background image

2

nuaire.co.uk 

029 2085 8400

19. 08. 19. Leaflet Number  671858

Installation and Maintenance

MRXBOXAB-ECO-LP1SW Mechanical Ventilation Unit with Heat Recovery

ducting in 

204 x 60mm 

ceiling void.

in ceiling.

Side view of unit 

mounted in the ceiling void.

Air valve 

Figure 4. Typical side view example of a (standard unit) mounted in a 
ceiling void using 204 x 60mm rectangular ducting and air valves.

2.1 Condensate Drain Installation

1. Unit comes complete with external drain pipe (21.5mm waste 

pipe). Use conventional plumbing connections to link up with 
U-trap or alternative drain method (Solvent cement connections 
or compression fit connections are recommended). The condensate 
must be discharged under a water level in a U-trap drainpipe or an 
alternative drain method which acts as an airlock.

2. This condensate discharge connection is suitable for 21.5mm dia. 

overflow pipe. Solvent cement should be used to make the joint.

3. If using a U-trap please ensure the U-trap has been filled to a 

suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the pipe 

should be in insulated to prevent freezing.

Nuaire recommend MVHR-DRAIN be used as the primary condensate 
take-off (see fig. 5 and 6).

CORRECT

INCORRECT

Flow

Side elevation

When installed horizontally the ribs must be at the bottom to 
ensure  correct operation. 

Figure 5. Typical side view example of a (standard unit) mounted in a 
ceiling void using 204 x 60mm rectangular ducting and air valves.

Figure 6. Typical side view example of a (standard unit) mounted in a 
ceiling void using 204 x 60mm rectangular ducting and air valves.

2.1.1 Fixing

Offer up the MVHR-DRAIN inlet to the threaded tail of the appliance 
waste outlet or MVHR-DRAIN knuckle or running adaptor, and tighten 
the threaded cap sufficiently hand-tight to provide a water-tight seal 
(check that the cap screws on square and does not ‘cross-thread’). 
When the screwed cap is tight, the MVHR-DRAIN body is secure.

1. Cut the pipe to length, allowing for the full compression socket 

depth (using an appropriate pipe cutter, such as a Hepworth ratchet 
pipe cutter).

2. Remove any ‘swarf’ from the end of the plastic pipe. Ream the 

copper pipe end to remove any ‘burr’, and file if necessary to remove 
any external sharp edges. Mark the socket depth on the pipe, and 
check that the pipe section to be jointed is free of any surface 
damage which may affect the joint seal.

3. Unscrew the cap from the MVHR-DRAIN outlet, and slide the cap 

and rubber seal onto the pipe.

4. Insert the pipe end fully into the socket.

5. Slide the rubber seal and screwed cap up against the face of the 

socket, and tighten the cap sufficiently hand-tight (check that the 
cap is square to the body and does not ‘cross thread’). Hand tight 
should be adequate to form a proper seal.

2.2 Extract/Input Areas

The unit is designed to extract air from all wet rooms e.g. bathroom, 
kitchen, en-suite, utility room (with sink).

WC’s do not need to be ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and lounge. 
Extract / input grilles should be adjustable valve types (not supplied).

External grilles must have a minimum free area of 12,250 mm2.

2.3 Ducting

Before commencing ducting installation reference should be made 
to building regulations document “Domestic ventilation compliance 
guide”. This document supports ADF2010 and details installation, 
testing and commissioning of all ventilation systems.

It is recommended that rigid ducting must be used it all times. Flexible 
ducting has a very high resistance and it is impossible to calculate 
how much resistance will be on a system if used. If used the flexible 
ducting must be kept to a minimum and should always be pulled taut. 
A maximum of 300mm should be used on each leg.

To prevent condensation on the outside of the outside air inlet duct and 
the air outlet duct from the MRXBOXAB-ECO-LP1, these ducts should 
be insulated.

Ducting must be installed in such a way that resistance to airflow is 
minimised. Bends should be kept to a minimum.

A minimum distance of 300mm between the appliance and any bends 
in ductwork is recommended.

204 x 60mm rectangular ducting should be used. (Refer to dwelling 
ducting design drawing, figure 6 on page 4 for further information).

Ducting joints must be sealed with silicone type sealant and needs 
to be taped. Ducting shall be adequately and reliably fixed to the 
appliance.

Содержание MRXBOXAB-ECO-LP1-OHSW

Страница 1: ...that they do not play with the appliance 2 0 INSTALLATION Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing...

Страница 2: ...pipe cutter 2 Remove any swarf from the end of the plastic pipe Ream the copper pipe end to remove any burr and file if necessary to remove any external sharp edges Mark the socket depth on the pipe a...

Страница 3: ...imum high rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ex...

Страница 4: ...1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceil...

Страница 5: ...mper 1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in...

Страница 6: ...only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen...

Страница 7: ...Intake and extract temperatures are monitored at the point the airflows enter the unit if the range falls within the set parameters the bypass damper is opened automatically to target an indoor comfo...

Страница 8: ...on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintaine...

Отзывы: