DESCRIPTION

The PolyMatrix nVent RAYCHEM PMKG-J2LP is a NEMA 4X rated 
connection kit for use with nVent RAYCHEM BTV-CR, BTV-CT, QTVR-CT, 

XTV-CT, KTV-CT and LBTV2-CT self-regulating heating cables.
Materials for one powered splice are included in this kit.

For technical support call nVent at (800) 545-6258.

TOOLS REQUIRED

• Screwdriver 

• Needle-nose pliers

•  Wire cutters 

•  Utility knife

•  Adjustable pliers 
•  Heat gun or mini-torch (for LBTV2 only)

ADDITIONAL MATERIALS REQUIRED

•  Pipe straps
• Tape 

– GT-66 Installation temperature above 40°F (5°C)

 

– GS-54 Installation temperature above –40°F (–40°C)

•  HCS-100-A 

(Required for LBTV2)

•  Grommets 

(Required for KTV and LBTV2)

This component is an electrical device which must 

be installed correctly to ensure proper operation 

and to prevent shock or fire. Read these important 

warnings and carefully follow all of the installation 

instructions.
•  To minimize the danger of fire from sustained 

electrical arcing if the heat ing cable is damaged 

or improperly installed, and to comply with the 

requirements of nVent and the 1996 National Electrical 

Code, ground-fault equipment protection must be used 

on each heating cable branch circuit. Arcing may not 

be stopped by conven tion al circuit protection.

•  Component approvals and performance are based 

on the use of specified parts only. Do not use 

substitute parts or vinyl electrical tape.

•  The black heating cable core and fibers are 

conductive and can short. They must be properly 

insulated and kept dry.

•  Damaged bus wires can overheat or short. 

Do not break bus wire strands when scoring the 

jacket or core.

•  Keep components and heating cable ends dry 

before and during installation.

HEALTH HAZARD

. Prolonged or repeated contact with 

the sealant in the core sealer may cause skin irritation. 

Wash hands thoroughly. Overheating or burning the 

sealant will produce fumes that may cause polymer fume 

fever. Avoid contamination of cigarettes or tobacco. 

Consult MSDS RAY/5510 for further information.
CHEMTREC 24-hour emergency telephone: 

(800) 424-9300
Non-emergency health and safety information: 

(800) 545-6258.

WARNING:

CAUTION:

KIT CONTENTS
Item Qty  Description

Junction box with lid

B 2 Bases

Red grommets

Core sealers

Tops (3/4 inch NPS thread)

Green/yellow heat-shrinkable tubes

Ring gaskets

H 2 Locknuts

Terminal block

A

B

C

F

E

D

G

H

I

APPROVALS

Hazardous Locations

Class I, Div. 2, Groups B, C, D

Class II, Div. 2, Groups F, G

Class III

Class I, Div. 2, Groups A, B, C, D

Class II, Div. 2, Groups F, G

Class III

Class I, Div. 2, Groups A, B, C, D

Class II, Div. 2, Groups F, G

For BTV and LBTV Heating Cable Systems Only

PMKG-J2LP