OPUS(40/60/95)

Installation Manual

4.3 Electrical Consumption

Unit Size

Power Consumption (Watts)

FLC (amps)

OPUS40

14

0.11

OPUS60

43

0.32

OPUS95

72

0.60

4.4 PCB Details

 

SWL  N     L

 

Mains connection

NET connections for

Ecosmart devices

*(see note)

Volt free relay 

contacts 

or connection

Fault

for OPUS-RFI Run

Switch to activate

continuous trickle

Fan connections

Trickle

operation

switch

position

13 

View Inside Electronic Control Module With Cover Removed

4.5 Wiring

4.5.1 Simple Wiring

N

L

Room light

Fuse

2 Amp max

Switch

SWL

N

L

*Link

Isolator

14 

Simple Wiring

4.5.2 Wiring Using Run-On Timer And Enabler (Integral PIR, 
Humisen, ES-Humidistat etc.) 

SWL

N

L

Room light

Switch

Fuse

2 Amp max

N

L

Isolator

15 

Wiring Using Run-On Timer And Enabler (Integral PIR, Humisen, 
ES-Humidistat etc.)

5.0 COMMISSIONING

For commissioning purposes, the unit has a miniature control panel 
mounted in its fascia hidden behind the front cover facilitating high and 
low speed adjustment (trickle and boost) together with run on timer 
(1- 60minutes).

The front cover is removable without the aid of tools. Any adjustments 
shall be quickly and easily achieved with a standard screwdriver. The 
control panel also has status indication lamps visible behind the corner 
“window”.

Run and standby versions shall have auto changeover and duty share 
as standard, the fan shall changeover every twelve hours of run time to 
maximise the unit’s effective life span. All models shall have foam filters 
as standard.

6.0 CONTROLS

The unit has the following functions integrally mounted within on a 
purpose made PCB, all such components are pre-wired and factory 
fitted by the manufacturer.

Min speed: 

Used to regulate trickle speed. Can be disabled    

 

 

using switch (Figure 13).

Max speed: 

Used to regulate full speed. Adjustable.

Run-on timer: 

1 to 60 minutes.

7.0 MAINTENANCE

Before any maintenance or cleaning operation, switch off the fan 
and disconnect from the main power supply.

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

Even with optional filtered extract grilles fitted, some dust, fluff etc. 
will pass through the filter, and which if allowed, will build up internally 
on motors and impellers, shortening the life of the unit and, in severe 
cases, leading to overheating of the motors. 

Consequently, it is strongly recommended that all units are inspected 
and cleaned every year.

The front cover can be removed and cleaned with water and a mild 
detergent using a soft cloth and the motor fan assembly can be cleaned 
with a dry brush or dry cloth. Ensure the unit does not come into 
contact with any kind of liquid or solvent. If this should occur, contact a 
qualified technician before reassembling the fan. 

To clean the filter (if fitted), remove from the unit and wash in tepid 
water to which a little mild detergent has been added. Shake out the 
excess water and allow the filter to dry naturally, replace when dry.

Содержание OPUS 40

Страница 1: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The replacement cord must be of the same technical specification as the original cord or gre...

Страница 2: ...r environmental air Nuaire would always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The Nuaire range of Opus 230V fa...

Страница 3: ...nge to inner case screw 3 5 x 9 5 4 off Rear spigot to inner case screw 3 5 x 6 5 2 off Rear spigot blanking plate to inner case 3 5 x 6 5 2 off Grille section to inner case 3 5 x 19 4 off 6 Internal...

Страница 4: ...M5 screws Stud wall 8 Recess Mounted In Stud Wall For applications including stud walls and ceilings that require top spigot configuration not suitable for Opus 95D units 1 Unpack the unit and compon...

Страница 5: ...cables or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables 4 1 Ecosmart Control Connections 4 1 1 Net Connections The IDC plug in...

Страница 6: ...l changeover every twelve hours of run time to maximise the unit s effective life span All models shall have foam filters as standard 6 0 CONTROLS The unit has the following functions integrally mount...

Страница 7: ...when the product reaches its end of life Fans motors controls actuators cabling and other electrical components can be segregated into WEEE recycling streams Sheet metal parts aluminium extrusion hea...

Страница 8: ...8 27 01 22 Document Number 671398 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk OPUS 40 60 95 Installation Manual NOTES...

Отзывы: