32
37
ASd:
The Anti-Short Cycle Delay indicates
the time required for the unit to wait before
running again.
This parameter is set to 0 min
because Nyle units come equipped with
safety timers already in place.
SF:
Sensor Failure indicates that the
temperature sensor has failed.
bLL:
Black Light Level indicates the brightness
of the LCD screen.
ADVANCED MODE
In Advanced mode you can adjust all of the basic
parameters as well as; Un, Tsb, So, HtS and LtS.
The main function of this mode is to add more
control over your unit and to set restrictions for
parameters in basic mode.
Advanced Mode Menu:
From the main screen press and hold both arrow
keys simultaneously. The screen will display the
flashing Un parameter to indicate that you have
entered the menu.
Un:
Indicates the temperature units. This can be
in either Fahrenheit (°F) or Celsius (°C).
LtS:
Low Temp. Stop indicates the lowest
temperature that the On or OFF parameters can
be set to in Basic Mode.
HtS:
High Temp. Stop indicates the highest
temperature that the On or OFF parameters can
be set to in Basic Mode.
tSb:
Temp Setback indicates the value for
setting back the On and OFF temperature
values.
Default to 0
°F
because it is not
applicable to the application of this unit type.
So:
Sensor Offset allows for compensation
of any difference between the displayed
temperature and the temperature being read by
the sensor.
RESTRICTED MODE
Lock out
You can format your parameters to completely
restrict all user adjustment of the control when
in restricted mode. To do this set the HtS value
equal to the OFF value and the LtS equal to the
On value. This makes the OFF/On range equal
to the HtS/LtS range and thereby unadjustable in
restricted mode.
Switching the Controller to Restricted Mode will
prevent users from adjusting most or all of the
parameter settings. The main screen will
function normally.
Note:
The OFF parameter is the only parameter
that can be accessed in Restricted Mode. So be
sure that your desired parameter values are set
before changing over to restricted mode.
In addition, the differential between the
OFF/ON parameters is fixed in restricted mode.
If the OFF parameter is adjusted the On
parameter will adjust to maintain the differential.
Setting the controller to restricted mode:
• Turn power off from the controller
• Carefully remove the front panel
• Locate the jumper and carefully position it on
one pin as shown in the diagram below.
The controller is now in restricted mode. Securely
replace the cover before reconnecting power to
the controller.