XBC 75 & 85 (ES / BC Control) 

Installation Manual

9.2 Basic Control (BC) Units

The Basic (BC) Control units described in this manual are supplied 
without any controls. It is the installer’s responsibility to select and 
install suitable controller(s) and circuit(s) to produce the desired output 
from the units while remaining within the units safe performance 
envelope.

Any electric heater must be connected to a suitable control 
circuit with adequate safety interlock to fan operation. 
Including an over temperature safety device rated at 80°C 
maximum. The fans should remain running for at least 4 
minutes after the electric element is turned off to ensure the 
unit does not overheat.

Do not wire power supply directly into the heating elements. 
A control circuit such as a thyristor controller must be used to 
regulate heater power.

The alarm relay on condensate may require the use of a contactor 
if the host equipment supply is switched.

Do not wire the power supply to motor via the motor alarm relay 
as terminals are only closed after the motor is energized.

Any heating or cooling coils fitted are supplied without control 
valve and actuator.

The wiring illustrations below are for the fans, bypass damper and 
electric heater XBC units with basic control. All wiring is terminated in 
junction boxes fitted to the unit.

9.2.1 Wiring - BC Control

 

18 

Wiring - BC Control

Содержание XBC75-V Series

Страница 1: ...TATING PARTS This unit contains fast moving rotational parts which may start automatically It is the sole responsibility of the installer to adequately guard these components REFER TO INSTRUCTION MANU...

Страница 2: ...5 Attenuator Length 900 900mm 6 Unit Roof No Suffix Standard Unit No Roof WP Twin Pitched Roof Factory Fitted 3 0 DELIVERY 3 1 Receiving Equipment All equipment is inspected prior to despatch and lea...

Страница 3: ...nit Dimensions mm and Weights kg Unit Code Unit Dimensions mm Control Dimensions mm Unit Weights Packed Weights A B C J K M E F G kg kg XBC75 H 2800 2126 876 940 740 940 250 730 800 720 902 XBC85 H 28...

Страница 4: ...Horizontal XBC75 Units 2000 1001 600 117 4 3 4 Dampers Ref No XBC Ancillary Code Description Dimensions mm Weight kg Width Height Length 4 XBC75 H MD24V Motorised dampers 24V for Horizontal XBC75 Eco...

Страница 5: ...ns mm and Weights kg Unit Code Unit Dimensions mm Control Dimensions mm Unit Weights Packed Weights A B C J F H W D kg kg XBC75 H 2500 954 1416 610 894 60 954 2500 630 730 XBC85 H 3000 1000 1676 940 7...

Страница 6: ...000 1741 600 107 4 5 4 Dampers Ref No XBC Ancillary Code Description Dimensions mm Weight kg Width Height Length 4 XBC75 V MD24V Motorised dampers 24V for Vertical XBC75 Ecosmart model ES Units 620 56...

Страница 7: ...Battery 5 2 Vertical Units e g XBC75 V XBC85 V 8 Vertical Unit Access All access panels are located on one side of the fan unit Note Unit must be isolated before panels are removed 9 Vertical Unit Ove...

Страница 8: ...ondition Observe and record filter pressure drops after performance commissioning Typically filter dirty condition occurs when the initial filter clean readings have been increased by 125Pa If filter...

Страница 9: ...rnal nylon aluminium blade interconnection linkage Fitted with Belimo SM230A S drive open drive close actuator complete with switch Motorised damper wiring will require connection on site and possible...

Страница 10: ...for Ecosmart Devices Max SL run on 0 Test Link Wire 1 Trickle ES CO2 Connection BMS Input Signal 0V 0 10V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX RX Frost Extract N E L SL DP CL N R...

Страница 11: ...st Link wire see note Trickle 1 ES CO2 BMS Connection Input Signal 0 10V 0V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX Frost RX Extract N E L SL DP CL N RET Run Fault Damper Connections...

Страница 12: ...t 80 C maximum The fans should remain running for at least 4 minutes after the electric element is turned off to ensure the unit does not overheat Do not wire power supply directly into the heating el...

Страница 13: ...required local to heater Min NET Connections for Ecosmart Devices NET Connections for Ecosmart Devices Max o n SL run Test Link wire see note 0 1 Trickle ES CO2 BMS Connection Input Signal 0 10V 0V Ec...

Страница 14: ...nt knob is located in the control pack and must be set to the desired air off temperature MIN Minimum speed adjustment MAX Maximum speed adjustment SL Run on Switched Live Run On Timer TRICKLE adjustm...

Страница 15: ...ther paper components can be largely recycled or fully processed in energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please...

Страница 16: ...the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air te...

Отзывы: