Obvius A90DC-10 Скачать руководство пользователя страница 13

Register formatting

The Modbus data register set includes both 16 and 32 bit values, as well as signed and unsigned numbers.   On Modbus 
systems that do not allow you to read 32bit values, you can calculate the pulse count as follows:

Total = (MSW * 65536) + LSW

When using C or other programming languages, you can combine them with bit shifting and xor. 

Total = (MSW << 16) | LSW;

It is important to read both the MSW and LSW values in a single Modbus read request.  Use the Modbus function 0x03 to 
read all the Modbus data registers in a single block, and then assemble the data point values from the Modbus registers 
received in the query.  If  the MSW and LSW values are read in separate queries, the value may be updated between Modbus 
queries and the resulting combined number may be incorrect.

Data points such as the total and per-channel current measurements are provided as signed values to represent both positive 
and negative current flow.  A positive value represents current flow in the direction of the arrow on the top of the hall effect 
sensor.   Signed values are encoded in standard two's compliment format.

As a general rule, disabled or max scale current channel register values are formatted with a MAXINT16 or MAXINT32 
value depending on whether the register is 16 or 32 bit respectively.  This rule applies for all of the individual current 
measuring channels 1-12, the total current and average current sets including instantaneous and average values.   The 
Modbus register point map described earlier defines the entire Modbus map for the device.

Alarm configuration

The A90DC-12 provides features to detect alarm conditions related to Solar PV applications.  For example, in a PV array, 
the system may have 10 pv panels wired in series per string, and 12 strings that run back to a combiner box.  The A90DC-12 
can be installed at the combiner box to monitor the current levels on all 12 strings at the same time.  If a panel in one of the 
strings fails, the A90DC-12 can detect the reduction in current from the failed string and set an alarm flag to indicate the 
problem.  

To configure the A90DC-12 to detect this fault condition, several options must be configured. These options include the 
following:

Deviation threshold.

Minimum current threshold.

Minimum deviation time for alarm.

The first item to do is calculate what level you need to detect. If you have 10 panels in series and one fails, there should be a 
10% reduction in power production.   The deviation threshold should be set less than but close to 10%.  A good starting 
point will be 7%, and then adjust the set point after the system has some working data to review. 

The second item is the minimum current threshold.  In a solar PV system, the total current produced varies throughout the 
day.  At sunrise and sunset, the amount of power produced is minimal.  The minimum level at which the A90DC-12 can 
detect current is 0.75A, so the differences between channels will be below the ability of the A90DC-12 to detect.  To prevent 
this, the minimum current threshold option sets the point at which current levels must reach in order to enable the alarm 
feature.  If the minimum current threshold is set to 4 amps, the alarm feature will become operational when the average 
current per channel level exceeds 4 amps.    A good value to set for this option is the maximum current expected, less 10%. 
This will allow the average to exceed the minimum current threshold even if one channel fails completely. 

The third feature that you must set is the minimum deviation time for alarm.  This feature allows you to select the period of 
time which the alarm must be in effect before it is reported.  This will help suppress transient alarms when brief problems 
occur such as shadows from a truck or plane are present on one or more panels in a single string. 

Page 14

A90DC-12 – DC Current Monitor

www.

.com

[email protected]

1.800.561.8187

Содержание A90DC-10

Страница 1: ...A90DC 12 DC Current Monitor Obvius LLC Installation and Operation Manual Model A90DC 12 A90DC 10 Date Sep 4 2013 Page 1 A90DC 12 DC Current Monitor www com information itm com 1 800 561 8187 ...

Страница 2: ...his warranty provides specific legal rights that may be varied by state law Obvius s products are not designed for life or safety applications Product Application Limitation Obvius strongly believes in continuous improvement therefore we must reserve the right to change specifications and product offerings without notice Where possible we will substitute products with equivalent functionality when...

Страница 3: ...ister List 11 Register formatting 14 Alarm configuration 14 Mechanical Drawings 15 A90DC 12 Firmware Update 16 Markings and Symbols WARNING A potential risk exists if the operating instructions are not followed General Warning Symbol This symbol indicates the need to consult the operating instructions provided with the product This symbol indicates the presence of electric shock hazards This symbo...

Страница 4: ...is instrumental in detecting failed equipment in applications such as Solar PV arrays Applications The A90DC 12 Series DC Current Monitor has several applications These include DC Load Monitoring Solar PV Power Generation Battery Charge and Discharge monitoring Installation Checklist An A90DC 12 system installation has the following components Required hardware A90DC 12 Series DC current monitor r...

Страница 5: ...brief events Unused channels may be disabled to exclude them from total and average calculations Communications1 RS 485 S 9600 baud N 8 1 two wire Supports up to 32 external devices expandable Isolation The RS485 terminals electrically isolated to 1500V from the remainder of the A90DC 12 board Environmental2 North America Temperature 30º 70ºc 0 95 humidity non condensing Altitude up to 2000M For i...

Страница 6: ...e for each device i e no two devices with the same address Connect each device in the chain by daisy chaining the devices together Observe and polarity on the Modbus devices For more information about Modbus loops please read our Modbus FAQ available at Do not ground the RS485 shield inside the electrical panel All RS485 and 24vdc power wires including the shield should be insulated to prevent acc...

Страница 7: ...printed on the product packaging label If other A90DC 12 devices are to be used in the system you must verify the Modbus address on each is unique one to prevent two devices from having the same address A Modbus master device or software package is required to configure options on the A90DC 12 as well as read the output data The Obvius Config Console software free at www obvius com can be used to ...

Страница 8: ...sulated wire may be used depending on the application see specifications page for details It should only pass through the hall effect sensor opening When installing the load wire do not pull on or otherwise stress the hall effect sensors Step 9 power up the A90DC 12 and the load wires and confirm the readings match the expected current flow Note If cleaning is required use a dry towel to remove du...

Страница 9: ...o computes several system wide values including a total and average value for all channels For each of these both an instantaneous and long average value is reported Total instantaneous current is the sum of the instantaneous values for all 12 channels If any channels are disabled the current value for the channel is not included in the totals When using the A90DC 12 with the AcquiSuite data acqui...

Страница 10: ...tantaneous AMPS 100 average of 12 channels eg 1234 12 34A 5 40006 INT16 average current long average AMPS 100 average of 12 channels eg 1234 12 34A 6 40007 UINT16 Alarm Channel 0 no alarm 0xFFFF invalid No alarm 1 12 range alarm channel 102 internal positive powersupply bad 5V 103 power input over voltage 104 power input under voltage 105 Internal reference powersupply bad 2 5V 106 Current overran...

Страница 11: ...NT16 reserved 43 40044 UINT16 input broken wire alarm bitmap 1 broken wire 0 not broken bit0 input1 offset point type desc modes mA 44 40045 UINT16 input 1 mode NV r w 45 40046 UINT32 input 1 value MSW inst 46 40047 input 1 value LSW 47 40048 UINT32 input 1 ave MSW ave 48 40049 input 1 ave LSW 49 40050 UINT32 input 1 min MSW min 50 40051 input 1 min LSW 51 40052 UINT32 input 1 max MSW max 52 40053...

Страница 12: ... status of the input represented in ohms mA or volts The value uses a short term average of the last 16 a d converter readings to compute the value of this register In voltage and current mode the instantaneous value is calculated several times per second In resistance mode the value is calculated at least every two seconds 0xFFFFFFFF will report an off scale high condition or any other invalid da...

Страница 13: ...ombiner box to monitor the current levels on all 12 strings at the same time If a panel in one of the strings fails the A90DC 12 can detect the reduction in current from the failed string and set an alarm flag to indicate the problem To configure the A90DC 12 to detect this fault condition several options must be configured These options include the following Deviation threshold Minimum current th...

Страница 14: ... mounted inside an appropriate enclosure rated for the weather location and electrical components located inside it The A90DC 12 mounting holes are detailed below Page 15 A90DC 12 DC Current Monitor www com information itm com 1 800 561 8187 ...

Страница 15: ...tep 4 Power up the 24vdc supply to the A90DC 12 The Green Alive LED should light up and blink Step 5 Run the LPC2000 Flash Utility The following screen will be displayed Step 6 Set the following communications options COM1 or COM2 depending on your computer serial port Use baud rate 38400 or slower Check Use DTR RTS for Reset XTAL Freq kHz 14745 Step 7 Click the Read Device ID button The PartID an...

Отзывы: