Units should always be positioned with sufficient space 

to allow removal of the access covers and subsequent 

removal of fan and motor assemblies etc. 

The installation must be carried out by competent

personnel in accordance with the appropriate authority and

conforming to all statutory and governing regulations.

2

Unit Code

Prefab Code

A

B

C

D

E

F

G

NALTF 9-10

NALPFC 4B

767

767

947

947

837

837

75

NALTF 11-12

NALPFC 5B

973

973

1203

1203

1064

1064

100

NALTF 13-17

NALPFC 6B

1169

1375

1399

1605

1268

1471

100

Unit

Prefab

Code

Curb Code

A

B

C

NALTF 9-10

NALPFC 4B

917

917

250

NALTF 11-12

NALPFC 5B

1173

1173

250

NALTF 13-17

NALPFC 6B

1374

1580

250

NALTF/TRF 

Roof and Plantroom Twinfans

15. 05. 17. Leaflet Number 671269

Roof Opening Dimensions

Figure 6.

Figure 5.

Note: Prefabricated curbs can be used to support internal or external units.

Typical Roof Upstand for NALTF 18-24

Figure 7.

680           700 Spigot

640

50mm Spigot

1

2030

1183

1550 min

Curb

1850 max

165 louvre

1200 Spigot

2313

700 Spigot

210

1200 Spigot

2140 max

150

Curb

3.0 Installation

Units must not be installed at an angle over 5

o

from the 

horizontal (to ensure the backdraught shutters operate 

satisfactorily). Units must be installed with the access panel

on top, never up-side-down. 

Ductwork connections must be airtight to prevent loss of

performance. 

The method of mounting used is the total responsibility of

the installer. The lower edge of the casing has an internal

skirt allowing the unit to be located on an upstand or 

prefabricated curb if desired. The units must be securely

screw fixed to the upstand/curb to prevent vibration and/or

wind damage.

It is the installers responsibility to drill the case to provide

access for the electrical cables. Care should be taken not to

damage internal components and the cable entry must be

properly sealed. NOTE: on bottom inlet units the electrical

cabling may be routed up through the bottom inlet spigot.

Upstand Details

Details of roof opening dimensions etc required and basic

construction of a builders upstand etc are shown below for

typical concrete and decking roof installations.

Testing after Installation

Ensure that the Fan unit and any specified controls are 

fitted securely according to the instructions.

Switch on the mains supply. Push the test button to run

each fan and check that they run satisfactorily.

If a switched live signal is used, activate this signal and

check that the fan runs. De-activate the switched live signal

and check the run-on-time; adjust if necessary.

Adjust the maximum and minimum airflow (if required) by

following the commissioning procedures.

Prefabricated Curb

CODES: NALPFC (typical)

Manufactured in 

aluminium alloy these 

curbs will reduce design 

work and guarantee correct 

unit mounting when on site.

Note: Upper faces of curb are fitted with robust sealing

strip.

Prefabricated curb dimensions

Содержание NALTF Series

Страница 1: ...sing is manufactured from heavy gauge Aluzinc aluminium zinc coated mild steel A full size internally lined access panel is fitted to the top face and is fully detachable for inspection purposes The motor plate and frames are supported on the base by resilient mountings allowing the fan unit to be operated without the need for separate anti vibration fan case mountings The units incorporate two in...

Страница 2: ...d of mounting used is the total responsibility of the installer The lower edge of the casing has an internal skirt allowing the unit to be located on an upstand or prefabricated curb if desired The units must be securely screw fixed to the upstand curb to prevent vibration and or wind damage It is the installers responsibility to drill the case to provide access for the electrical cables Care shou...

Страница 3: ...TRF 9 15 and NALTF 9 15 only Controls for NALTF NALTRF 9 15 The NALTF NALTRF 9 15 fan units incorporate an integral auto changeover controller which provides 12 hour duty share operation and automatic selection of the standby fan should the duty fan fail Fault indication to an external device is provided via volt free contacts of a relay Note the relay is energised when no fault is present Note It...

Страница 4: ...kg Changing a Drive Belt To replace a belt remove the two bolts from the motor mounting furthest from the fan and slacken the remaining two bolts Lift the motor plate and remove the belt Replacing the belt is the reverse of this procedure Figure 12 Adjusting the Drive Belts larger units Adjusting Drive Belt Tension larger units All belt drive units incorporate belt tensioning devices To adjust the...

Страница 5: ... of the part required 7 0 Warranty The unit has a one year warranty The warranty starts from the date of delivery and covers faulty materials or workmanship and includes parts and labour The labour element is subject to full free and safe access to the equipment as recommended by the CDM regulations This warranty is void if the equipment is modified without authorisation is incorrectly applied mis...

Страница 6: ...s given for the individual product the following general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of ...

Отзывы: