QTR B units (sizes A, B & C) are supplied with a rigid alu-
minium alloy rectangular bottom inlet spigot and 2 opposed
outlet  grilles (size D has a rectangular end inlet  or bot-
tom inlet spigot and a rectangular end outlet louvre)

QTR C units (case sizes A, B & C) are supplied with a rigid
aluminium alloy CIRCULAR end inlet spigot and 2 opposed
outlet grilles. 
QTR S units (case sizes A, B & C) are supplied with a rigid
aluminium alloy SQUARE end inlet spigot and 2 opposed 
outlet grilles.

NuAire Limited
Western Industrial Estate
Caerphilly,
Mid Glamorgan CF83 1XH
Telephone:  01222 885911
Facsimile: 01222 887033
Email: [email protected]

Leaflet 670922

FEBRUARY 1999

QTR QUIETWIN 
Belt Drive Twinfans

Single & three phase, roof  mounted

NOTE: 
This leaflet covers QTR units with case
SIZES A, B ,C & D

Included are both end inlet and bottom
inlet configurations.
The ‘D’ size units  differ in that they are
larger fans featuring a louvred end outlet.

The NuAire QUIETWIN Twinfan Belt Drive range consists
of 4 basic  designs with duties up to a maximum of  9m

3

/s.

The 4 models are coded as follows:

QTE 

(External Duct Mounted) in line unit

QTR     (Roof Mounted, end inlet) side exhaust unit.  
QTRB  (Roof Mounted bottom inlet) side exhaust unit. 
QTRD  Case size D. This is a large roof mounted fan, 

(bottom or end inlet) with end louvred exhaust. 

QTR Quietwin models

Units are rectangular in section and have circular or square*
rigid spigots at each end.  The casing is manufactured from
heavy gauge natural aluminium alloy.
A full size internally lined access panel is fitted to the top face.
The panel is fully detachable for inspection purposes. 
The motor plate and frames are supported on the base by
resilient mountings allowing the fan unit to be operated with-
out the need for separate anti vibration fan case mountings.
The units incorporate two independent motors with high effi-
ciency, forward curved centrifugal impellers running in metal
scrolls.  Taperlocked pulleys and wedge drive belts are
employed. The fans discharge into a common outlet chamber
through a shutter system that prevents ‘blowback through the
standby fan.
The motors are manufactured to  BS 5000  and are suitable for
single phase (case ‘A’ only) or three phase supply. Airflow and
failure monitors are standard as is Class B insulation. Suitable
for operation in ambient temperatures up to 40

o

C. 

Case size D has rectangular spigots.

Installation   

and Maintenance

Contents

Page

Coding

1

Dimensions                     

2

Installation

2

Motor electrical details

3    

Roof  aperture & curb details

5

Electrical installation                      

6

Service 6

Control option ‘M’  Microsave

7

Control option ‘C’  Mains

9

Maintenance  

11    

Ordering Spares

13

Certification

14

1

Fig. 1. General view of a typical QTR unit 

QTR

QTR= Quietwin, roof mounted, external use.

= rectangular bottom inlet  spigot & opposed outlet grilles.

= Case size A,B,C & D

= Fan performance curve number.

3 or 1 = 3: 3ph 400v, 1: 1 ph 230v 

= Microsave integral fan control.

= Mains fan control.

QTR B   A   1    3   C = Quietwin, roof mounted, bottom inlet, 
case size A,  3 phase and Mains control.

Coding (bottom inlet units sizes A,B & C).

Coding (end inlet units sizes A,B & C).

QTR= Quietwin, roof mounted, external use.

= Circular end spigot & opposed outlet grilles.

= Square end spigot & opposed outlet grilles.

= Case size A,B,C & D

= Fan performance curve number.

3 or 1 = 3: 3ph 400v,  1: 1 ph 230v 

= Microsave integral fan control.

= Mains fan control.

QTRC A  1    3    M = Quietwin, roof mounted, circular end inlet 
spigot, case size A,  3 phase and Microsave control.

Содержание QUIETWIN QTR

Страница 1: ...ames are supported on the base by resilient mountings allowing the fan unit to be operated with out the need for separate anti vibration fan case mountings The units incorporate two independent motors...

Страница 2: ...he installer the lower edge of the casing has an internal skirt allowing the unit to be located on an upstand or prefabricated curb if desired See prefabricated curb details on page 5 The unit should...

Страница 3: ...23 3 1400 1 5 3 7 18 5 96 4 CASE SIZE A Table 4 Start Run currents etc Electrical Details See table 3 4 5 Because the run and start currents depend upon the duty and asso ciated ductwork of an individ...

Страница 4: ...t Drive Twinfans continued Table 5 Start Run currents etc CASE SIZE B Table 6 Start Run currents etc CASE SIZE C Installation and Maintenance QUIETWIN QTR BELT DRIVE TWINFAN 4 General Electrical Weigh...

Страница 5: ...nit Support Base Removable top covers Unit support base Inlet spigot 2500 2315 200 1200 1200 200 min100 min 75 50 1790 2490 Unit Weight and Fixing Size D units For unit weights see electrical informat...

Страница 6: ...power control Figure 9b 6 3 YEAR WARRANTY The three year warranty starts from the date of delivery and includes parts and labour for the first year The labour element is subject to full free and safe...

Страница 7: ...the User Control is included inside the fan unit for delivery to site Take care not to misplace the item before installation Wiring Connections Supply 230V 1 Phase to terminals E N L in control module...

Страница 8: ...K Y RUN FAULT Low voltage Communications Cable Not used in this option MT AVI connection BL RD BK Y MICROSAVE USER CONTROL CONTROL MODULE IN FAN Single phase QUIETWIN with MICROSAVE control Link Link...

Страница 9: ...S Building Management System override control on off and system status Code Description CT A Auto duty sharing CT M Manual duty sharing Mains Control Options NOTE See relevant Installation Maintenance...

Страница 10: ...1 L2 N E H BL RD BK Y RUN FAULT 230v MAINS CONTROL 230v 1 phase supply Link Link NET CT AVI Audible Visual Indicator connection QUIETWIN FAN Three phase 230v Switched Live Connection twinfan operates...

Страница 11: ...es operate freely by locating the spindle and flap through the blower outlet aperture and carefully moving the flap A click will be heard when the switch operates See fig 11 NOTE Do not bend the flaps...

Страница 12: ...g switches operate freely by locating the spindle and flap through the blower outlet aperture and carefully moving the flap A click will be heard when the switch oper ates See fig 14 NOTE Do not bend...

Страница 13: ...30364 530373 530368 530372 530367 530373 530368 530372 530367 530373 530368 530374 530369 530373 530368 530374 530369 530375 530373 530368 530374 530375 530376 530374 530369 530375 530376 530374 53036...

Страница 14: ...e Directive Applied Harmonised Standards E50081 1 EN50082 1 EN60204 1 EN60335 2 80 Basis of Self Attestation Quality Assurance to BS EN ISO 9001 BSI Registered Firm Certificate No FM 149 Signature of...

Страница 15: ...37 EC Machinery Directive 93 44 EEC Amendment to the Machinery Directive Applied Harmonised Standards EN292 1 EN292 2 EN294 EN29001 Applied National Standards BS848 Parts One Two and Five Signature o...

Страница 16: ...tion 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate...

Отзывы: