46 | DE
OBO Bettermann
Installing the isCon® system
7 6
Fastening the air-termination rod to pipes, a wall or T
support
The isCon
®
system can offer supports for fastening to pipes, walls or T
supports for mounting isFang air-termination rods with air-termination rod
stands (see “5.5.2 Air-termination rod support for isFang mounting” on
page 18). This applies to air-termination rods with openings at the side
or the bottom, as well as to rods with an external isCon
®
conductor.
Fig 48:
Fastening air-termination rods to pipes, walls or T supports
Please note:
– Fasten the air-termination rod to the building structure using the sup-
ports listed in Tab. 5 on page 19 and suitable fastening materials.
– In the case of a non-metallic building structure, connect the equi-
potential bonding directly to the equipotential bonding of the
air-termination rod (see “7.8 Attaching the potential connection” on
page 48).
Note!
In the case of a metallic, earthed building structure, the equipotential
bonding is created using the metallic fastening clips of the air-termination
rod. No additional connection is required.