Installation Manual

6.1.3 Two Speed - Dual Wound Motor - 3 Phase

L1

L2

Low
Speed

High
Speed

L3

L1

L2

L3

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

1U

1V

1W

2U

2V

2W

Motor Terminal Box

/ Isolator

Wiring - Two Speed - Dual Wound Motor - 3 Phase

6.1.4 Two Speed - TAP / PAM Wound Motor - 3 Phase

1U

1V

1W

2U

2V

2W

NOTE
HIGH SPEED
Supply: 2U  2V  2W
LINK:    1U  1V  1W

LOW SPEED
Supply: 1U  1V  1W

 

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

Motor Terminal Box

/ Isolator

Wiring - Two Speed - TAP / PAM Wound Motor - 3 Phase

6.1.5 Two Speed Motors - Example Contactor Control

AI

A2

E

1      3      5 

L1    L2    L3 

1U    1V   1W 

2U    2V   2W 

2      4      6 

AI

A2

1      3      5 

2      4      6 

AI

A2

1      3      5 

2      4      6 

For low speed connect

Contactor C1

 

For high speed connect

Contactor C2 and C3

Motor Terminal Box

Note: High Speed - 
Supply:  2U  2V  2W
Link: 1U  1V  1W

Low Speed - 
Supply: 1U  1V  1W

C1

C2

C3

400V 3 phase 50Hz supply  
380V 3 phase 60Hz supply  
460V 3 phase 60Hz supply  

Two Speed Motors - Example Contactor Control

6.0 ELECTRICAL INSTALLATION

Motors are totally enclosed and protected to IP55 (Dust and low 
pressure water jets). Motors comply with BS5000, EN600034 and 
IEC34-1. Enclosures are to IP55 with class H insulation. Motors are 
tested in accordance with EN12101-3 2015. 

Note the requirements for maintenance of the motor. Failure to 
comply with the recommendations will invalidate any warranty 
claim.

For good EMC engineering practice, any sensor cables or switched 
live cables should not be placed within 50mm of other cables or on 
the same metal cable tray as other cables.

6.1 Wiring

Electrical supply wiring connection is to an externally mounted isolator 
box on the case exterior. The box is pre-wired to the motor with heat 
resisting cable.

Total length of motor leads should not exceed 30 metres. If a screened 
motor cable is used, maximum length should be 25 metres. Consult 
our Technical Department if you wish to use longer leads. Inverters are 
configured to suit specific fans and control applications as described on 
the Customer Order free of charge.

Individual wiring instruction are included with each unit.

Under fire conditions the electrical supply must not run through 
the inverter (the inverter must be bypassed).

6.1.1 Star D.O.L. Starting (3kW and below) - 3 Phase 

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

L1

L2

L3

STAR

L1  -  U1

L2  -  V1

L3  -  W1
Link W2, U2, V2

U1

V1

W1

W2

U2

V2

Wiring - Star D.O.L. Starting (3kW and below) - 3 Phase

6.1.2 Delta D.O.L. Starting (4kW and above) - 3 Phase 
 

 

U1

V1

W1

W2

U2

V2

DELTA

L1  -  U1  -  W2
L2  -   V1  -  U2 
L3  -  W1  -  V2

Note: 
For all D.O.L. (Direct On Line)
operation or Inverter type Speed Control
wire in DELTA

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

Wiring - Delta D.O.L. Starting (4kW and above) - 3 Phase

Содержание SVTC8

Страница 1: ...urer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or...

Страница 2: ... competent person to determine if any additional PPE is required 2 0 INTRODUCTION The Nuaire SVTC8 unit comprising fan motor assembly shall be certified for high temperature operation at 400 C for 2 hours The range shall have been type tested to EN12101 3 The units shall be either 2 speed or inverter driven providing low speed for day to day environmental ventilation and one off operation for emer...

Страница 3: ...e below states the main characteristics of the SVTC8 fan range certified for operation at 400 c for 2 hours The unit Is thermally uninsulated May be located in the smoke reservoir Is dual purpose i e suitable for day to day operation and one off emergency use Suitable for mounting in horizontal orientation only 4 1 Fitting Unit to Ceiling Raise the SVTC8 unit up into the chosen mounting position U...

Страница 4: ... with EN12101 3 2015 Note the requirements for maintenance of the motor Failure to comply with the recommendations will invalidate any warranty claim For good EMC engineering practice any sensor cables or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables 6 1 Wiring Electrical supply wiring connection is to an externally mounted is...

Страница 5: ...eed of the motor supplied by the mains and that the delivered power corresponds to the previous definitions These qualifications ensure the qualification of the driven fan by the manufacturer Maintenance Constraints Regular service visits must be performed on the installation AT LEAST EVERY 6 MONTHS incorporating the following checks i Checking insulation resistance R 100 MOhms 500V DC If the drai...

Страница 6: ...ons The remaining two years covers replacement parts only This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions...

Страница 7: ...01 09 21 Document Number 671711 7 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk NOTES 7 ...

Страница 8: ...ovision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Ambient humidity the humidity at the unit s installed location shall be within the range 10 to 95 for controls non condensing Air humidity the humidity of the air passing through the unit shall be within the...

Отзывы: