NuAire XBC75-V Series Скачать руководство пользователя страница 10

10

21. 01. 21. Document Number  671661

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

XBC 75 & 85 (ES / BC Control) 

Installation Manual

9.0 ELECTRICAL INSTALLATION

Before commencing work, make sure that the unit, switched live 
and Nuaire control are electrically isolated from the mains supply.

All inter-connections between circuit boards, blowers and sensors are 
made at the factory. This diagram only shows the essential field wiring 
points for clarity.

9.1 Ecosmart Control (ES) Units

*Remove link wire if switched live signal, an enabler or BMS signal is 
connected.  

If a damper is not fitted, connect (Factory Fitted) a link wire from OP 

to RET. This will cancel the delay.

Independent speed control can be achieved by removing the net link 
connection between supply and extract control boards.

9.1.1 Volt Free Contacts

Volt free contacts are not fused. If these are used to power any external 
equipment, the installer must provide adequate fusing or other 
protections. These contacts are rated at 5 A resistive, 0.5 A inductive.

Run Connections - Contacts:

 closed when fan running. 

Fault Connections - Contacts:

 closed when no fault, open when fault. 

Heat Demand - Contacts:

 Closed when heating selected.

9.1.2 Wiring - ES Control, No Heating

 
 

15 

Wiring - ES Control, No Heating

Damper Connections

Run 

Signal

Signal

Fault 

Min 

Max     

 on

SL run 

Test

0

Trickle           

         1

ES-CO2

BMS

Connection Input

Signal

0-10V

0V

Ecosmart

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault

TX

Frost

RX

Extract

N

E

L

SL

DP

CL

N

RET

Link Wire*

Heat

Demand   Run        Fault

Heat Demand 

Signal

Min 

NET Connections for Ecosmart Devices

Max      SL run 

 on

0

Test

Link Wire*

         1

Trickle           

ES-CO2

Connection

BMS

Input

Signal

0V

0-10V

Ecosmart

Pwr
Standby
Fan 1

Heating

Fan 2

Cooling
Fault

TX
RX

Frost

Extract

N

E

L

SL

DP

CL

N

RET

Run        Fault

Damper Connections

Run 

Signal

Fault 

Signal

Damper Link

NET Connections for Ecosmart Devices

Damper Link

Volt Free Relay Contacts

Volt Free Relay Contacts

Remove NET link Connection 

for independent speed control

Pump

 Alarm 

rel

ay

5 amps 250A ac/30V dc

br

eak on 

fault

Con-Pump 

Fuse (1 amp)

Ea

rth

Neut

ral

Li

ve 230V

Mains Ea

rth

Mains Neut

ral L1 L2 L3

L1  L2 L3

L1 L2  L3

Isolator 

by others

Customer

Connections

400V-50Hz 3ph

9.1.3 Wiring - ES Control, LPHW Heating

 

 

16 

Wiring - ES Control, LPHW Heating

Inlet 

Outlet

Sensor  Sensor 

Cool

       DX

Sensor    Coil 

Damper Connections

Run 

Signal

Fault 

Signal

Cool 

 Frost

Demand  Alarm  DX-1   DX-2

Min 

Max      SL run 

 on

Test

0         1

Trickle           

ES-CO2

BMS

Connection Input

Signal

0-10V

0V

Ecosmart

Pwr
Standby
Fan 1

Heating

Fan 2

Cooling
Fault

TX

Frost

RX

Extract

N

E

L

SL

DP

CL

N

RET

Link Wire*

Heat

Demand   Run        Fault

Heat Demand 

Signal

Setting

Heater Temperature 

o

C

15

20

25

30

Min 

NET Connections for Ecosmart Devices

Max     

 on

SL run 

0

Test

         1

Trickle           

Link Wire*

ES-CO2

BMS

Connection Input

Signal

0-10V

0V

Ecosmart

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault

TX

Frost

RX

Extract

N

E

L

SL

DP

CL

N

RET

Run        Fault

Damper Connections

Run 

Signal

Signal

Fault 

Damper Link

NET Connections for Ecosmart Devices

Damper Link

Volt Free Relay Contacts

Volt Free Relay Contacts

Remove NET link Connection for independent speed control

Pump

 Alarm 

rel

ay

5 amps 250A ac/30V dc

br

eak on 

fault

Con-Pump 

Fuse (1 amp)

Ea

rth

Neut

ral

Li

ve 230V

Mains Ea

rth

L1

Mains Neut

ral

L2 L3

L1  L2 L3

L1 L2  L3

Isolator 
by others

Customer

Connections

400V-50Hz 3ph

Содержание XBC75-V Series

Страница 1: ...TATING PARTS This unit contains fast moving rotational parts which may start automatically It is the sole responsibility of the installer to adequately guard these components REFER TO INSTRUCTION MANU...

Страница 2: ...5 Attenuator Length 900 900mm 6 Unit Roof No Suffix Standard Unit No Roof WP Twin Pitched Roof Factory Fitted 3 0 DELIVERY 3 1 Receiving Equipment All equipment is inspected prior to despatch and lea...

Страница 3: ...nit Dimensions mm and Weights kg Unit Code Unit Dimensions mm Control Dimensions mm Unit Weights Packed Weights A B C J K M E F G kg kg XBC75 H 2800 2126 876 940 740 940 250 730 800 720 902 XBC85 H 28...

Страница 4: ...Horizontal XBC75 Units 2000 1001 600 117 4 3 4 Dampers Ref No XBC Ancillary Code Description Dimensions mm Weight kg Width Height Length 4 XBC75 H MD24V Motorised dampers 24V for Horizontal XBC75 Eco...

Страница 5: ...ns mm and Weights kg Unit Code Unit Dimensions mm Control Dimensions mm Unit Weights Packed Weights A B C J F H W D kg kg XBC75 H 2500 954 1416 610 894 60 954 2500 630 730 XBC85 H 3000 1000 1676 940 7...

Страница 6: ...000 1741 600 107 4 5 4 Dampers Ref No XBC Ancillary Code Description Dimensions mm Weight kg Width Height Length 4 XBC75 V MD24V Motorised dampers 24V for Vertical XBC75 Ecosmart model ES Units 620 56...

Страница 7: ...Battery 5 2 Vertical Units e g XBC75 V XBC85 V 8 Vertical Unit Access All access panels are located on one side of the fan unit Note Unit must be isolated before panels are removed 9 Vertical Unit Ove...

Страница 8: ...ondition Observe and record filter pressure drops after performance commissioning Typically filter dirty condition occurs when the initial filter clean readings have been increased by 125Pa If filter...

Страница 9: ...rnal nylon aluminium blade interconnection linkage Fitted with Belimo SM230A S drive open drive close actuator complete with switch Motorised damper wiring will require connection on site and possible...

Страница 10: ...for Ecosmart Devices Max SL run on 0 Test Link Wire 1 Trickle ES CO2 Connection BMS Input Signal 0V 0 10V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX RX Frost Extract N E L SL DP CL N R...

Страница 11: ...st Link wire see note Trickle 1 ES CO2 BMS Connection Input Signal 0 10V 0V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX Frost RX Extract N E L SL DP CL N RET Run Fault Damper Connections...

Страница 12: ...t 80 C maximum The fans should remain running for at least 4 minutes after the electric element is turned off to ensure the unit does not overheat Do not wire power supply directly into the heating el...

Страница 13: ...required local to heater Min NET Connections for Ecosmart Devices NET Connections for Ecosmart Devices Max o n SL run Test Link wire see note 0 1 Trickle ES CO2 BMS Connection Input Signal 0 10V 0V Ec...

Страница 14: ...nt knob is located in the control pack and must be set to the desired air off temperature MIN Minimum speed adjustment MAX Maximum speed adjustment SL Run on Switched Live Run On Timer TRICKLE adjustm...

Страница 15: ...ther paper components can be largely recycled or fully processed in energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please...

Страница 16: ...the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air te...

Отзывы: