SINGLEPAK

In Line Single Fan

Fig. 1 General view of fan unit

Introduction

The Singlepak range of In Line singlefans  are rectangular in sec-
tion and manufactured in galvanised steel. The fan units and the
matching ancillaries are fitted with circular spigots. Fans are
available with duties up to 0.95m

3

/s. and are suitable for air

extract or air input. 
Integral backdraught shutters fitted as standard.  Access panels
top and bottom simplify installation and maintenance.  

Units are supplied complete with heavy gauge steel mounting
feet.  Singlepak may be installed at any angle 

except vertically

blowing downwards and inverted horizontally.

QSP (Quiet Singlepak) unit cases have fire resistant acoustic 
lining. 

Fan is easily serviced after removal of the access panel. Each
assembly is electrically terminated in a connector box inside the
unit casing. Supply cable enters unit through cable grommet
provided on case side. 
The motors have thermal overload protection and sealed for life
bearings. Forward curved centrifugal impellers are fitted.

A matching range of ancillaries including silencers, filters and
heaters is available.
Auto Transformer or Electronic speed controls are available. A
run on timer is avauilable giving automatic operation when
linked to a light switch or similar source.

Handling

Always handle the units carefully to avoid damage and distor-
tion. If mechanical aids are used to lift the unit, spreaders should
be employed and positioned so as to prevent the slings, webbing
etc. making contact with the casing.

Mounting

The method of mounting used is the total responsibility of the
installer.
Note that the unit is supplied with flange holes, see fig. 1.  The
mounting feet (supplied)  can be attached at any of these points
and the unit may be installed at any angle.

Installation

Units should always be positioned with sufficient space to allow
removal of the access covers and subsequent removal of fan and
motor  assemblies etc. 
Note: when the unit is mounted horizontally the correct orien-
tation must be observed as indicated by direction labels on the
side of the unit case.  

Note Do not install the unit inverted.

Speed Controls and 
Remote Fan Failure Indicator.

These controls may be mounted onto any firm surface using the
fixing holes provided in the base. Drill and plug the mounting
surface, positioning the control or indicator so that the cover
screws remain accessible. This is particularly important if a bat-
tery of controls is being installed. Fix the unit using suitable
woodscrews (not supplied). For wiring purposes, the control or
indicator cover has knock out slots for cable entry to suit up to
20mm conduit.

Testing after Installation

Ensure that the Singlepak unit and Control / Remote Fan
Failure Indicator, as relevant, are fitted.
Switch on and check that the Singlepak unit runs satisfactorily.
If a NuAire Transformer speed control has been installed  check
that the correct speed variation is obtained.
For electronic type speed controls follow the installation set-up
procedure provided with the control.
Switch off. If a Run-on Timer (230 RTIM) is fitted, check that
the fan continues to run. 
Time the run-on period, which is adjustable between 5 and 30
minutes nominal. 
Timer controls are set at the works to the shortest period.

Contents

Page

Introduction

...............................................   1

Installation      ...............................................     1

Testing after Installation  ............................   1

Dimensions  ...................................................    2

Motor Details  ..............................................     3

Electrical Diagrams   .................................      4

Maintenance    .............................................      6

Replacement of parts   ................................     6

Certification .................................................     8

Rating plate

Mounting
feet supplied

Connection
terminal box

Removable
access panel

Removable
access panel

1

Содержание SINGLEPAK SP125

Страница 1: ... mounting used is the total responsibility of the installer Note that the unit is supplied with flange holes see fig 1 The mounting feet supplied can be attached at any of these points and the unit may be installed at any angle Installation Units should always be positioned with sufficient space to allow removal of the access covers and subsequent removal of fan and motor assemblies etc Note when ...

Страница 2: ...mperature safety cut out rated 13amps Manual reset button located on integral terminal box Constructed from galvanised steel Can be installed at any angle The filter medium is non woven synthetic fibres which are resistant to moisture fungus bacteria and frost Cover retained by quick release toggle clips Constructed from galvanised steel Fitted with a gasket liner X D Q SP125 Q SP200 Q SP200H Q SP...

Страница 3: ... the terminal block provided in the terminal box inside the casing If a control other than NuAires is being installed the design of suitable circuitry is the responsibility of others ESC1 electronic type SP CON transformer type Dims A B C ESC1 3A 83 88 180 ESC1 6A 115 95 195 ESC1 10A 115 95 195 ESC1 3A illustrated SPCCON7 5 illustrated Dims weights A B C kg SP CON 1 5 115 85 180 1 70 SP CON 3 5 20...

Страница 4: ... on rise of temperature simple manual reset from external push button Unit and Run on Timer Singlepak Heaters Single phase single stage SH 100 SH 125 SH 200 SH 250 Motor L N L N SL L N N L T1 T2 L N E L N 230v 50Hz 1 ph AC supply Typical stage switching by others To Heater control circuit by others NB Singlepak Heatwers 3 Phase For 3 phase multi stage wiring information please telephone NuAire Tec...

Страница 5: ...pes SPCON 1 5 SPCON 3 5 SPCON 7 5 Not suitable for use with the following units SP QSP200 SP QSP200H SP QSP250 Motor L N L N 230v 50Hz 1 ph AC supply L N L2 N L1 Fan unit Singlepak with Electronic speed control types ESC1 3A ESC1 6A ESC1 10A Motor L N L N Note on Speed Controls A list of setting instructions is supplied with each Speed Control unit ...

Страница 6: ...ment is the fan motor assembly due to a failed motor or dam aged impeller In either eventuality the complete fan motor assembly must be removed from the unit case NOTE BEFORE COMMENCING WORK ELECTRICALLY ISOLATE THE TWINPAK UNIT AND OR THE ASSOCIATED NUAIRE CONTROL IF FITTED FROM THE MAINS SUPPLY Remove the access cover Disconnect the incoming wiring from the connection box located inside case Sup...

Страница 7: ...ity and Safety of Electrical Equipment Designation of machinery SINGLE IN LINE FAN Machinery Types SINGLEPAK QIUET SINGLEPAK SP QSP Relevant EC Council Directives 89 336 EEC 92 31 EEC EMC 73 23 EEC 93 68 EEC Low Voltage Directive Applied Harmonised Standards EN55014 1 EN55014 2 EN60204 1 EN60335 2 80 Basis of Self Attestation Quality Assurance to BS EN ISO 9001 BSI Registered Firm Certificate No F...

Страница 8: ... installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to ductwork systems They must not be used to support the ductwork 5 0 INSTALLATION REQUIREMENTS In addition to the p...

Отзывы: