Page

: 18 of 25

 

   

 

3  Emergency Stop System 

The device is equipped with an emergency stop 

button (6). 

Pressing the emergency stop button disconnects 

the switched AC and DC outputs from the mains. 

The button is mechanically latching. Emergency 

stop is deactivated by pulling the button. 

The switched AC and DC outputs can be turned on 

again by pressing the Outputs ON/OFF switch. 

 

 

 DANGER

  

 

Danger of electric shock 

The 

“Service” AC outputs are 

not

 switched off via the Emergency Stop 

System. 

 

3.1  Emergency Stop safety features 

The Emergency Stop function of the nVent SCHROFF power distribution unit is controlled 

and monitored by a "PILZ" safety relay. 

The safety relay provides a safety-related interruption of the switched outputs. The safety 

relay meets the requirements of EN 60947-5-1 and EN 60204-1 in applications with E-STOP 

push buttons. 

The emergency stop push button is vandalism-proof. If the emergency stop is sheared off 

during operation, the emergency stop function is also triggered. 

 

The safety relay meets the following safety requirements: 

  The circuit is redundant with built-in self-monitoring. 

  The safety function remains effective in the case of a component failure. 

  The correct opening and closing of the safety function relays is tested automatically in 

each on-off cycle. 

  Two emergency stop input circuits with cross-circuit detection. 

  Emergency stop function is triggered when either one of the two emergency stop 

input circuits is interrupted or a cross-circuit between the circuits is detected.  

 

The safety relay drives two power contactors responsible for switching the 

outputs. 

The power contractors are monitored by auxiliary contacts within a feedback 

loop of the safety relay. In case of one power contactor failing by a stuck 

contact the system can not be turned on again. 

The red ERROR LED on front panel signals if one of the power contactors 

got stuck

 

Содержание 21270-001

Страница 1: ...1 Rack Safety Plus 3 U 230 400 V AC Power Distribution Unit with Emergency Stop User Manual Release 1 4 16 05 2022 Doc No 63972 416...

Страница 2: ...ility or liability for any errors or inaccuracies that may appear in this document Except as permitted by such license no part of this publication may be reproduced stored in a retrieval system or tra...

Страница 3: ...on 8 2 2 Front and Rear View 9 2 3 Example Configurations 10 2 4 Mains inlets 13 2 5 AC Outlets 14 2 6 DC Outlet Option 15 2 7 RCD and Circuit Breakers 15 2 8 Surge Arrester Option 16 2 9 Inrush Curre...

Страница 4: ...Date 2022 05 16 Page 4 of 25 7 Technical data 24 7 1 Dimensions 25...

Страница 5: ...l environment or for commercial use 1 2 Not intended use The use of the power distribution unit as a safety function for a machine is not allowed and can lead to hazards If the equipment is used in a...

Страница 6: ...Short description of the danger The signal word DANGER indicates an immediate danger Non observance will result in severe injuries or death WARNING Symbol Short description of the danger The signal wo...

Страница 7: ...tive equipment at all you could be seriously injured Wear protective equipment adapted to the work processes Check the protective equipment before each use to ensure that it is intact Use only approve...

Страница 8: ...Mains fuses Circuit breaker panel Emergency stop system Status LEDs for phase presence and emergency stop ON OFF switch for switched outputs Possible configuration options Mains input 400 V 3 phase or...

Страница 9: ...1 Example Switched Power Outputs IEC 60320 C13 230 V AC 10 A 4 RCD option 13 Configurable output panel 2 Example Switched Power Outputs IEC 60320 C19 230 V AC 16 A 5 Circuit Breakers 14 Mains Fuses T...

Страница 10: ...Date 2022 05 16 Page 10 of 25 2 3 Example Configurations PN 21700 001...

Страница 11: ...Date 2022 05 16 Page 11 of 25 PN 21700 003...

Страница 12: ...Date 2022 05 16 Page 12 of 25 PN 21700 005...

Страница 13: ...stribution Unit The following overview represents the availability at the time of publication of this manual For the current availability visit schroff nvent com 400 V AC Inputs Cable 2 5 m Harting Ha...

Страница 14: ...the time of publication of this manual For the current availability visit schroff nvent com Switched 230 V AC Outlets IEC 60320 C13 IEC 60320 C13 IEC 60320 C13 locking outlets IEC 60320 C19locking ou...

Страница 15: ...828249 The DC PSU is connected to Phase L1 2 7 RCD and Circuit Breakers The outputs are protected by circuit breakers 5 The number of the circuit breaker corresponds to the number of the output for ex...

Страница 16: ...Date 2022 05 16 Page 16 of 25 2 8 Surge Arrester Option The Power Distribution Unit can be equipped with a surge arrester 1 phase 3 phase...

Страница 17: ...s the current limiting circuit of the inrush current limiter will be bypassed Then the load is directly connected to the AC If an AC dump overshoots the defined time Toff it will be detected by the in...

Страница 18: ...ttons The emergency stop push button is vandalism proof If the emergency stop is sheared off during operation the emergency stop function is also triggered The safety relay meets the following safety...

Страница 19: ...relay output pin 1 2 is closed If the emergency stop function is triggered the safety relay interrupts the relay contact If the outputs are not enabled via the Output ON OFF switch the relay output i...

Страница 20: ...e voltage and current rating of the cable should be greater than the ratings marked on the product WARNING Protective earth GND connection The power distribution unit must be operated with protective...

Страница 21: ...y regulations e g by authorized specialized companies or authorized departments of the company It is mandatory to mount the power distribution unit with slide rails A The power distribution unit can b...

Страница 22: ...the configuration Switch the system on via the main switch 1 The AC Service outputs will be switched on Turn on the switched AC outputs 12 13 and DC output 11 with the Outputs ON OFF switch 9 The pic...

Страница 23: ...ned cloth Use a dry cloth or are cloth slightly dampened with clean water or soapy water to clean the case Do not use chemical cleaning agents 6 Disposal The devices described in this manual must be r...

Страница 24: ...otection fuses 16 AT H Mains supply voltage fluctuations 10 Overvoltage category II Environment Ambient temperature operation 5 40 C Ambient temperature transport storage 25 65 C Maximum operational a...

Страница 25: ...Date 2022 05 16 Page 25 of 25 7 1 Dimensions...

Отзывы: