Installation Manual

3.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

3.1 Surface Mounted Installation

Rear mounted 

spigot

100 dia.

Surface Mounted In Cavity Wall

1. Unpack the unit and components. Discard the top spigot (040918), 

rear blank (040917) and recess flange (040919). Remove the front 
cover/grille and disconnect the motors from the control circuit 
board, noting their orientation. Rotate the yellow retaining clip and 
remove the fan assembly. Leaving the control unit in place, remove 
the top section only.

2. Use the base is a template mark the discharge spigot and mounting 

holes onto the surface.

3. Core cut the hole for the spigot to 100mm diameter.

4. Run suitable cable into the unit, noting the wiring should be for a 

fixed wired installation.

5. Run any ancillary wiring into the knock-out “square”.

6. Secure the case to the surface taking care not to twist or distort the 

case.

7. Connect all wiring (Section 4.5) and re-fit top section of control unit. 

Re-fit fan assembly and connect motors to control board. Rotate 
yellow clip to lock in place.

8. Complete the installation by securing the front cover and fitting any 

filters and test-run the unit. 

9. Adjust control settings as required.

3.2 Recess Mounted With Top Spigot Installation

 

Top mounted spigot

of mounting 

frame

Side bracket 

3 x M5 

screws

Stud wall

Recess Mounted In Stud Wall

For applications including stud walls and ceilings that require top spigot 
configuration 

(not suitable for Opus 95D units).

1. Unpack the unit and components. Discard the rear spigot (040954), 

top spigot blank (040921) and outer casing (040915). Fit the recess 
flange (040919) and rear spigot blank (040917). Remove the front 
cover/grille and disconnect the motors from the control circuit 
board, noting their orientation. Rotate the yellow retaining clip and 
remove the fan assembly. Leaving the control unit in place, remove 
the top section only.

2. The unit should not be mounted directly to a partition wall / ceiling 

but a suitable frame should be erected to secure the mounting 
frame kit to (Figure 10).

3. Run suitable cable into the unit, noting the wiring should be for a 

fixed wired installation.

4. Run any ancillary wiring into the knock out “square”.

5. Secure the case to the frame using the machine screws provided 

taking care not to twist or distort the case.

6. Connect all wiring (Section 4.5) and re-fit top section of control 

unit. Re-fit fan assembly and connect motors to control board. 
Rotate yellow clip to lock in place.

7. Complete the installation by securing the front cover and fitting any 

filters and test-run the unit.

8. Adjust control settings as required.

Fan Unit Rotated for Top Spigot Configuration 

(Not Suitable 

for Opus 95D Units)

Top mounting

spigot

blank

Rear spigot

Recessed mounting

flange

Motor/fan unit 

assembly rotated 

10 

Recess Mounting Kit In Wall Aperture With Top Spigot 
Configuration

Fan unit top spigot 

Cut bracket flush with

mounting surface of wall

Fan Unit

An aperture of 310mm x 220mm 

is required for fan and mounting kit

Recessed mounting flange

MS screws

Self tapping screws x 3

Содержание OPUS 40

Страница 1: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The replacement cord must be of the same technical specification as the original cord or gre...

Страница 2: ...r environmental air Nuaire would always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The Nuaire range of Opus 230V fa...

Страница 3: ...nge to inner case screw 3 5 x 9 5 4 off Rear spigot to inner case screw 3 5 x 6 5 2 off Rear spigot blanking plate to inner case 3 5 x 6 5 2 off Grille section to inner case 3 5 x 19 4 off 6 Internal...

Страница 4: ...M5 screws Stud wall 8 Recess Mounted In Stud Wall For applications including stud walls and ceilings that require top spigot configuration not suitable for Opus 95D units 1 Unpack the unit and compon...

Страница 5: ...cables or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables 4 1 Ecosmart Control Connections 4 1 1 Net Connections The IDC plug in...

Страница 6: ...l changeover every twelve hours of run time to maximise the unit s effective life span All models shall have foam filters as standard 6 0 CONTROLS The unit has the following functions integrally mount...

Страница 7: ...when the product reaches its end of life Fans motors controls actuators cabling and other electrical components can be segregated into WEEE recycling streams Sheet metal parts aluminium extrusion hea...

Страница 8: ...8 27 01 22 Document Number 671398 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk OPUS 40 60 95 Installation Manual NOTES...

Отзывы: