Installation and Maintenance

MRXBOXAB-ECO-LP1SW Mechanical Ventilation Unit with Heat Recovery

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 
2010.

2. The unit is supplied with independent control for both normal and 

boost airflows. (see fig. 10).

3. Correct commissioning is essential to ensure the ventilation air 

flowrates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption.

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 
 
A calibrated moving vane anemometer and hood will be required to 
carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment.

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The label covering the control has an adhesive panel 
which should be removed post commissioning to prevent tampering.

Control module

+

-

-

+

- +

-

+

- +

Power

Post commissioning remove

adhesive backing under 

this section

060905

Ventilation Controls

For commissioning: 

refer to user manual

+

-

8.0 COMMISSIONING

IMPORTANT

The filters fitted inside the unit are protected with a plastic film. Prior to 
commissioning remove the covers (fig. 13), take off the film and replace.

Figure 15.  PCB inside enclosure.

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

9.0 STATUS INDICATION

The status of the unit is indicated by a series of LED’s on the control box 
cover. The variants are listed below.

9.1 Integral automatic HX bypass (AB units only)

Intake and extract temperatures are monitored at the point the 
airflows enter the unit, if the range falls within the set parameters the 
bypass damper is opened automatically to target an indoor comfort 
temperature all year round.

9.2 Summer / Winter Switch

When the switch position is set to Summer, the integral automatic 
summer bypass is fully operational. In the alternative Winter position, 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode. 

9.3 Frost Protection

In the event of the intake air temperature at the unit dropping below 
the predetermined set point (-5°C as standard) the supply fan will 
reduce to minimum speed, once the temperature rises above the set 
point the fan will return to its commissioned speed.

Please note this mode will only activate after ten days of continuous 
run time. If commissioning of the unit is outside of this timeframe 
please notify the after sales department prior to site visit.

10.0 MAINTENANCE/CLEANING 
 
 
 
 

IMPORTANT

Isolation - Before commencing work make sure that the unit, 

switched live and control are electrically isolated from the mains 

supply and switched live supply.

Nuaire recommend that filters are inspected every 6 months and 
replaced every 12 months. A flashing LED (section 9.0) will indicate that 
a filter change is required. This indication repeats every 12 months and 
will turn off automatically after 5 Days.

Remove the filter covers on the front panel of the unit by gripping the 
two circular tabs either end of the filter covers and pulling away from 
the unit. The filter can now be extracted by pulling the removal loop on 
the front edge of the filter. Once the filters have been inspected return 
or replace them as necessary. 

Inspect the heat exchanger every 5 years. Generally check for damage 
and security of components. Refit cover.

7.2 Optional Controls 

For further information contact Nuaire on 02920 858 400.

Note: The display on the unit control panel will not indicate when a 
higher speed setting has been triggered by an external source, such 
as an ES-PIR2 etc.

Содержание MRXBOXAB-ECO-LP1-OHSW

Страница 1: ...that they do not play with the appliance 2 0 INSTALLATION Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing...

Страница 2: ...pipe cutter 2 Remove any swarf from the end of the plastic pipe Ream the copper pipe end to remove any burr and file if necessary to remove any external sharp edges Mark the socket depth on the pipe a...

Страница 3: ...imum high rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ex...

Страница 4: ...1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceil...

Страница 5: ...mper 1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in...

Страница 6: ...only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen...

Страница 7: ...Intake and extract temperatures are monitored at the point the airflows enter the unit if the range falls within the set parameters the bypass damper is opened automatically to target an indoor comfo...

Страница 8: ...on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintaine...

Отзывы: