MRXBOX(AB)-ECO2-AE

Installation Manual

2.0 INTRODUCTION

The ECO2-AE wall mounted range of units are designed to offer 
improved sound levels and an aesthetically pleasing installation by 
housing a Mechanical Ventilation with Heat Recovery unit (MVHR) 
inside an acoustically lined enclosure.

The MVHR unit is fitted with two independent fans. Each fan has full 
speed control for background and boost ventilation rates. To recover 
heat from the extract air the heat exchanger block is utilised. The heat 
exchanger can recover up to 95% of the normally wasted heat. 

If the MVHR unit has integral automatic HX bypass (AB models 
only),

 the bypass damper shall open automatically via a wax actuator 

allowing the air to bypass the heat exchanger to deliver fresh filtered air 
during the warmer months.

 

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Airflow Through Unit (Opposite Hand Unit)

 

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Airflow Through Unit (Standard Hand Unit)

The unit must remain switched on at all times to maintain 
ventilation within the dwelling. Turning the unit off will cause long 
term damage to the unit and building fabric.

This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been given 
supervision or instruction concerning the use of the appliance by a 
person for their safety. Children should be supervised so that they 
do not play with the appliance.

3.0 MECHANICAL INSTALLATION

Installation must be carried out by competent personnel in accordance 
with the appropriate authority and conforming to all statutory 
governing regulations. All mains wiring must be in accordance with the 
current I.E.E. Regulations, or the appropriate standards. Ensure that the 
mains supply (Voltage, Frequency and Phase) complies with the rating 
label.

Please allow a minimum of 350mm in front of the enclosure.

The fan must be installed indoors, on a suitable wall away from direct 
sources of frost, heat and water spray or moisture generation.

For a vibration-free result the unit must be mounted to a non-
reverberant wall.

3.1 Transportation Fixings

To prevent damage during transportation the product is shipped 

with securing fixings, these can be found front and centre of the 

enclosure top panel (Figure 3). These must be removed before use, 

failure to do so will result in excessive vibration and noise. The 

screws removed can be discarded and replaced with rubber caps 

provided. 

 

Spigot fixing plate

Transportation fixings

Transportation Fixings

3.2 Wall Mounting

The unit is designed for wall mounting on a solid wall only, a gypsum 
block/plasterboard wall will not suffice. Examples of suitable 
installation are shown overleaf. The wall brackets supplied should be 
secured to the wall using suitable fixings (supplied by others) as per 
the dimensions given in Figure 4; the head of the chosen fixing should 
protrude no more than 8mm from the wall bracket. The enclosure 
assembly can then be lifted using suitable equipment and moved into 
position so it is sitting directly on the wall brackets (ensuring the rear 
panel of the enclosure is not in contact with the wall bracket fixings). 
The enclosure can be secured to the wall brackets using the 4x M8 
fixings supplied.

No part of enclosure should be in contact with the building structure, 
the only components that should be in contact are the wall mounting 
brackets.

Care must be taken to ensure the unit is installed true in all 3 
dimensions. Failure to do so may result in overflow from the 
internal condensation drip tray.

Wall Bracket Dimensions

25

25

656 crs

9.1 dia.

30

94

94

33

Содержание MRXBOX-ECO2-AE

Страница 1: ...unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user m...

Страница 2: ...ON Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations All mains wiring must be in accordance wit...

Страница 3: ...e Collar 9 Condensate Drain MVHR DRAIN Condensate Drain Uninsulated Drain Pipe With Min 5 Fall Running To SVP 3 2 1 Solid Wall Mounting Recommended The MVHR unit fixed to a solid wall construction usi...

Страница 4: ...40 series of British Standards deals with this issue and currently states that an air intake must be at a minimum distance of 300mm from a gas boiler balanced flue Installers are advised to be aware o...

Страница 5: ...very high moisture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please...

Страница 6: ...n pipe with min 5 o fall running to SVP Insulated extract duct 12 Typical Ducted Arrangement For A Wall Mounted Unit Using Circular Ducting 3 10 2 Rectangular Ducting Exhaust air from kitchen bathroom...

Страница 7: ...panel of the enclosure should be removed by loosening the two screws the Ecosmart cable can then be connected to the underside of the MVHR unit within The cable should be fed through rubber blanking...

Страница 8: ...ms 6 3 Status Indication The status of the unit is indicated by a series of LED s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher...

Страница 9: ...ing nylon corner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other...

Страница 10: ...10 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Страница 11: ...11 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Страница 12: ...12 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Отзывы: