background image

5

15. 03. 21. Document Number  671838

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO4-1Z

Installation Manual

3.8 ADF 2010 Ventilation Calculations Design of MVHR 
Systems

The MVHR system has been sized for the winter period. Additional 

ventilation may be required during the warmer months and it has 

been assumed that the provisions for purge ventilation (e.g. openable 

windows) could be used.

Step 1: 

For any design air permeability, determine the whole dwelling 

ventilation supply rate from 

Whole Dwelling Ventilation Rates table.

As an alternative where the design air permeability is intended to be 

more than (>) 5m3/(h.m2) 50 Pa, allow for infiltration for all dwelling 

types by subtracting from the whole dwelling ventilation supply rate 

from Whole Dwelling Ventilation Rates table;

 0.04 x gross internal 

volume of the dwelling heated space (m3).

Step 2:

 Calculate the whole dwelling extract ventilation rate by 

summing the individual room rates for ‘minimum high rate’ 

from ADF 

2010 - Extract Ventilation Rates table.

(For sanitary accommodation only, as an alternative, the purge 

ventilation provisions given in ADF 2010 can be used where security is 

not an issue. In this case ‘minimum high extract rate’ for the sanitary 

accommodation should be omitted from the step 2 calculation).

Step 3:

 The required airflow rates are as follows:

The maximum whole dwelling extract ventilation rate (e.g. boost) 

should be at least the greater of step 1 and step 2. Note that the 

maximum individual room extract rate should be at least those 

given in 

ADF 2010 - Extract Ventilation Rates table.

The minimum air supply rate should be at least the whole building 

ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.
For further information refer to “Domestic Ventilation Compliance 

Guide” www.planningportal.gov.uk/buildingregulations/approved 

documents/partl/compliance.

3.8.1 Pre Commissioning MRXBOX MVHR Units

MRXBOX units are designed to ventilate the whole dwelling and must 
not be used during site construction or the clean-up period. Cement 
and plaster dust can be abrasive and can affect fan performance 
and reliability. Please ensure that the filters are checked prior to 
commissioning to ensure there is no build-up of dust or debris.

While the property is drying out, very high moisture levels are likely 
to occur. Therefore it is advisable that if the installation and building 
works are complete the unit is left running. If the building works are 
not complete please close the air valves or cover up the air valves to 
prevent condensation forming in the ductwork and the MRXBOX unit 
due to natural migration of warm air.

3.9 Dimensions (mm) 

10 

Unit Dimensions

789

14

56

52

191

290

200

485

672

If ancillary distribution box MRXBOX-DB4 is to be used 
refer to documentation supplied with MRXBOX-DB4 
for additional infomation as requirements will differ.

Condensate drain position for standard hand 
configuration. For opposite hand configuration, 
position will be mirrored to other side.

Содержание MRXBOXAB-ECO4-1Z

Страница 1: ...hildren shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains important information on the safe and appropriate assembly transport commissionin...

Страница 2: ... long term damage to the unit and building fabric This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the applianc...

Страница 3: ... insulated to prevent freezing Nuaire recommend MVHR DRAIN be used as the primary condensate take off Figures 8 and 9 3 5 Extract Input Areas The unit is designed to extract air from all wet rooms e g bathroom kitchen en suite utility room with sink WC s do not need to be ventilated if openable windows are fitted Supply air should be to all habitable rooms e g bedrooms and lounge Extract input gri...

Страница 4: ...nd the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 220 x 90mm rectangular ducting should be used refer to dwelling design drawing Figures 11 12 Ducting...

Страница 5: ...e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in ADF 2010 Extract Ventilation Rates table The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide www p...

Страница 6: ... with min 5 o fall running to SVP MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP 3 10 2 Rectangular Ducting 12 Typical Rectangular Ducting Arrangement For Wall Mounted Units Air supply to lounge in ceilings via AirValve Extract air from kitchen bathroom in ceilings via AirValve Exhaust air from kitchen bathroom to outside via louvre grille Mini...

Страница 7: ...g regulations 4 2 Wiring Diagrams Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm 4 2 1 Unit Only MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 5A Fuse BS1362 2 Pole Isolator 14 Wiring Di...

Страница 8: ...compliance guide www planningportal gov uk building regulations approved documents partf associated A calibrated moving vane anemometer and hood will be required to carry out commissioning 7 Adjustment valves should be locked in place to prevent further adjustment 8 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect ...

Страница 9: ... right is reserved to make such changes without prior notice 6 4 Frost Protection In the event of the intake air temperature at the unit dropping below the predetermined set point 5 C as standard the supply fan will reduce to minimum speed once the temperature rises above the set point the fan will return to its commissioned speed Frost protection will only activate after ten days of continuous ru...

Страница 10: ...10 15 03 21 Document Number 671838 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z Installation Manual NOTES ...

Страница 11: ...11 15 03 21 Document Number 671838 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z Installation Manual NOTES ...

Страница 12: ...12 15 03 21 Document Number 671838 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z Installation Manual NOTES ...

Отзывы: