background image

3

28. 07. 21. Document Number  671856

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO(3/5)-(SC/SW)

Installation Manual

3.1.2 Option 2 - Non-Solid Wall

If it is not practical to use a solid wall, the MVHR unit should be 
fixed to a stud partition with a 25mm minimum thickness MDF 
panel solidly fixed behind the plasterboard.

If fixing to a stud wall the MDF panel should extend, width wise, over a 
minimum of 3 vertical studs with centres of no more than 400mm. Add 
additional vertical supports if necessary. 

Height wise, ideally, the MDF panel should extend from floor to ceiling 
but as a minimum should be a least 2m high.

Fix the mounting bracket to the wall (Figure 3) and use the wall 
mounted bracket to mount the unit on (Figure 4).

 

Non-Solid Wall Mounted Unit Installation

Ducting in the 

ceiling void.

mounted in a 

Side view of unit 

a stud partition 

cupboard fixed to 

with the 25mm 

MDF fixed behind 

MVHR-DRAIN

the plasterboard.

Condensate drain,

uninsulated drain 

pipe with min 5

o

fall running to SVP.

Valve in ceiling.

3.2 Loft Mounting

3.2.1 Option 1 - Tank Stand

The MVHR unit should be positioned on a tank stand using the 
Anti-vibration tray assembly discarding the angle brackets. 

Anti-vibration tray assembly (MRXBOX-AV(3/5)) is to be purchased 
separately.

 
 
 

Tank Stand Loft Mounted Unit Installation

3.2.2 Option 2 - Angled Brackets

The MVHR unit should be positioned on a 25mm minimum 
thickness MDF panel that is vertically fixed across the roof trusses 
to form a solid false wall. 

Add additional vertical supports if necessary. Use the Anti-vibration 
tray assembly (MRXBOX-AV(3/5)) including the angle brackets, to be 
purchased separately.

 
 

Angled Brackets Loft Mounted Installation

3.3 Off-Site Cupboard Construction

For off-site constructed cupboards adequate support must be included 
in the steel frame to support the weight of the units in operation and to 
allow for dynamic loads in transit to site.

If the unit is to be bolted to a plywood or MDF backboard then this 
must be of sufficient thickness to support the unit’s weight and 
through-bolted with washers fitted to spread the load. 

The cupboard manufacturer should satisfy themselves that the method 
of mounting is sufficient to support the weight of the unit in operation 
and transit to site.

The top of the unit is to be suitably braced within the cupboard for 
transport.

3.4 Condensate Drain

The condensate must be discharged under a water level in a U-trap 
drainpipe or an alternative drain method which acts as an airlock. This 
condensate discharge connection is suitable for 21.5mm Ø overflow 
pipe. Solvent cement should be used to make the joint. 

If using a U-trap please ensure the U-trap has been filled to a suitable 
level of water to avoid any air locks. If the condensation pipe is fitted in 
an unheated space the pipe should be in insulated to prevent freezing.

An MVHR-DRAIN is recommended for use as the primary 
condensate take-off (Figures 10 and 11).

Содержание MRXBOXAB-ECO3-OHSW

Страница 1: ... or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information Thi...

Страница 2: ...e unit and building fabric 1 Airflow Through unit Standard Unit Extract air from house Intake air Exhaust air from outside to outside from house to house Supply air Intake air from outside Extract air from house Supply air to house Exhaust air from house to outside 2 Airflow Through OH unit Opposite Hand Unit Extract air from house Intake air Exhaust air from outside to outside from house to house...

Страница 3: ...uld be positioned on a 25mm minimum thickness MDF panel that is vertically fixed across the roof trusses to form a solid false wall Add additional vertical supports if necessary Use the Anti vibration tray assembly MRXBOX AV 3 5 including the angle brackets to be purchased separately 8 Angled Brackets Loft Mounted Installation 3 3 Off Site Cupboard Construction For off site constructed cupboards a...

Страница 4: ...led taut A maximum of 300mm should be used on each leg To prevent condensation on the outside of the outside air inlet duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended I...

Страница 5: ... as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in ADF 2010 Extract Ventilation Rates table The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further ...

Страница 6: ... Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct 3 10 2 Rectangular Ducting 14 Typical Rectangular Ducting Arrangement For Wall Mounted Units Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air from outside via air brick All duct betwe...

Страница 7: ...connected to the underside of the MVHR unit within The cable should be fed through rubber blanking plug to provide a seal when the cover is re fitted 4 3 Wiring Diagrams 4 3 1 Unit Serving Kitchen And Bathroom 16 Wiring Diagram Unit Serving Kitchen And Bathroom ECO3 3A Fuse BS 1362 ECO5 5A Fuse BS 1362 MAINS 230V 50Hz Light Room Light Switch Double Pole N L 3 Pole Isolator Kitchen Switch Blue Brow...

Страница 8: ... to solely boost the unit Additional switch should be used local to the wet rooms Section 4 3 3 5 2 Status Indication The status of the unit is indicated by a series of LED s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher speed setting has been triggered by an external source such as an ES PIR2 etc 20 Unit Control On Front Pan...

Страница 9: ...ulations and guidelines taking into account all site based risks 9 0 AFTER SALES AND REPLACEMENT PARTS For technical assistance or further product information including spare parts and replacement components please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the part number is not known please give a full descrip...

Страница 10: ...10 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Страница 11: ...11 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Страница 12: ...12 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Отзывы: