A

B

Removable 
top panel

Rectangular bottom 
inlet spigot

Code: QTRB

Control module
located internally

Opposed 
outlet grilles

C

E

F

Spigot

Unit

A                B              C

E

F

QTRB A

974

974             622            457           229

QTRB B

1233          1233             701           762           304 

QTRB C              1430         1635             796            889           381

NOTE: Rectangular  Bottom Spigot only.

Table 1.  

Dimensions 

QTR Roof Mounted Belt Drive Twinfans
END INLET UNITS
Sizes:   A, B & C.

DIMENSIONS (mm)

Table 2.  

DIMENSIONS (mm)

Fig. 2. 

Fig. 3. 

For unit weights 
see electrical tables

For unit weights 
see electrical tables

A

B

Removable 
top panel

Opposed
outlet
grille

Square inlet 
spigot on end 
of unit 
Code: QTRS

Circular spigot 
on end of unit 
Code: QTRC

E

D dia

E

Control module
located internally

C

QTR ‘C‘      QTR ‘S’

Unit

A

B

C

D dia

E sq

QTR A

974

974

622

400

305

QTR B

1233

1233

701

500

457 

QTR C

1430

1635

796

630

610

NOTE: Circular or Square Spigots.

BOTTOM  INLET UNITS
Sizes:   A, B, C.

Controls

Two methods of control are available:
i.    MICROSAVE (M) control.   (leaflet 670915)
ii.   MAINS (C) control.               (leaflet 670912)
Note that when a Microsave option is supplied, the user  
control is included inside the fan case for delivery.
Details of control installations are given in relevant separate
leaflets which deal with each control type.

Installation 

Quietwin MUST NOT BE MOUNTED AT AN ANGLE
OF MORE THAN 5

O

FROM THE HORIZONTAL to

ensure that the shutters operate satisfactorily.
Units should always be positioned with sufficient space
to allow removal of the access covers and subsequent
removal of fan and motor assemblies etc. from above.
The QTR units are supplied for installation onto vertical duct-
work (bottom inlet) roof; back inlet roof and bottom inlet
with end louvre outlet (case size ‘D’) applications. Ductwork
connections must be airtight to prevent loss of performance. 

The method of mounting used is the total responsibility of the
installer. the lower edge of the casing has an internal skirt
allowing the unit to be located on an upstand or prefabricated
curb if desired. See prefabricated curb details on page 5.
The unit should be securely screwed to its curb or mounting
to prevent vibration and/or wind damage.
If a unit is converted from bottom inlet to to side inlet after
installation, the redundant bottom inlet must be blanked off at
the spigot. It is essential that the cross sectional area of the new
side inlet is not less than that of the original bottom inlet.
Otherwise severe reductions in performance will occur.
It is the responsibility of the installer to drill the casing to
allow the electrical cables to be connected. The cable entry
should be effectively sealed Note that on the bottom inlet
(QTRB units) the cabling could be carried up from inside the
building, through the bottom inlet spigot.
If a NuAire control has been supplied, wire the control to the
Fan unit and also to the mains supply. The QTR unit has an
internal terminal box and is supplied ready for connection to
the electrical supply via the chosen control. See page 6.

Handling

Always handle the units carefully to avoid damage and distor-
tion. If mechanical aids are used to lift the unit, spreaders
should be employed and positioned so as to prevent the slings,
webbing etc. making contact with the casing. 

ELECTRICAL ISOLATION

Note that the unit must be provided with a means of
isolation (by others) for maintenance purposes etc.  
A suitable isolator can be supplied by NuAire on
request as a separate item.

Installation and Maintenance    

QUIETWIN  QTR BELT DRIVE TWINFAN

2

QTR= Quietwin, roof mounted, external use.

= Rectangular end inlet spigot.

= Rectangular bottom inlet spigot.

= Case size D only

= Fan performance curve number.

3 = 3ph 400v, 

= Microsave integral fan control.

= Mains fan control.

QTRR  D  1    3    M = Quietwin, roof mounted, rectangular end
spigot, case size D,  3 phase and Microsave control.

Coding (bottom/ end inlet units sizes D).

Содержание QUIETWIN QTR

Страница 1: ...ames are supported on the base by resilient mountings allowing the fan unit to be operated with out the need for separate anti vibration fan case mountings The units incorporate two independent motors...

Страница 2: ...he installer the lower edge of the casing has an internal skirt allowing the unit to be located on an upstand or prefabricated curb if desired See prefabricated curb details on page 5 The unit should...

Страница 3: ...23 3 1400 1 5 3 7 18 5 96 4 CASE SIZE A Table 4 Start Run currents etc Electrical Details See table 3 4 5 Because the run and start currents depend upon the duty and asso ciated ductwork of an individ...

Страница 4: ...t Drive Twinfans continued Table 5 Start Run currents etc CASE SIZE B Table 6 Start Run currents etc CASE SIZE C Installation and Maintenance QUIETWIN QTR BELT DRIVE TWINFAN 4 General Electrical Weigh...

Страница 5: ...nit Support Base Removable top covers Unit support base Inlet spigot 2500 2315 200 1200 1200 200 min100 min 75 50 1790 2490 Unit Weight and Fixing Size D units For unit weights see electrical informat...

Страница 6: ...power control Figure 9b 6 3 YEAR WARRANTY The three year warranty starts from the date of delivery and includes parts and labour for the first year The labour element is subject to full free and safe...

Страница 7: ...the User Control is included inside the fan unit for delivery to site Take care not to misplace the item before installation Wiring Connections Supply 230V 1 Phase to terminals E N L in control module...

Страница 8: ...K Y RUN FAULT Low voltage Communications Cable Not used in this option MT AVI connection BL RD BK Y MICROSAVE USER CONTROL CONTROL MODULE IN FAN Single phase QUIETWIN with MICROSAVE control Link Link...

Страница 9: ...S Building Management System override control on off and system status Code Description CT A Auto duty sharing CT M Manual duty sharing Mains Control Options NOTE See relevant Installation Maintenance...

Страница 10: ...1 L2 N E H BL RD BK Y RUN FAULT 230v MAINS CONTROL 230v 1 phase supply Link Link NET CT AVI Audible Visual Indicator connection QUIETWIN FAN Three phase 230v Switched Live Connection twinfan operates...

Страница 11: ...es operate freely by locating the spindle and flap through the blower outlet aperture and carefully moving the flap A click will be heard when the switch operates See fig 11 NOTE Do not bend the flaps...

Страница 12: ...g switches operate freely by locating the spindle and flap through the blower outlet aperture and carefully moving the flap A click will be heard when the switch oper ates See fig 14 NOTE Do not bend...

Страница 13: ...30364 530373 530368 530372 530367 530373 530368 530372 530367 530373 530368 530374 530369 530373 530368 530374 530369 530375 530373 530368 530374 530375 530376 530374 530369 530375 530376 530374 53036...

Страница 14: ...e Directive Applied Harmonised Standards E50081 1 EN50082 1 EN60204 1 EN60335 2 80 Basis of Self Attestation Quality Assurance to BS EN ISO 9001 BSI Registered Firm Certificate No FM 149 Signature of...

Страница 15: ...37 EC Machinery Directive 93 44 EEC Amendment to the Machinery Directive Applied Harmonised Standards EN292 1 EN292 2 EN294 EN29001 Applied National Standards BS848 Parts One Two and Five Signature o...

Страница 16: ...tion 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate...

Отзывы: