Maintenance

ISOLATION
BEFORE COMMENCING WORK MAKE SURE THAT
THE UNIT AND NUAIRE CONTROL, IF FITTED,
ARE ELECTRICALLY ISOLATED FROM THE MAINS
SUPPLY.

Maintenance  Intervals (fan unit)

The first maintenance should be carried out three months after
commissioning and thereafter at twelve monthly intervals.
These intervals may need to be shortened if the unit is operating
in adverse environmental conditions, or in heavily polluted air.

Lubrication

Motors are fitted with sealed for life bearings and therefore
require no further lubrication.

General Cleaning and Inspection (fan unit)

Clean and inspect the exterior of the Singlepak unit and associat-
ed controls etc.
Remove the access panel from the Singlepak unit. Inspect and, if
necessary, clean the fan and motor assemblies and the interior of
the case.  If the unit is heavily soiled it may be more convenient
to remove the fan / motor assemblies.
Check that the shutters are free to move smoothly and that they
seal the appropriate fan outlet effectively.
Clean and inspect the fan and motor assembly as follows; taking
care not to damage, distort or disturb the balance of the impeller.

a)     Lightly brush away dirt and dust, paying particular 

attention to any build up at the motor ventilating slots. 
If necessary, carefully remove with a blade or scraper.

b)    Stubborn dirt at the impeller may be carefully removed   

with a stiff nylon brush.

c)     Check all parts for security and general condition. 

Check that the impeller rotates freely.

Refit the assembly to the unit then  replace the access covers.

Controls

If NuAire controls and or remote indicators are fitted, remove
the covers and carefully clean out the interiors as necessary.
Check for damage. Check security of components. Refit the
access covers.

Filter Cassette

Every three months (or more frequently if operating conditions
warrant) release the cover and inspect the filter. The filter ele-
ment is formed over a wire mesh supporting  frame and can be
vacuum cleaned (preferably from the frame side). Badly soiled
filters can be replaced, spares available from NuAire on request.
Quote code SF followed by unit size e.g. SF250. Note: the
replacement frame/filter element may need to be ‘formed’ to
shape as the original prior to fitting.

Replacement of Parts

The only item of the Singlepak unit likely to require replace-
ment is the fan / motor assembly due to a failed motor or dam-
aged impeller. In either eventuality the complete fan / motor
assembly must be removed from the unit case.

NOTE:

BEFORE COMMENCING WORK, ELECTRICALLY
ISOLATE THE TWINPAK UNIT AND / OR THE 
ASSOCIATED NUAIRE CONTROL, IF FITTED, 
FROM THE MAINS SUPPLY.

Remove the access cover. Disconnect the incoming wiring  from
the connection box (located inside case) Support the weight of
the fan/motor assembly and remove the mounting screws and
washers. Lift the assembly out of the case.
After replacing the faulty item, refit the fan/motor assembly and
reconnect the incoming wiring to the terminal box. Replace the
access cover.

Schedule of Parts

When ordering spares please quote the serial number of the unit
together with the part number if.  If the part number is not
known please give a full description of the part required. The
serial number will be found on the identification plate attached
to the unit casing

3 YEAR WARRANTY

The three year warranty starts from the date of delivery and
includes parts and labour for the first year.
The labour element is subject to full, free and safe access to the
equipment as recommended by the CDM regulations.
The remaining two years covers replacement parts only.

NOTE:
Installation & Maintenance of the equipment must be as
directed in the instructions provided with the unit.

Service

As a manufacturer NuAire provides you with factory trained
Service Engineers. Our Engineers are supported by a comprehen-
sive range of spare parts 'off the shelf '.
If you are an industrial or commercial user, you may be interested
in details of NuAire's regular maintenance Service Contracts. 
This is a worthwhile service that helps you get the most from our
products.
Our Service Department will be happy to give you 
more information.

Telephone:

02920 858585

Controls Application Service (CAS)

A team of Engineers and technicians is available to provide pre
and post order support.
We are on hand to provide help and advice from the most basic
use of any NuAire equipment to the more complex applications,
maximising on the versatility of our control products.

Telephone:   029 2085 8585
Facsimile:     029 2085 8586

(Q)SP125

(Q)SP200

(Q)SP200H

(Q)SP250

(Q)SP400

(Q)SP400H

771950

771954

771955

771517

771418

771847

Spares listing

Unit 

code

Blower assembly

c/w  motor.

Installation and Maintenance  

SINGLEPAK IN LINE FAN

NB
If you have any comments or queries on any of our products or
services please write to the Product Information Manager at the
main address.

Содержание SINGLEPAK SP125

Страница 1: ... mounting used is the total responsibility of the installer Note that the unit is supplied with flange holes see fig 1 The mounting feet supplied can be attached at any of these points and the unit may be installed at any angle Installation Units should always be positioned with sufficient space to allow removal of the access covers and subsequent removal of fan and motor assemblies etc Note when ...

Страница 2: ...mperature safety cut out rated 13amps Manual reset button located on integral terminal box Constructed from galvanised steel Can be installed at any angle The filter medium is non woven synthetic fibres which are resistant to moisture fungus bacteria and frost Cover retained by quick release toggle clips Constructed from galvanised steel Fitted with a gasket liner X D Q SP125 Q SP200 Q SP200H Q SP...

Страница 3: ... the terminal block provided in the terminal box inside the casing If a control other than NuAires is being installed the design of suitable circuitry is the responsibility of others ESC1 electronic type SP CON transformer type Dims A B C ESC1 3A 83 88 180 ESC1 6A 115 95 195 ESC1 10A 115 95 195 ESC1 3A illustrated SPCCON7 5 illustrated Dims weights A B C kg SP CON 1 5 115 85 180 1 70 SP CON 3 5 20...

Страница 4: ... on rise of temperature simple manual reset from external push button Unit and Run on Timer Singlepak Heaters Single phase single stage SH 100 SH 125 SH 200 SH 250 Motor L N L N SL L N N L T1 T2 L N E L N 230v 50Hz 1 ph AC supply Typical stage switching by others To Heater control circuit by others NB Singlepak Heatwers 3 Phase For 3 phase multi stage wiring information please telephone NuAire Tec...

Страница 5: ...pes SPCON 1 5 SPCON 3 5 SPCON 7 5 Not suitable for use with the following units SP QSP200 SP QSP200H SP QSP250 Motor L N L N 230v 50Hz 1 ph AC supply L N L2 N L1 Fan unit Singlepak with Electronic speed control types ESC1 3A ESC1 6A ESC1 10A Motor L N L N Note on Speed Controls A list of setting instructions is supplied with each Speed Control unit ...

Страница 6: ...ment is the fan motor assembly due to a failed motor or dam aged impeller In either eventuality the complete fan motor assembly must be removed from the unit case NOTE BEFORE COMMENCING WORK ELECTRICALLY ISOLATE THE TWINPAK UNIT AND OR THE ASSOCIATED NUAIRE CONTROL IF FITTED FROM THE MAINS SUPPLY Remove the access cover Disconnect the incoming wiring from the connection box located inside case Sup...

Страница 7: ...ity and Safety of Electrical Equipment Designation of machinery SINGLE IN LINE FAN Machinery Types SINGLEPAK QIUET SINGLEPAK SP QSP Relevant EC Council Directives 89 336 EEC 92 31 EEC EMC 73 23 EEC 93 68 EEC Low Voltage Directive Applied Harmonised Standards EN55014 1 EN55014 2 EN60204 1 EN60335 2 80 Basis of Self Attestation Quality Assurance to BS EN ISO 9001 BSI Registered Firm Certificate No F...

Страница 8: ... installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to ductwork systems They must not be used to support the ductwork 5 0 INSTALLATION REQUIREMENTS In addition to the p...

Отзывы: