background image

6

nuaire.co.uk 

029 2085 8400

30. 04. 19. Leaflet Number  671220

Installation and Maintenance

AXUS Circular Long Cased Axial Flow Fans

5.0 Setting To Work

IMPORTANT

Isolation - Before commencing work, make sure 

that the unit, switched live and Nuaire controls are 

electrically isolated from the mains supply.

Warning - Inverter Speed Control 

An inverter is used to provide speed control. When the 

fan is isolated, allow 5 minutes for the capacitors in the 

inverter to discharge before commencing any work on 

the unit.

IMPORTANT

Isolation - Before commencing work, make sure that the 

unit, switched live and Nuaire controls are electrically 

isolated from the mains supply.

Note that the volt free contacts are not fused. If these are used to 
power any external equipment, the installer must provide adequate 
fusing or other protections. 

5.1 Electrical

5.1.1 Using The Test Button

The test button allows the blower within the unit to be checked for its 
operation. If the fan is running already, press the button once to stop 
the fan, press again to switch on the fan. 

Note that the fan will return to normal operation after 30 seconds.

5.3 Settings

5.3.1 Setting The Maximum Airflow rate

Ensure the power supply is switched off and that a link wire is 
connected from the supply L to the SL terminal. Unplug all items 
connected to the ‘Net‘ connectors.

Switch on the power supply.

Wait for the fan to reach steady condition. 
Measure the airflow using standard commissioning instruments at 
a suitable point in the ductwork. 
If adjustment is required, rotate the pot marked ‘MAX’ to obtain 
the desired airflow. Remove the link wire if not required (fig. 7).

5.3.2 Setting The Minimum / Trickle Airflow Rate (Nomial 20%)

Repeat the same procedure as for maximum airflow above but 
without the link wire between supply L and SL terminal. Ensure the 
trickle switch is in the ‘ON’ position. Adjustment must be made on 
the pot marked ‘Min’.

Note that the minimum setting (nominally 20%) must be 
below the maximum setting; otherwise minimum setting will be 
automatically set to be the same as the maximum.

The minimum speed set is the trickle speed at which the fan 
operates.

Note: The working speed range of the user control and sensors is 
between the minimum and maximum set points.

5.2 LED Indication

PWR  

 

GREEN: Power on & OK.

Standby   

 LED on when fan is not running.

Fan 1  

 

GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2  

 

GREEN: Fan 2 is running, RED: Fan 2 faulty.

Heating*   

Not applicable, see note.

Cooling*   

Not applicable, see note.

Fault  

 

LED on when a fault is present on unit.

Frost*    

Not applicable, see note.

Tx  

 

LED on when the controller is transmitting data.

Rx  

 

LED on when the controller is receiving data.

* Note that the control panel is common to all the Ecosmart 
products and will have indicators for functions that are not 
available in this particular fan. However these indicators will not be 
illuminated.

Min 

= Minimum speed adjustment

Max 

= Maximum speed adjustment

SL runon 

= Switched live run-on

 

   timer adjustment

Trickle 

= Selects trickle running:

 

    0 = off, 1 = selected

Test 

= Test button 

  Max        SL runon

 Min          

Trickle

Test

1

0        

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx

Ecosmart

Connector

LED indicators 

Figure 12.  

Ventilation Mode

Local Control

0.00

OFF/ Trickle

0.25

Speed 1

0.50

Speed 2

1.50

Speed 3

2.50

Speed 4

3.50

Speed 5

4.50

Speed 6

5.50

Speed 7

6.50

Speed 8

7.50

Speed 9

8.50

Speed 10

9.50

Содержание Ecosmart

Страница 1: ...referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating plate 2 0 Handling The fan impeller is carefully balanced and centralised in the fan case it is therefore essential that great care is exercised when handling the unit Check the weight on the rating plate de...

Страница 2: ...ppropriate fasteners and for ease of installation the cover should be removed and the casing separated from the base If cooling fans are fitted they should be disconnected while installation takes place The cable connecting the Ecosmart control and the fan must be a screened power cable not exceeding 30 metres The screening must be earthed at both ends using the special cable glands supplied Bridg...

Страница 3: ...ELTA 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply 1U 1V 1W 2U 2V 2W Motor terminal box NOTE HIGH SPEED Supply 2U 2V 2W LINK 1U 1V 1W LOW SPEED Supply 1U 1V 1W Note individual wiring instructions are included with each unit 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 Low Speed High Speed L3 L1 L2 L3 460V 3 phase 60Hz supply 380V 3 p...

Страница 4: ...e Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5 2 4 6 U V W CONTACTER A1 A2 0V 0 10V BMS signal NET connection U V W E DP CL Connections to fan via screened power cable Purpose made glands are provided to earth the screening N RET Note Internal conn...

Страница 5: ...eened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farnell Part No 963 021 The system s response...

Страница 6: ...red airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire between supply L and SL terminal Ensure the trickle switch is in the ON position Adjustment must be made on the pot marked Min Note that the minimum setting nominally 20 must be below the maximum setting oth...

Страница 7: ...K mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales For technical assistance or further product information including spare parts and replacement components please contact the After Sales Department 6 1 Maintenance Intervals Maintenance should be carrie...

Страница 8: ...ne contaminants and unit orientation 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4...

Отзывы: