NuAire MRXBOX95B-LH2 Скачать руководство пользователя страница 3

3

24. 01. 17. Leaflet Number 671500

Installation and Maintenance

MRXBOX95B-LH1/LH2 Mechanical Ventilation with Heat Recovery & Summer Bypass

2.2 Installing Nuaire CONTRAP

In ducted ventilation systems, condensation will occur when

warm, humid air extracted from your bathroom, shower, kitchen

or utility room hits the cooler surface of the ventilation duct. 

If the extracted air is sufficiently cooled, the moisture will 

condense back to water and become trapped in the ducting,

potentially causing damage to the fan.

Nuaire’s CONTRAP is simply connected to the system as part

of the vertical duct run and an internal gutter within the trap

collects the moisture and then drains it out through a standard

overflow pipe to the outside. This ensures that the moisture

cannot enter a potentially hazardous area. 

Use insulated ducting

By using insulated ducting, the inner duct layer stays warmer,

and therefore keeps the extracted air at a higher temperature. 

This allows the water to condense outside the building and not

in the ducting.

Any air intake terminal MUST be installed in accordance

with the appropriate regulation. 

As a guide, the BS5440 series of British Standards

deals with this issue and currently states that an air

intake must be at a minimum distance of 300mm from 

a gas boiler balanced flue. Installers are advised to 

be aware of the requirements of this standard when

installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at

least 300mm apart.

Figure 4. Typical MVHR ducted arrangement for a loft mounted unit using the Nuaire condensation trap 125mm dia. (CONTRAP 125).

Nuaire 

CONTRAP 

condensation 

trap. 

To soil stack

or soffit vent.

Insulated.

Tile Vent.

Condensed water 

forming inside 

the duct 

Insulated.

Insulated.

2.3 Extract/input areas

The unit is designed to extract air from all wet rooms 

e.g. bathroom, kitchen, en-suite, utility room (with sink).

WC’s do not need to be ventilated if openable windows are

fitted. Supply air should be to all habitable rooms e.g. bedrooms

and lounge. Extract / input grilles should be adjustable valve

types (not supplied).

2.4 Ducting

1.

If the unit has been specified as SAP appendix Q installation

the use of flexible is prohibited. If flexible ducting is to be

used it should be kept to a minimum and should always be

pulled taught.

2. The unit is supplied with 125mm dia. outlets.

To prevent any condensation on the ducting it should be

insulated externally vapour-proof as far as the unit.

3. Ducting layout plans should be adhered to if available.

4. It is recommended that 125mm dia. or 204 x 60mm ducting be

used and the number of 90 Deg bends be kept to a minimum.

5. Ducting joints must be sealed with duct tape and/or silicone

sealant.

For further information refer to Building Regulations Part F and

BRE appendix Q website.

IMPORTANT: When using a “T” Piece to connect the CONTRAP

drainage and the MVHR drain pipework the MVHR drain 

must

always be fitted before the “T” Piece

to prevent condensate

from feeding back into the MVHR system. 

To SVP 

“T” piece 

MVHR Drain 

To unit 

To CONTRAP 

Содержание MRXBOX95B-LH2

Страница 1: ...switch This opens the damper via a wax actuator When the switch signal is de activated the unit returns to its original state air through the heat exchanger Outside air supplied through the bypass is...

Страница 2: ...MVHR DRAIN outlet and slide the cap and rubber seal onto the pipe 4 Insert the pipe end fully into the socket 5 Slide the rubber seal and screwed cap up against the face of the socket and tighten the...

Страница 3: ...larly supply and extract air grilles should be at least 300mm apart Figure 4 Typical MVHR ducted arrangement for a loft mounted unit using the Nuaire condensation trap 125mm dia CONTRAP 125 Nuaire CON...

Страница 4: ...m spigot 450 VIEW FROM TOP Condensate drain alternative position 21 5mm dia condensate drain 21 5mm dia condensate drain alternative position SIDE VIEW non controls 3 0 Dimensions mm Figure 6 Filter F...

Страница 5: ...ce with current IEE wiring regulations See fuse rating MAINS 230V 50Hz Room light Light switch Double Pole N L 3 Pole isolator Kitchen switch Green yellow Blue Brown Black Summer bypass switch Grey on...

Страница 6: ...de of the unit to allow access for maintenance purposes 1 Replace filters every 5 years Remove the top cover and slide out the two G4 filters fitted either side of the heat exchanger Replace with new...

Страница 7: ...eing affected 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be ar...

Страница 8: ...8 24 01 17 Leaflet Number 671500 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk...

Отзывы: