CAREL® ir33 PLATFORM PROGRAMMABLE CONTROLLER FOR REFRIGERATED UNITS - PAGE 1 of 3

 

26 

 

 

 

Integrated Electronic 

 Microprocessor Controller 

Programming The Instrument 

 

To Modify Defrost, Differential and Other Parameters 

 

 

 

1.  Press & hold “Prg” & “SET” keys together for at least five (5) seconds; display    

will flash “0,” representing password prompt. 

 

 

2.  

Press ▲ until password “22” is reached. 

 

3.  Press “SET” key to confirm password. 

 

 

4.  Press ▲ or ▼ to reach a category to  

be modified. 

 

5.  

Press “SET” to modify selected parameter. 

 

 

6. 

Increase or decrease the value using 

the ▲ or ▼ button respectively. 

 

 

7. Press the “SET” key to temporarily save the 

new value and return to the parameter display. 

 

8. Press & hold the “Prg” key for 5 full seconds 

to save changes. This will also mute the audible 

alarm (buzzer) and deactivate the alarm relay. 

 

Warning!  Save Your Parameter Settings! 

 

1. 

To store the new parameter values, PRESS         

and HOLD the “Prg” key for at least 5 seconds.  

2.  All modifications made to parameters will be lost            

if you do NOT press a button within 60 seconds. 

Should this “timeout” occur, normal operational 

settings (prior to modifications being made) will 

resume. 

3. If the instrument is switched off before pressing the 

“Prg” key, all modifications to parameters will be lost.   

Set 

 

aux 

Prg 

mute 

def 

 

Prg 

mute 

Set 

Set 

 

Set 

 

aux 

Prg 

mute 

How To Change Reading  

From Fahrenheit (°F) To Celsius (°C) 

 

 

1. Press and hold “Prg” and “SET” keys 

together for at least 5 seconds; display will 

show “0” (password prompt). 

 

 

2. Press ▲ until password “22” is reached. 

 

 

3. Confirm by pressing “SET” key. 

 

 

4. Press ▲ or ▼ until reaching the 

parameter “/ 5.” 

 

 

5. Press “SET” to modify this selected parameter. 

 

6. Press ▲ or ▼ to change value to 

desired setting: “0” for Celsius (°C) or “1” 

for Fahrenheit (°F). 

 

7. Press “SET” key to temporarily save the new 

value and return to the display of the parameter. 

 

 

8. Press & hold “Prg” key for 5 full seconds to  

save changes. 

Note! All values will automatically 

convert to new scale. No conversion is required.

 

Prg 

mute 

Set 

Set 

def 

 

 

aux 

Set 

 

aux 

def 

 

Set 

Prg 

mute 

To Activate / Deactivate Auxiliary Output

  

 

Press and hold the “aux” key for 1 second. 

 

aux 

To Activate Manual Defrost 

 

 

Press and hold “def” key for at least 5 seconds. 

def 

 

To Reset Any Alarms With Manual Reset 

 

Press and hold the “Prg” and “aux” key for 

at least 1 second.

 

 

aux 

def 

 

 

aux 

def 

Set 

 

aux 

Prg 

mute 

 

aux 

This data derived from Carel® Controller Material:  

ir33 +030220441 - rel. 2.0 - 01.05.2006. 

User Manuals\Carel ir33 Platform Programmable Controller For    

Refrig Units - Rev C Date: 06/22/2022

 

Содержание FSC663R

Страница 1: ...er Shown With Product For Illustrative Purposes Only This Unit is Similar to FSC663R MODEL FSC463R FSC663R REFRIGERATED GRAB N GO MERCHANDISER SCC P N 20 30109 Oasis READ AND SAVE THESE INSTRUCTIONS U...

Страница 2: ...PERFORMED BY STORE PERSONNEL EXTERIOR INTERIOR GENERAL CLEANING TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY TROUBLESHOOTING TO BE PERFORMED BY STORE PERSONNEL UNLESS STATED OTHERWISE TROUBLESHOO...

Страница 3: ...eet contains important warnings to prevent injury or death Please read carefully PRECAUTIONS MAINTENANCE WIRING DIAGRAM INFORMATION See next page for PRECAUTIONS MAINTENANCE and WIRING DIAGRAM informa...

Страница 4: ...nts are true and accurate CAUTION ADVERSE CONDITIONS SPACING ISSUES Performance issues caused by adverse conditions are NOT warranted To prevent damage to end panels due to condensation apply industri...

Страница 5: ...ls from case before removing from skid to prevent buckling Illustrations below show case being removed from skid REMOVAL OF CASE FROM SKID POSITIONING UNIT 5 Place case in proper location Plug cord in...

Страница 6: ...and plumb You may need to remove front and or rear toe kick to access levelers Use adjustable wrench and or a pry bar to adjust leveler Do not use Pry Bar on Toe Kick as it will buckle Do not use Pry...

Страница 7: ...irmly and pulling up and outward See illustration at top right Field Wiring Ballast Box Thermostat Controller Main Power Switch Main Power Switch 3 Main Power Switch For self contained cases the main...

Страница 8: ...throughs Caution If ceiling originated lines are used you MUST seal both upper and lower PVC Center Pass Through Protective Plate Shown After Removal of Knock Outs center pass throughs at entrance po...

Страница 9: ...T PLACEMENT 1 Min SIDE VIEW SIDE VIEW Do Not Allow Product On Decks To Hang Over Product Stop Do Not Stack Product Nearer Than 1 To Underside of Plenum Do Not Stack Product On Decks Higher Than The Un...

Страница 10: ...mechanism s flat bar into the bracket with slot at center of case See illustration at top right and mid right 3 Security Cover Removal Optional A With key inserted in the lock rotate the locking mech...

Страница 11: ...s will be operational To verify fans are operational lift up deck pans check to see that the coil fans are functioning properly See illustration below partially disassembled for illustrative purposes...

Страница 12: ...set temperature and airflow 2 Shelf Bracket Assembly Shelf bracket assemblies ARE NOT to be adjusted or moved from their factory determined slots Item 3 below provides an exception to this guideline 3...

Страница 13: ...d in upper section of the case in front of honeycomb and under shelving 3 LED Light Fixture Removal and Replacement This case is provided with mini LED lights which will rarely require change out To r...

Страница 14: ...shows location of refrigeration lines for self contained operation Two 2 drains accessible from top of unit by lifting up decking See POWER UP CHECK EVAPORATOR FAN AREA section in this manual for unde...

Страница 15: ...ter Dryer Electrical Starter Unit Condenser Coil Housing Condenser Coil Fan Fan Housing Motor Refrigeration Lines Sight Glass Compressor Pan Self Contained Merchandiser s Condensate Unit Illustrated P...

Страница 16: ...and water solution and a non abrasive soft cloth For stubborn stains use a nylon brush DO NOT use abrasive cleaners or Brillo pads as these can destroy the shelf bracket finish Caution After removing...

Страница 17: ...outlet before beginning fan shroud and surrounding tub area cleaning 1 Turn off power 2 Remove deck from case 3 Clean fan shroud area and surrounding tub area with moist cloth Quarterly Tub Drain Cau...

Страница 18: ...t The power end of cord is to connect at the red dot marker at the end of the LED lamp See MAINTENANCE FUNDAMENTALS SHELF BRACKET ASSEMBLY REMOVAL LIGHT FIXTURES section in this manual for more specif...

Страница 19: ...s Check motor shaft for bearing wear Check that fan motors are securely mounted in brackets Verify that fan blades are securely mounted to fan motor Check that nothing is preventing blade rotation Che...

Страница 20: ...ns If case light still do not come on call SCC Technical Service phone number listed on last page of this operating manual Control Display Is Flashing See your case s serial label for your model s spe...

Страница 21: ...on condensable is not in the system Check that Liquid Line Drier is not plugged Check that there are no close offs around Condensing Coil Check Set Point Temp it may be adjusted too high Check System...

Страница 22: ...t High Superheat doesn t need adjusting Check that the Thermostatic Element charge isn t depleted Check that there is air no seepage of air around Condensing Coil Check that the Coil is not iced up Hi...

Страница 23: ...ructions as to proper dilution safety precautions and scrubbing method After thoroughly cleaning pan with scrub brush and solution rinse thoroughly with clean water in spray bottle and wipe dry with s...

Страница 24: ...llapse the honeycomb to allow it to be pulled out of honeycomb retainer C Pry downward and away from honeycomb retainer Clean honeycomb with warm water and soap solution Submerse if necessary Use brus...

Страница 25: ...FIED TO CAN CSA STD C22 2 NO 120 ELECTRICAL RATING REFRIGERANT DESIGN PRESSURE MINIMUM CIRCUIT AMPACITY MAXIMUM OVERCURRENT 120 1 60 16 A R513A AMOUNT 50 OZ HIGH 186 LOW 88 20A 20A Super Heat Temp 6 8...

Страница 26: ...e instrument is switched off before pressing the Prg key all modifications to parameters will be lost Set aux Prg mute def Prg mute Set Set Set aux Prg mute How To Change Reading From Fahrenheit F To...

Страница 27: ...ser Interface Display 27 CAREL ir33 PLATFORM PROGRAMMABLE CONTROLLER FOR REFRIGERATED UNITS PAGE 2 of 3 Integrated Electronic Microprocessor Controller This data derived from Carel Controller Material...

Страница 28: ...defrost temperature evaporator C F F 50 200 dP1 Maximum defrost duration evaporator min F 1 250 d6 Display on hold during defrost C 0 2 dd Dripping time after defrost min F 0 15 d 1 Display of defrost...

Страница 29: ...h of Purchaser shall be effective unless in writing nor operate as a waiver of any other breach of the same term thereafter SCC shall not lose any right because it has not exercised it in the past App...

Отзывы: