2 | nVent.com
C1
CB19
CB17
CB15
CB13
CB3
CB9
CB11
CB7
CB5
CB1
CB16
CB42
CB20
CB18
CB4
CB14
CB12
CB10
CB8
CB6
CB2
C2
C3
C4
C5
C6
C7
C8
C9 C10
CB23
CB25
CB27
CB29
CB21
CB26
CB28
CB30
CB22
CB24
CB31
CB33
CB35
CB37
CB39
CB40
CB36
CB32
CB34
CB38
1
3
5
7
9
19
17
15
13
11
29
27
25
23
21
39
37
35
33
31
2
4
6
8
10
12
14
16
18
20
30
28
26
24
22
32
34
36
38
40
Panel
NGC-UIT2-EX
assembly location
Panel
door
Alarm
light
KIT CONTENTS
Qty Description
1 NGC-UIT2-EX
12
6/32 in Kep nuts (locking nuts)
1
5-ft 9-pin RS-232 (Null Modem) cable
Provide Suitable Panel Enclosure, and Determine Locations for NGC-UIT2-EX Assembly in Panel
1. Provide suitable panel enclosure
To protect its electronic components, the nVent NGC-UIT2-EX
must be mounted in a panel with a minimum IP32 (Type 1)
enclosure for non-hazardous locations. An IP54 (Type 4) or better
ATEX/IECEx enclosure is required for Hazardous locations. An
IP52 (Type 12) or better enclosure is recommended. The NGC-
UIT2-EX assembly comes with a sealing gasket and hardware to
mount the enclosure.
Note: The NGC-UIT2-EX is designed for operation in ambient
temperatures from –40°C to 60°C (–40°F to 140°F). If the ambient
temperature is outside this range, a space heater and/or cooling
fan will be required in the panel.
2. Determine locations for the NGC-UIT2-EX assembly in the
electrical panel
The NGC-UIT2-EX should be located on the front of the panel near
eye level (for convenient viewing). The NGC-UIT2-EX assembly is
an electronic unit and must not be located where it will be exposed
to strong magnetic fields or excessive vibration.
Conditions of Safe Use
This equipment must be installed in a hazardous location
classified cabinet or panel rated as follows:
• Internal and external ambient of: -40ºC to +60ºC
• Minimum ingress protection rating of IP54
• ATEX / IECEx: Zone 2 or better
• US / CAN: Class I Div 2 or better
• Can only be opened with the use of a tool
Do not connect/disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
Ne débranchez pas l'équipement que l'alimentation est
coupée ou que la zone est connue pour être non dangereux.
• Use appropriately classified Limited Power Source, or
LPS. Follow all applicable wiring codes and regulations.
• Peripheral equipment must be suitable for the location in
which it is used.
There are no non-incendive circuits or non-incendive field
wiring within or associated with the unit.
WARNING:
IMPORTANT:
Network Connection
Local/ Remote Port
nVent RAYCHEM RS-232/RS-485 ports may be used to communicate with host computers
(nVent RAYCHEM Supervisor Software) or DCS
Local RS-232
A non-isolated, 9 pin D sub male
Remote RS-485 #2
2-wire isolated, 9 pin D sub male
Data Rate
9600 to 57600 baud.
Maximum cable length
For nVent RAYCHEM RS-485 not to exceed 1200 m (4000 ft). Cable to be shielded twisted pair.
Field Port
RS-485, 2-wire isolated. Used to communicate with external devices, such as nVent RAYCHEM NGC-30-CRM and
RMM2. Maximum cable length not to exceed 1200 m (4000 ft). Cable to be shielded twisted pair.
Field RS-485 #1
2-wire isolated, 9 pin D sub male
Data Rate
To 9600 baud
LAN
10/100 Base-T Ethernet port with Link and Activity Status LEDs
USB Ports
USB 2.0 Host port Type A receptacle (X2)