Visually inspect wire terminals to locate terminals “C or X” and “R,” 
“RH” or “RC” 

Determine if the Common Wire (typically blue wire, but not always) is
present and connected to the C terminal: 

If Common Wire is connected to C or X terminal, you likely have 
24 VAC power available 
If your thermostat does not have a Common Wire connected to C
or X terminal or if you have unused wires in the thermostat wire
bundle, test the voltage of unused wires (typically blue wire) to
determine if there is 24 VAC power available

Using a volt meter, touch one voltmeter lead to the metal screw of the
C or X terminal and the other lead to R, RH, or RC terminal. 

RC RH

 

W Y2

Y

 

G

 

C

C/X

 

L

 

RC

 

RH

 

W3/0/B

W2/E

W

 

Y2

 

G

 

C

 

L

Y

 

C/X

 

W2/E

W3/0/B

Voltage readings of around 24V (between 24 to 30 VAC) 
means there is power available at the C terminal – proceed 
to Step 1 to remove your old thermostat 
Voltage readings of around 0V (below 18 VAC) means the 
Common Wire is not connected – visit 

nvenergy.com/powershift/selfinstallguide

 for additional 

instructions on how to connect the 24VAC Common Wire at 
the HVAC unit 

If you can't identify the Common Wire, please visit 

nvenergy.com/powershift/selfinstallguide

 for further 

instructions. 

If you determine that the C/X Wire is not connected and are not 
comfortable proceeding, please call 855-676-9373 to schedule a 
professional installation. 

REMOVE OLD THERMOSTAT 

STEP 

Turn off electricity to the HVAC system 

CAUTION 

It is important to verify there is no voltage at the wall. 

Switch OFF power to heating and cooling equipment Locate correct 
breaker(s); typically labeled A/C, FAU, or HVAC. 
No voltage should be present at the thermostat 

Confirm using a volt meter, touch one voltmeter lead to the 
metal screw of the C or X terminal and the other lead to R, RH, 
or RC terminal. 
Voltage readings of around 24V means incorrect breaker has 
been turned off. Switch OFF main breaker 

Volts

 

AC

 

v

 

ON 

OFF 

RC

 

RH

 

W3/0/B

W2/E

W

 

Y2

 

G

 

C/X

 

L

Y

 

v

 

Page 2 

Содержание Smart Thermostat

Страница 1: ...onal installation By selecting the self installation option it is the users responsibility to ensure that the thermostat is installed safely and properly NV Energy will not be liable for any damages caused by failure to comply with the installation instructions Screwdriver x 2 Volt Ohm Meter Labels 1 Standard Phillip head screwdriver included 1 Mini screwdriver 1 8 in 3mm Pencil Flashlight optiona...

Страница 2: ...eadings of around 0V below 18 VAC means the Common Wire is not connected visit nvenergy com powershift selfinstallguide for additional instructions on how to connect the 24VAC Common Wire at the HVAC unit If you can t identify the Common Wire please visit nvenergy com powershift selfinstallguide for further instructions If you determine that the C X Wire is not connected and are not comfortable pr...

Страница 3: ...e labels provided in box with the new PowerShift thermostat Identify and attach labels to each wire of your existing thermostat according to the terminal it is screwed into Make sure all your wires labeled before proceeding If you had to connect a new 24 VAC common wire you will use the C X label on that wire C X G C X Y Y2 G Y Y2 W W2 E W3 0 B RC RH W W2 E W3 0 B RC RH Disconnect and remove your ...

Страница 4: ... exposed end of correct wires to matching screw terminals as labeled in Step 1 Tighten the terminal screw until each wire is secure enough to lightly pull on without coming loose Do not over tighten this may cut the wire IMPORTANT Menu Select Info RC RH W3 0 B W2 E W Y2 G L Y C X C X If you have just single R wire you can use either RH or RC terminal and leave the wire jumper clip in place If you ...

Страница 5: ... connected to your Internet router to enable the PowerShift system to work properly A Connect the provided Ethernet cable between the gateway Ethernet port and any available port of your home router B Connect the provided 5VDC power supply between the gateway and a 120 VAC power source that will always stay powered on Startup sequence After plugging in the device the three LEDs at the top of gatew...

Страница 6: ...k any air vent for cool air coming out Once cooling system is confirmed to be functioning adjust to desired setpoint close to the indoor temperature Your PowerShift thermostat will run on a default Cooling temperature program until you activate your account through the PowerShift portal Menu Select Info 7880 COOL COOL FAN AUTO HOLD TUE AUG 23 10 45A CAUTION Important DO NOT test cooling mode if ou...

Страница 7: ...mperature schedules and program your thermostat Download mobile app for your smart phone to access your thermostat and adjust settings from anywhere Communicate with your thermostat by making adjustments to suit your comfort preferences the system will continually learn from the adjustments you make Watch your savings add up it may take up to one month for savings report data to appear in the port...

Страница 8: ...tage cooling 1st stage heating 2nd stage heating 3rd stage heating 24VAC Power supply for Heating side 24VAC Power supply for Cooling side RC RH W3 0 B W2 E W Y2 G C X L Y Terminal Conventional Heat Cool system Heat Pump System 1st stage compressor 2nd stage compressor Auxiliary heating Emergency heating Changeover valve System monitor Fan Page 8 ...

Отзывы: