POSITIONING
The luminaire with detector should be sited so that the occupants of the room fall inside the detection patterns shown in
the appropriate diagram below:
The diagram is based on a ceiling mounting height.
Note that the lower the sensor is installed, the
smaller the detection range will be.
If wall mounted, the detection zone will vary
depending on the surroundings but perpendicular
reach will be at least 10m
The area closest to the sensor & also the area more
perpendicular to the sensor will have higher
sensitivity.
The distances quoted are approximate & may vary
depending on surroundings
Avoid direct sunlight entering the sensor.
Do not site within 1m of forced air heating or
ventilation.
Do not fix to a vibrating surface.
Avoid metallic objects directly in front of the sensor
head.
These sensor kits are capable of switching/controlling
more than one luminaire in a ‘master & slave’ set up.
This is done by linking non-sensored fittings (slaves)
to the one with the sensor fitted (master) using the
live output from the sensor.
Note!
DO NOT link other fittings containing MW
sensors together in this way, as it can cause false
triggering of the sensors.
SETTINGS
The following adjustments can be made using the DIP switches located on the sensor unit.
DEFAULT FACTORY SETTINGS…
Sensitivity – 10m, Time – 20mins, Lux Level control disabled
LUX
Set the required Lux level by using S1, S2 & S3 DIP switches as shown
below.
TIME
Set the required time delay between 5 secs - 30 mins using S4, S5 & S6 DIP switches as shown below:
N.B. DIP switch ON (up) or -- (down)
Ceiling mounted height: 6m
Sensitivity:100%/75%
Wall mounted height: 2m
Sensitivity: 100%