Humidifier Connection
A 24VAC bypass or fan powered humidifier may be installed.
NOTE
:
Do Not Use
a traditional humidistat to control humidi-
fier operation. If a humidifier is installed, let the Observer®
Control operate humidifier.
Bypass Humidifiers
A bypass humidifier is normally wired directly to the furnace
or fan coil HUM and 24VAC COM terminals. The Observer®
Control will automatically energize the HUM output during a
call for humidification. See the humidifier installation instruc-
tions for the proper wiring procedure for each particular hu-
midifier.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in or-
der to energize upon a switch or contact closure. For this
application, a 24VAC N.O. Isolation Relay (DPST)
MUST
be
used to prevent mixing the internal humidifier power with the
indoor equipment transformer. Applying 24VAC isolation re-
lay coil to furnace or fan coil HUM and COM terminals will
allow the Observer® Control to automatically energize the
HUM output during a call for humidification. The N.O. relay
contacts will be used to energize the humidifier. See fan
powered humidifier installation instructions for more details.
Содержание TSTAT0201CW
Страница 12: ...12 616 01 1019 00 A14558 2 Press under All Days then press EDIT...
Страница 20: ...20 616 01 1019 00 3 90 5 20 0 97 Fig 2 Wall Control Assembly Pieces...
Страница 25: ...25 616 01 1019 00...
Страница 40: ...40 616 01 1019 00 Fan on with W An option to turn the fan on with a call for heating ON OFF default...
Страница 65: ...65 616 01 1019 00 Zones...
Страница 75: ...75 616 01 1019 00 Appendix Wiring Diagrams Note R and C required for single stage communicating equipment...
Страница 76: ...76 616 01 1019 00...
Страница 77: ...77 616 01 1019 00...
Страница 78: ...78 616 01 1019 00...