background image

nVent.com  |  5

Problem

Solution

Braid clips are missing.

The braid clips are attached to the cardboard packing insert 

under the lid. The braid clips must be used to ensure a 

ground connection. If clips are missing or lost, call nVent at 

(800) 545‑6258.

Mounting bracket is missing.

A pipe mounting bracket is supplied with the Power Connection, 

Powered Splice, Powered Tee and Lighted End Seal kits. A 

wall mounting bracket or additional pipe mounting bracket 

may be ordered using one of the catalog numbers listed under 

“Optional Accessories” on the front page of these instructions 

when you place your order.

Connector does not snap onto bracket.

The bracket has two sets of attachment clips. Fold up the four 

outer clips for the Power Connection and Lighted End Seal 

kit. Fold up only the center clips for the Powered Splice and 

Powered Tee kits.

Heating cable type not mentioned.

RayClic connection kits are approved for use only with 

RAYCHEM HWAT, XL-Trace, and IceStop heating cables. Do not 

use with other heating cables.

Braid clip does not fit.

Be sure the clip is installed on the metal braid, not on 

the outer jacket.

Heating cable does not have aluminum wrap.

Only HWAT heating cables have the aluminum wrap under the 

braid. Skip the aluminum wrap removal step for XL-Trace and 

IceStop heating cables.

Heating cable cannot be inserted into connector.

Check for the following:

•  Apply lubricant to heating cable primary (white) jacket.

•  Outer jacket strip length is 3 1/8-inches.

•  Braid clip is installed on top of the metal braid, not on the 

outer jacket.

•  Braid is pulled back over braid clip.

•  For HWAT, 1-inch of braid is removed.

•  Sealing nut is loose (but not removed).

•  Connection screws are loose.

Lid does not close.

Be sure all screws are fully tightened before closing the lid.

Heating cable cannot be removed.

The power connection and end seal are designed to be installed 

only once; the heating cable cannot be removed once installed. 

Additional RayClic-E and RayClic-LE end seals can be ordered 

from nVent.

Light does not come on.

•  Verify there is voltage present.

•   Verify the cable guide is screwed down completely.

•  If the light still does not function, the RayClic-LE cannot be 

repaired and must be replaced.

 

Troubleshooting Guide

Содержание RAYCHEM

Страница 1: ... Cable 877Z De Icing and Snow Melting Not UL Listed with XL Trace heating cable for buried piping APPROVED w For HWAT IceStop and XL Trace only Hazardous Locations For IceStop GM XT only Class I Div 2 Groups A B C D RayClic Connection System RayClic LE Lighted End Seal Kit Installation Instructions This component is an electrical device that must be installed correctly to ensure proper operation a...

Страница 2: ...enough extra heating cable to make service loops as required Make sure end of heating cable is cut clean Remove the outer jacket Place metal clip over the base of exposed braid For the RayClic LE lighted end seal fold up the four outer snaps then position the connector over the snaps and press down Score around and down the outer jacket of the heating cable 3 1 8 inches from the end If you experie...

Страница 3: ...nsert prepared heating cable end into connector Push until heating cable is fully inserted and end is visible through opening in connection cover plate Note RayClic connection kits are designed to be installed only once the heating cable cannot be removed once installed IceStop and XL Trace 6A HWAT Only Using wire cutters cut away 1 inch of the braid Pull exposed braid back over metal clip Using w...

Страница 4: ...ailed in steps 3 through 9 pages 2 4 Close the lid and snap the lever shut Do not force lid closed if lid does not close check the connection to ensure all screws are fully tightened Tighten the nuts on the heating cable entries until grommets are compressed Position attachment clips on mounting bracket as shown Attach the connector to the mounting bracket by pressing until it snaps in place Compl...

Страница 5: ...g cables Braid clip does not fit Be sure the clip is installed on the metal braid not on the outer jacket Heating cable does not have aluminum wrap Only HWAT heating cables have the aluminum wrap under the braid Skip the aluminum wrap removal step for XL Trace and IceStop heating cables Heating cable cannot be inserted into connector Check for the following Apply lubricant to heating cable primary...

Страница 6: ...8 Fax 86 21 5426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notice Raychem IM H58082 RayClicLE EN 1805 PN P0000008...

Отзывы: