Time 18 Universal Time Is Your Friend 19 System logs 19 Firmware Update 20 Diagnostics 20 Host Lookup 20 Connection Test 20 LCD Console 21 Log File Data 23 Log File Status 23 Log File Format 23 Log Storage Capacity 25 Uploading data to the BMO website 25 Retrieving Data From the AcquiLite 26 HTTP Direct from the AcquiLit...

Страница 4: ...bit connection point hub or switch IP address and Netmask check with system administrator Gateway address check with system administrator DNS server address check with system administrator HTTP Proxy address optional may be required if the AcquiLite is behind a firewall check with system administrator 3 Insulation connected to meters inside high voltage panels should have an insulation rating in e...

Страница 5: ...ms Pulse rate option 100hz minimum pulse width 5ms Contact closure threshold 100Ω to 2 5kΩ user selectable Pulse count values are stored in non volatile memory Isolation2 The RJ45 Ethernet is isolated to 1500VDC from the main board Power input Pulse inputs and USB port and are non isolated Environmental Pollution Degree 2 Altitude up to 2000M For indoor and outdoor use when used in an appropriate ...

Страница 6: ...gerous if wire scraps come into contact with high voltage wires Step 4 Power up and diagnostics A power supply is not provided with the AcquiLite EMB therefore it is up to the installer to provide the required 24VDC After power is applied the green Alive light in the upper right of the AcquiLite should come on and the LCD display will display a series of diagnostic screens ending with the followin...

Страница 7: ...he AcquiLite or Dynamic Host Configuration Protocol DHCP address this process assigns an IP address dynamically to the AcquiLite when it is connected to the network from a host DHCP server or Direct connection between the AcquiLite and a single temporary computer such as a laptop primary connection will be dialin or dialout by modem You will need the following information from your network adminis...

Страница 8: ...tained automatically Simply select the Enable DHCP from the first TCP IP configuration menu Step 4 After the address information has been set you must reboot the AcquiLite Select the Previous Menu option after step B above The menu will then state that the AcquiLite must be rebooted to take effect Press the Select button to allow the AcquiLite to reboot Once the AcquiLite has rebooted the new IP a...

Страница 9: ...nd the scope of this document however A From the Windows start menu select the Settings Network Connections option Double click the Local Area network connection icon in the network folder then click the Properties button B In the network setup dialog there should be a list of items including adapters clients and protocols Locate the item labeled Internet Protocol TCP IP Note If you have multiple ...

Страница 10: ...e steps for each Modbus device Step 7 Select the Modbus Setup menu option Specify the Modbus Loop Name This will become the name of the AcquiLite This is the name that will appear on the BMO website service if subscribed Specify the data logging period The default is 15 minutes Step 8 Decide upon a method of data transfer see section later in this document If you select the HTTP Post method to sen...

Страница 11: ...word for read only access Log information is stored in var log modbus For read write delete access use the login name root and the admin password The three usernames specified are not able to be changed or renamed nor can arbitrary usernames be added to the AcquiLite Access is only controlled by setting the password for the three existing usernames noted above The operator and user accounts are di...

Страница 12: ... used to configure a Modbus device that is not presently connected to the system add a framework configured device or add a Modbus TCP connected device See the section on manually adding a device below Troubleshoot The AcquiLite will review the devices connected and offer suggestions about any problems found Rename all devices This option allows you to edit all the device names in one configuratio...

Страница 13: ...f the page several buttons are present Done returns you to the device list page Log File This icon will display a table view of the most recent data in the current log file Use the log file export page for complete log data access XML This icon will show the current data from the Modbus device in an XML format The URL from this icon can be copied and used to gather xml data for client side Javascr...

Страница 14: ...ata points are rotated about every 10 seconds The values on the LCD console are updated when the next log interval occurs Point Config Some devices have configurable point features Most data points are automatically configured and this option may not be displayed Advanced At the lower right corner of the page an advanced configuration button may be present depending on the Modbus device features A...

Страница 15: ...ddress already listed in the device list page Modbus TCP Gateway IP This option allows the AcquiLite to log data from a remote Modbus device that is attached to the LAN via a Modbus TCP gateway device such as an EGX or Moxa gateway Modbus TCP Gateway Port If a remote Modbus TCP gateway is used the tcp port of the remote gateway must be specified The default TCP port is 502 on most gateways Device ...

Страница 16: ... control based on the IP address of the system making the request The Modbus TCP protocol does not have provisions for any authentication password or other methods of security By default the gateway feature is disabled and set to No Access The Modbus TCP gateway is a feature that allows the AcquiLite to share the attached Modbus RS485 devices with other systems such as PCs with software and buildi...

Страница 17: ... the wireless diagnostics options will be present in the AcquiLite Please refer to the AcquiSuite A8812 or A8810 user manuals for further details on the wireless diagnostic features Networking Network Status This page displays the current status of the AcquiLite network connections Several interfaces may be shown if both Ethernet and ppp dialin dialout are active at the same time Each interface wi...

Страница 18: ...ommon mistake is configuring the Laptop IP to the same address as the IP address of the AcquiLite In order for the laptop and AcquiLite to communicate the IP addresses should not be identical see the basic network config for suggested IP addresses Use the LCD console to run the Network Status test This will attempt a number of things including a ping query to the gateway address If the AcquiLite c...

Страница 19: ... data in the database in UTC format and then convert the information when generating a report for the user For example if you wish to draw a graph of KW over Time prompt the user for a date range say Jan 1 midnight to Jan 2 midnight Take the user specified end points and convert these times from Local time to UTC Next create an SQL query using the new UTC formatted data as your select statement ie...

Страница 20: ...les will be displayed If any firmware updates are available a button to the right will be shown labeled Download The firmware files are asarm cramfs The main AcquiLite firmware file including the modbus and data logging software usrarm cramfs High level system support files such as FTP and timezone information ramdisk gz Low level system files and system libraries zImage The Linux operating system...

Страница 21: ... failure is due to the password not being correct LCD Console The AcquiLite has an LCD console and two push buttons labeled Menu and Select These can be used to configure some of the basic features of the AcquiLite The intended purpose of the console is to configure the AcquiLite to a point where a computer can communicate with it for further detailed configuration When the AcquiLite is running it...

Страница 22: ...ing requests This test does not verify if the DNS servers can actually resolve DNS names to IP addresses For a more complete test use the Connection Test web page in the AcquiLite diagnostics menu Modbus Status This option will report the number of devices currently detected by the AcquiLite The display will show a device count for Devices OK New and Failed These are as follows Devices OK The numb...

Страница 23: ...name starts with mb xxx where xxx is the Modbus device address number One file with the log extension is the file where the most recent data is being stored Other log files have a gz extension These are older log data files that have been compressed to save space The file name will be a link that will open up a browser window to view the contents of the single log file Clicking on the single log f...

Страница 24: ...8 No space left on device 32 Broken pipe 52 Invalid Exchange 101 Network is unreachable 110 Connection timed out 111 Connection refused 113 No route to host 129 Illegal Function function was not allowed by the slave device 130 Illegal Data Address the data address is not allowed by the slave device 131 Illegal Data Value 132 Illegal Response Length 138 Gateway Path Unavailable the Modbus TCP gatew...

Страница 25: ... log files to your server you must manually delete them To delete log files refer to the FTP method of downloading log files One step detailed in the FTP section is how to delete a log file from the AcquiLite Uploading data to the BMO website After the AcquiLite has been configured and has logged some data you will want to collect the data for analysis There are several ways of collecting the data...

Страница 26: ...information about the transfer process use the Connection Test page in the Testing Diags menu on the AcquiLite for a full report of the data upload progress Retrieving Data From the AcquiLite Overview of how the system was designed to work Now that you have installed your AcquiLite and configured it to collect data from your meters and sensors you will want to collect the data from your AcquiLite ...

Страница 27: ...is uploaded Designed for integration with existing energy reporting systems Contact Obvius technical support for further details and sample scripts Removing Data From the AcquiLite When using an HTTP Post method to allow the AcquiLite to push data to a database server the AcquiLite will automatically remove log files from its flash memory once the AcquiLite has confirmed that the file was received...

Страница 28: ...l be shown on that dialog Simply copy paste this URK into your link The AcquiLite can provide Modbus device data in XML format This feature coupled with browser based AJAX Javascript can provide a very powerful tool to allow the creation of custom web pages Further examples of XML and its uses are available on the Obvius website in the Documentation Technotes section Page 28 A7810 AcquiLite Data A...

Страница 29: ...proximately 4 x 4 25 x 2 deep The AcquiLite has 4 mounting holes for use with a 6 screw The drawing above shows the relative position of the mounting holes Page 29 A7810 AcquiLite Data Acquisition Server www calcert com sales calcert com 1 800 544 2843 0 5 10 15 20 25 30 ...

Отзывы: